background image

22

02/22

8105-803B

B. Top Vent Adapter Installation

3 to 3 inch Top Vent Adapter

3 to 6 inch Top Vent Offset Adapter

1. Put a layer of high temperature silicone on the 3 inch 

(76mm) exhaust outlet. Do not put silicone inside of pipe 

(Figure 22.1)

.

2.  Slide the top vent adapter onto the rear exhaust outlet and 

adjust the assembly to a vertical position

 (Figure 22.1)

.

3.  Install the 4 mounting screws.
4.  Drill 2 holes with #26 drill bit through the rear exhaust 

outlet using the 2 holes already in the short horizontal 

pipe  in  the  top  vent  adapter  as  a  guide.  Install  the  2 

screws

 (Figure 22.1)

.

5.  Install the vent pipe into the top vent adapter.
6.  To clean the top vent adapter open the clean-out cover 

(Figure 22.1)

.

C. Rear Vent Adapter Installations

1. Put a layer of high temperature silicone on the 3 inch 

(76mm) exhaust outlet. Do not put silicone inside of pipe

 

(Figure 22.1)

.

2.  Slide the adapter onto the rear exhaust outlet and adjust 

the assembly to the appropriate position.

3.  Install the vent pipe into the adapter.

Clean-Out Cover

Rear Vent

Adapter

(811-0620)

Figure 22.2

 - Rear Vent Adapter (811-0620)

Clean-Out

 Cover

Top Vent

Adapter

(TPVNT-6)

Figure 22.3

 - 90° Rear to Top Vent Adapter (TPVNT-6)

Silicone Rear 

Exhaust Outlet

3 to 6 inch 

Offset Adapter

3 to 3 inch 

Offset 

Adapter

Use holes located on 

each side a drilling guide

Figure 22.1

Содержание OUTFITTER-II

Страница 1: ...iquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearance...

Страница 2: ...nstallation Location Considerations 5 B Thermostat Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Removal of Appliance from Pallet 6 F Install Checklist 7...

Страница 3: ...iency 87 5 HHV Tested Efficiency 81 9 EPA BTU Output 9 605 to 40 667 per hr BTU Input 11 676 to 49 207 per hr Vent Size 3 or 4 Type L or PL Hopper Capacity 130 lbs Fuel Premium Wood Pellets Weighted a...

Страница 4: ...Stove Composition These pellet burning stoves are made of steel cast iron or a combination of both with a ceramic viewing glass These stoves incorporate a self feeding system including a fuel storage...

Страница 5: ...nstallation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restricti...

Страница 6: ...faces have been wiped clean with a soft cloth if applicable Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum saf...

Страница 7: ...ng this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check...

Страница 8: ...A Appliance Dimensions Figure 8 1 Top View 2 1 2 64mm 4 1 2 114mm Figure 8 3 Front View 24 1 2 622mm 36 1 2 927mm Figure 8 2 Side View 22 7 8 581mm 9 1 2 241mm FLUE 8 1 4 210mm AIR INLET 3 3 Dimensio...

Страница 9: ...76mm Figure 9 2 Side View w Top Vent Adapter TPVNT 7 28 711mm Figure 9 3 Top View w Top Vent Adapter TPVNT 7 3 to 4 inch Offset Adapter 811 0720 12 1 4 311mm 3 1 4 83mm Figure 9 4 Side View w Top Ven...

Страница 10: ...Adapter 812 3570 Figure 10 2 Side View w Top Vent Adapter TPVNT 7 3 to 6 inch Offset Adapter 812 3570 12 1 4 311mm 4 1 4 108mm 27 7 8 708mm 29 7 8 760mm Figure 10 3 Top View w Top Vent Adapter TPVNT...

Страница 11: ...Wall Inches Millimeters A Back Wall to Appliance 3 76 B Side Wall to Appliance 9 229 Corner Installation Inches Millimeters C Walls to Appliance 3 76 Table 11 1 Vertical Installation Inches Millimete...

Страница 12: ...tal venting or under the Top Vent Adapter with vertical installation CANADA INSTALLATIONS A non combustible floor protection extending beneath the flue pipe is required with horizontal venting or unde...

Страница 13: ...s A Height 52 1321 n a n a B Width 42 1 2 1080 n a n a C Depth n a n a 25 3 4 654 All minimums listed are to a combustible surface NOTE Illustrations reflect typical installations and are FOR DESIGN P...

Страница 14: ...12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of plants...

Страница 15: ...emand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to...

Страница 16: ...Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Considerations for successful draft include Pre...

Страница 17: ...eft side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it...

Страница 18: ...ssage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 Figure 18 1 Straight Out 6 in 152mm Minimum Non combustible Hearth Pad Wall Thim...

Страница 19: ...tructions for all reduced air clearances installations B Vertical into Existing Class A Chimney Non combustible Hearth Pad Clean out Cover Tee Wall Thimble Support Bracket Every 60 in 1 5m 12 in 305mm...

Страница 20: ...with Airspace Concrete Cap Figure 20 1 Non combustible Hearth Pad Airtight Clean Out Door Clean Out cover Sheathing 3 in 76mm Minimum 1 in 25mm Clearance Flashing Fireclay flue Liner with Airspace Con...

Страница 21: ...utside of house 3 Use hose clamp to secure flex pipe to collar assembly 4 Slide trim ring over flex pipe and run pipe through wall 5 Attach flex pipe to outside termination cap with second hose clamp...

Страница 22: ...e 2 screws Figure 22 1 5 Install the vent pipe into the top vent adapter 6 To clean the top vent adapter open the clean out cover Figure 22 1 C Rear Vent Adapter Installations 1 Put a layer of high te...

Страница 23: ...direct sunlight above a lamp television radiator a wall next to a window or direct heat from the appliance Avoid damp environments as this can lead to corrosion that may shorten thermostat life If pa...

Страница 24: ...Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 7 7 Mobile Home Installation Products of combustion generate carbon monoxide and different fuels generate different levels Carbon m...

Страница 25: ...25 02 22 8105 803B A Service Maintenance Log Date of Service Performed By Description of Service 8 8 Reference Materials...

Страница 26: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Отзывы: