background image

Page  30

7005-151D

December 22, 2006

R

Mt. Vernon Pellet Stove 

RR

D.  Igniter Replacement

  a.  Shut down the appliance by turning down the thermostat

 

and let the appliance completely cool down

.  

After the 

appliance has cooled down, unplug it and remove the 

ash drawer.

  b.  The  wire  leads  to  the  igniter  are  connected  to  the 

wire  harness  with  1/4  inch  (6.35mm)  male  /  female 

spade  connectors.    These  wires  will  pull  forward 

approximately 4 to 5 inches (102-127mm).  Disconnect 

the spade connections and remove the igniter from the 

chamber.  Remove the thumb screw and slide igniter 

out.

  c.  Install new igniter into the chamber and replace the 

screw.  Re-connect the wires to the 2 leads with the 

spade connectors.

  d.  Remove  right  side  panel  and  pull  wire  leads  back 

toward the rear of the appliance to take-up the 4 to 5 

inches (102-107mm) previously pulled out.  This will 

keep the wires out of the way of the ash drawer.  Double 

check that the igniter wires are clear of any movement, 

i.e.  ash  drawer,  firepot  cleaning  rod,  cleaning  slide 

plates, etc.

  f.  Re-install the ash drawer and close the ash removal 

door and then re-install the side panel and re-connect 

the power.

Thumb Screw

Igniter

Figure 30.2

2.  Exhaust Blower Replacement
•  Frequency:

  As needed

•  By:

   Quality Service Technician Recommended

•  Task:

a.  Follow instructions for removing the convection blower, 

and outside air if applicable.

b.  Remove the right side curtain. 
c.  Remove the wires connecting:

  a.  Vacuum switch - red & orange

  b.  Circuit breaker - gray & black

  c.  Electrical cord connector - black & double white

    with green

  d.  Thermostat terminal - 2 yellow
e.  Disconnect vacuum hose from the vacuum switch.
f.  Remove the rear screen from the stove by removing  

the 3 screws at the bottom and the 5 screws along the 

top of the screen. 

 See Figure 29.5 on page 29.

e.  Disconnect the double white and double blue wires from 

the exhaust blower.

f.  There is a removable plate on the exhaust blower.  Loosen 

the 6 screws in the keyhole shaped holes and rotate the 

plate.  

Figure 30.1

 

g.  Remove the exhaust blower and gasket.
i.  Re-install in reverse order.

NOTE:  PRIOR TO REPLACING THE EXHAUST 

BLOWER, THE CONVECTION BLOWER MUST BE 

REMOVED.  SEE PAGE 29.

Left Side Panel

Removed

Convection Blower

Exhaust Blower

Loosen screws &

remove blower

Figure 30.1

f i r e - p a r t s . c o m

Содержание Mt. Vernon MTVERNON-CCR

Страница 1: ...d follow these instruc tions for safe installa tion and operation DO NOT DISCARD WARNING Please read this entire manual before installation and use of this pellet fuel burning room heater Failure to f...

Страница 2: ...nserts and replaces And yet we are old fashioned when it comes to craftsmanship Each unit is meticulously fabricated and gold and nickel surfaces are hand nished for lasting beauty and enjoyment Our p...

Страница 3: ...ertical 14 E Masonry 15 F Alternate Masonry 15 Section 6 Mobile Home 16 Section 7 Appliance Set Up A Leg Leveling System 17 B Outside Air Kit 17 C Top Vent Adapter 18 D Log Set Placement 19 E Thermost...

Страница 4: ...Home Approved NOTE This installation must conform with local codes In the absence of local codes you must comply with the ASTM E1509 UM 84 HUD ULC ORD C 1482 D Electrical Rating 115 VAC 60 Hz Start 4...

Страница 5: ...ety Maintain the designated clearances to combustibles Insu lation must not touch the chimney You must maintain the designated air space clearance around the chimney This space around a chimney is nec...

