Page 8
7034-106F
August 13, 2009
R
Mt. Vernon Pellet Stove (AE)
R
R
Straight Back Against Wall
Inches
Millimeters
A
Back Wall to Appliance
2
51
B
Side Wall to Appliance
6
152
Corner Installation
Inches
Millimeters
C
Walls to Appliance
2
51
Vertical Installation
Inches
Millimeters
D
Back Wall to Flue Pipe
3
76
E
Side Wall to Appliance
6
152
F
Back Wall to Appliance
8
203
Installations with:
3 to 3 inch Top Vent Adapter and
3 to 6 inch Offset Adapter Kit
Corner Installation
Inches
Millimeters
G
Side Wall to Flue Pipe
3
76
Alcove Installation
Inches
Millimeters
Minimum Alcove Height
43
1092
Minimum Alcove Side Wall
6
152
Minimum Alcove Width
40
1016
Maximum Alcove Depth
36
914
B. Clearances to Combustibles (UL and ULC)
D
E
F
A
B
*L Exception
for Horizontal Installations:
USA INSTALLATIONS
: A non-combustible floor protec
-
tion is recommended extending beneath the flue pipe
when installed with horizontal venting or under the Top
Vent Adapter with vertical installation.
CANADA INSTALLATIONS
: A non-combustible floor
protection extending beneath the flue pipe is
required
with horizontal venting or under the Top Vent Adapter with
vertical installation.
Must extend inches (51mm) beyond each
side of pipe (shaded area)
Fire Risk.
Comply with all minimum clearances to
combustibles as specified.
WARNING
Failure to comply may cause house fire.
NOTE:
•
Illustrations reflect typical installations and are
FOR
DESIGN PURPOSES ONLY
.
•
I
llustrations/diagrams are not drawn to scale.
•
Actual installation may vary due to individual design
preference.
C
C
G
G
C. Hearth Pad Requirements (UL and ULC)
L*
K
K
M
Use a non-combustible floor protector, extending beneath
appliance and to the front, sides and rear as indicated.
Measure front distance “M” from the surface of the glass
door.
Hearth Pad Requirements
Inches
Millimeters
K
Sides
2
51
L*
Back
2
51
M
Front
6
152