Страница 6: ...NOT Over re Or any such action that may cause a re hazard WARNING Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions D Measuring Standar...

Страница 7: ...9mm 28 1 8 714mm 28 7 16 772mm 14 1 16 357mm C L 29 1 2 749mm 15 1 4 387mm C L 29 1 2 749mm 17 1 2 445mm 32 1 4 819mm 32 1 8 816mm C L C L 2 7 8 73mm 3 to 3 Adapter 1 5 8 41mm 3 to 6 Adapter 20 0 508m...

Страница 8: ...liance 2 51 H Side Wall to Flue Pipe 3 76 Alcove Installation Inches Millimeters Minimum Alcove Height 43 1092 Minimum Alcove Side Wall 6 152 Minimum Alcove Width 40 1016 Maximum Alcove Depth 48 1219...

Страница 9: ...combustible oor protection extending beneath the ue pipe is required with horizontal venting or under the Top Vent Adapter with vertical installation Must extend 2 inches 51mm beyond each side of pipe...

Страница 10: ...y be used Substitute or damaged vent components may impair safe operation WARNING B Venting Termination Requirements 1 Termination must exhaust above air inlet elevation It is recommended that at leas...

Страница 11: ...haust gases under positive pressure as 1 foot of horizontal pipe and a foot of horizontal pipe is twice as restrictive as a foot of vertical pipe D Pipe Selection Chart The table below can help you ca...

Страница 12: ...Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference A Alcove Figure 12 1 All minimums listed are to a combustible sur Minimum Maximum Inches...

Страница 13: ...or your installation 2 in 51mm Minimum 2 in 51mm Minimum B Through The Wall Horizontal termination cap must be a minimum of 12 inches 305mm from the wall Approved for mobile home instal lations Must u...

Страница 14: ...ingle wall pipe is approved for residential installations only C Vertical D Through The Wall Vertical Firestop Flashing Rain Cap 6 in 152mm Min Non combustible Hearth Pad 3 in 76mm Min Cleanout Cover...

Страница 15: ...combustible Hearth Pad Airtight cleanout door Sheathing 2 in 51mm minimum Flashing 1 in 25mm clearance 1 in 25mm clearance with firestop 6 in 152mm minimum Fireclay Flue Liner with airspace Concrete C...

Страница 16: ...tion requirements on pages 4 10 for listings to combustibles and appropriate chimney systems 6 Use silicone to create an effective vapor barrier at the location where the chimney or other component pe...

Страница 17: ...of 2 inch x 3 foot ex hose 2 hose clamps 1 collar assembly 1 termi nation cap assembly 1 trim ring 12 screws 1 Measure distance from oor to air vent opening in appli ance and mark location on wall Use...

Страница 18: ...s Figure 18 1 6 Install the vent pipe into the top vent adapter be sure to silicone all joints 7 To clean top vent adapter open clean out cover Figure 18 2 C Top Vent Adapter Installation 3 in to 6 in...

Страница 19: ...included wall mount thermo stat or purchase an optional programmable thermostat or remote control It is equipped with an adjustable heat anticipator The current rating is 05 amps The anticipator needs...

Страница 20: ...conomical fuel We recommend the use of a 50 50 blend of corn and wood pellets The only change in operation is that the feed rate may require a slight adjustment The BTU output of the appliance varies...

Страница 21: ...er if the flame height is too high or too low you will need to adjust the feed rate Wait until the appliance has been burning for 15 minutes before making your adjustments and allow 15 minutes for fee...

Страница 22: ...ING Fire Risk Do NOT operate appliance With appliance door open Firepot oor open Cleaning slide plates open Do NOT store fuel Closer than required clearances to com bustibles to appliance Within space...

Страница 23: ...nting system is clean Make sure front door is closed Replace control box Call light on No re Partially burned fuel in repot Firepot clean out plate not closed Firepot is dirty missed ignition Check th...

Страница 24: ...ebox causing loss of vacuum Empty hopper of fuel Use a wet dry vacuum cleaner to remove remaining fuel from hopper including feed tube Check feed chute for obstructions Loosen 2 screws and jiggle feed...

Страница 25: ...less steel baf e from rebox to clean ash from on top of baf e Clean behind rear brick panels Change fuel brand to premium Check that repot clean out plate is fully closed Reduce feed rate using feed r...

Страница 26: ...ly closed when cleaning is complete See Disposal of Ashes on page 27 WARNING NEVER pull repot cleaning rod or cleaning slide plates out when appliance is operating Hot pellets may fall into ashpan and...

Страница 27: ...rods OUT and IN a couple of times Figure 27 1 8 Cleaning Beneath Heat Exchanger Frequency Monthly or after burning 1 ton of fuel By Homeowner Task A more thorough cleaning is needed to remove the exce...

Страница 28: ...e a year or more often depending upon the quality of your fuel or if there is a lot of horizontal pipe sec tions Ash will build up more quickly in the horizontal sections 10 Cleaning the Hopper Freque...

Страница 29: ...ontent Maintenance Frequency As needed By Homeowner Task Poor quality pellet fuel or lack of maintenance can create conditions that make the repot ll quickly with ashes and clinkers This condition mak...

Страница 30: ...all the ash drawer and close the ash removal door and then re install the side panel and re connect the power Thumb Screw Igniter Figure 30 2 2 Exhaust Blower Replacement Frequency As needed By Qualit...

Страница 31: ...y shatter and cause injury WARNING Rope Retainer Rods Slide this end in first Crimped end at the bottom Crimped end must be parallel with the glass Glass Figure 31 3 Frequency As needed By Quali ed Se...

Страница 32: ...should be set on the lowest setting available When describing the location of a component it is always AS YOU FACE THE FRONT OF THE APPLIANCE 2 Convection Blower The convection blower is mounted at th...

Страница 33: ...ube in the center of the appliance and has a red reset button To access it remove the right side panel If the re tries to burn back into the feed system or push exhaust up the feed tube this snap disc...

Страница 34: ...ns VACUUM SWITC H EXHAUST BLOWER CONTRO L BOX CLEANING RODS 10 HEAT EXCHANGER TUBES RED CALL LIGHT TERMINAL BLOCK CENTER 2 SCREWS FOR THERMOSTAT WIRES POWER OUTLET FUSE Fuse Fuse Remove 3 screws on ea...

Страница 35: ...0440 8 Rope Retainer 7005 268 9 Glass Assembly with Gasket 7005 058 10 Hinge Door 450 2910 11 Screw 10 32 x 5 16 PH PHL MS ZC 229 1230 12 Hinge Pin Rivet Gold 72171 Nickel 433 1590 11 10 12 13 16 15 1...

Страница 36: ...Adapter 3 to 6 inch 33 Vacuum Switch 34 Control Box 35 Hopper 36 Snap Disc 2 200 o 37 Snap Disc 1 125 o 38 Feed Motor Assembly 39 Feed Spring Assembly 40 Exhaust Blower 41 Snap Disc 3 250o Nbr Descri...

Страница 37: ...5 062 PCR 7005 063 PMB 7005 065 PMH 7005 066 34 Control Box 4 speed SRV7000 206 Door Latch Assembly 7021 006 Door Rope Shield SRV7005 271 55 Door Left Matte Black with gold hinge pins 7005 020MBK 55 D...

Страница 38: ...repot 240 0930 Gasket Tadpole 10 ft 842 5130 6 Glass Assembly with Gasketing 7005 130 53 Hinge Pin Rivet Gold order quantity needed 72171 53 Hinge Pin Rivet Nickel order quantity needed 433 1590 Heat...

Страница 39: ...ome Technologies discontinues the model and two 2 years for optional accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be co...

Страница 40: ...ions included Read understand and follow these instruc tions for safe installation and operation Leave this manual with party responsible for use and operation This product may be covered by one or mo...

Отзывы: