Page  18

Quadra-Fire  •  Hudson Bay  •  7003-121_R20  •  11/14  

2. Cathedral Ceiling

Step 1.

Follow installation Steps 1 and 2 under vertical installation 

section, page 15.

Step 2.

Remove shingles or other roof covering as necessary to cut 

the rectangular hole for the support box. Cut the hole 1/8 in. 

(3mm) larger than the support box outline.

Step 3.

Lower the support box through the hole in the roof until the 

bottom of the support box protrudes at least 2 in. (51mm) 

below the ceiling (

Figure 5.17

). Align the support box both 

vertically and horizontally with a level. Temporarily tack the 

support box in place through the inside walls and into the 

roof sheathing.

LEVEL

CATHEDRAL CEILING

SUPPORT BOX

2 in. (51mm) 

MIN. BELOW

FINISHED 

CEILING

CUT HOLE 1/8 in. 

(3mm) GREATER IN 

SIZE THAN PATTERN 

OF SUPPORT BOX AS 

IT IS PROJECTED 

ONTO ROOF LINE

Figure 5.17 

Figure 5.18 

Step 4.

Using tin snips, cut the support box from the top corners 

down to the roof line, and fold the resulting flaps over the 

roof sheathing (

Figure 5.18

). Before nailing it to the roof, 

run a bead of non-hardening mastic around the top edges 

of the support box to make a seal between it and the roof. 

Clean out any combustible material from inside the support 

box.

Step 5.

Assemble the desired lengths of pipe and elbows necessary 

to reach from the appliance up through the round support 

box. Ensure that all pipe and elbow connections are in their 

fully twist-locked position. Assemble as instructed.

Step 6.

Place  the  support  clamp  (provided  with  the  support  box) 

inside the support box (at the bottom), and secure to the 

pipe section. The clamp allows the support box to support 

the  weight  of  the  pipe  sections.  Continue  to  add  pipe 

sections until you are above the roof line.

Step 7.

Complete the cathedral ceiling installation by following the 

same procedures outlined in steps 7 through 9 for vertical 

installations, pages 16-17.

Step 8.

Install the black trim collar around the outside of the cathedral 

ceiling support box (

Figure 5.19

). The two pieces of the trim 

collar slide over one another to allow for easy adjustment 

around  the  support  box.  Using  the  six  screws  provided, 

secure the four corners and the overlapping sections of the 

trim collar to the ceiling. You may want to predrill the holes 

for the overlapped sections for ease of installation.

CATHEDRAL 

CEILING 

SUPPORT 

BOX

TRIM COLLAR

SCREWS

Figure 5.19 

Содержание HUDSON BAY HUDBAY-FS

Страница 1: ...uirements HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns Do not touch glass until it is cooled NEVER allow children to touch glass Keep childre...

Страница 2: ...du plancher au plafond 1372 mm F Profondeur maximum de l alcove 914 4 mm G Largeur minimum de l alcove 1181 mm H Dessus de fourneau au plafond 533 4 mm CHEMIN E Un coussinet non combustible de chemin...

Страница 3: ...tion 12 G Vertical Termination 15 Section 6 Gas Information A Fuel Conversions 22 B Gas Pressures 24 C Gas Connection 25 Contains updated information Section 7 Electrical Information A Recommendation...

Страница 4: ...et above a 2000 foot elevation in the U S A If the heating value of the gas has been reduced these rules do not apply To identify the proper orifice size check with the local gas utility If installing...

Страница 5: ...eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1...

Страница 6: ...nstalled The vent system configuration to be used Gas supply piping Electrical wiring Whether optional accessories devices such as a blower thermostat or remote control are desired Carefully remove th...

Страница 7: ...Flooring beneath appliance may reach 90 degrees plus room ambient temperature Check with flooring manufacturer for maximum temperature allowed on flooring surfaces It is permissible to place the appli...

Страница 8: ...12 LOWEST DISCHARGE OPENING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Roof Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8...

Страница 9: ..._________________________________________ _ _ QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMA X...

Страница 10: ...hese items b Use of Elbows Fire Hazard Explosion Risk Asphyxiation Risk Do NOT connect this gas appliance to a chimney flue serving a separate solid fuel or gas burning appliance Vent this appliance d...

Страница 11: ...to the allowable 15 ft 5m run Each additional 90 elbow reduces the maximum horizontal distance by 3 ft 914mm Example The use of 3 elbows would reduce the allowable horizontal run to 9 ft 3 1 2 elbows...

Страница 12: ...installation instructions Connect vent sections per installation instructions Maintain all clearances to combustibles Do NOT allow vent to sag below connection point to appliance Maintain specified s...

Страница 13: ...the wall attach termination cap to the exterior wall with the four wood screws provided The arrow on the vent cap should be pointing up Figure 5 6 HOT WOOD SCREW WALL THIMBLE PART HHW2 PART 841 0670 P...

Страница 14: ...ment from the vent pipe to the vent termination cap must be sealed with silicone Termination caps shall not be recessed into a wall or siding FOLD STRAP HERE WALL THIMBLE COVER CEILING FIRESTOP AS REQ...

Страница 15: ...for required 1 in 25mm clearances air space to combustibles when passing through ceilings walls roofs enclosures attic rafters or other nearby combustible surfaces See page 17 Figure 5 16 Check the in...

Страница 16: ...e the roofing material overlaps the top edge of the flashing as shown in Figure 5 14 Verify that the chimney is the required height above the roof See roof pitch table Figure 4 3 on page 8 Step 7 Cont...

Страница 17: ...EILING FIRESTOP NAILS MIN 1 in 25mm CLEARANCE MIN 1 in 25mm CLEARANCE MIN 1 in 25mm CLEARANCE Figure 5 16 Fire Risk Explosion Risk Any occupied areas above the first floor including closets and storag...

Страница 18: ...edges of the support box to make a seal between it and the roof Clean out any combustible material from inside the support box Step 5 Assemble the desired lengths of pipe and elbows necessary to reac...

Страница 19: ...to the ceiling support box center the retro connector and attach it to the support box with sheet metal screws Step 7 The connection between the appliance and the retro connector may be completed with...

Страница 20: ...ramed a wall thimble is required This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles Figure 5 25 Step 4 To determine the length of flex...

Страница 21: ...er to extend through the opening in the wall thimble cover Step 8 Secure the top adapter to the flashing Use three sheet metal screws through the side of the top adapter into the flange on the flashin...

Страница 22: ...TENTS Replacement orifice replacement pilot injector and valve regulator TOOLS REQUIRED Ratchet with 7 16 in socket and 2 in 4 in extension power drill a 90 handle is helpful 2 Phillips bit 5 32 in al...

Страница 23: ...d Figure 6 5 With a 5 8 in wrench remove the orifice retain ing nut Replace with appropriate orifice 076 LP 125 NG Figure 6 6 Remove pilot hood and set aside NOTE Do not remove retaining clip from pil...

Страница 24: ...FORE pressure testing gas line at test pressures equal to or less than 1 2 psig PRESSURE NG LP Minimum Inlet Pressure 4 5 inches w c 11 0 inches w c Maximum Inlet Pressure 7 0 inches w c 14 0 inches w...

Страница 25: ...h of Massachusetts approved 1 2 inch 13mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 inch 13mm control valve inlet If substituting for these components please c...

Страница 26: ...e length 7 Low voltage and 110 VAC voltage cannot be shared within the same wall box Wire Size Max Length 16 gauge 65 feet 18 gauge 40 feet 20 gauge 25 feet 22 gauge 18 feet Shock hazard This applianc...

Страница 27: ...errors can cause improper and dangerous operation Verify proper operation after servicing Shock hazard Replace damaged wire with type 105O C rated wire Wire must have high temperature insulation RED...

Страница 28: ...bottom of the appliance that secure the door Rotate the door forward approximately 1 1 2 in 38mm Holding the ashlip lift the door up off of the stationary latches and away from the appliance Figure 8...

Страница 29: ...ing E Brick Set Installation Figure 8 6 The pilot shield has to be removed to install or remove the brick refractory Removal of the bracket requires removing two screws Pilot Bracket Pilot Shield Figu...

Страница 30: ...ck in place Figure 8 11 Install the rear brick Slide it in at an angle and place over the rear brick retainer Hand bend retaining tabs up to hold brick in place Push baffle towards back of firebox Fig...

Страница 31: ...pieces of embers in front of and around the gas logs where they can be seen Space them so that gas can contact them on all sides Avoid stacking the embers on top of each other NOTE Do not block gas po...

Страница 32: ...e To access the blower open the door located on the front of the pedestal Remove the two screws holding the blower bracket in place Figure 8 21 Disconnect wires to the blower motor Remove the blower f...

Страница 33: ...damper shall be replaced with the words flue restrictor J Shutter Adjustment K Glass Replacement NOTE Glass can be replaced either as three separate pieces or as an assembly with the door See Section...

Страница 34: ...service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water B Controls FAN SPEED This knob controls the speed of the blowe...

Страница 35: ...of the appliance May need to remove face front first 5 Push in gas control knob slightly and turn clockwise to the OFF position Do not force 6 Wait five 5 minutes to clear out any gas Smell for gas i...

Страница 36: ...Smoke and odors may be irritating to sensitive individuals Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if appliance will not be...

Страница 37: ...ion at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter...

Страница 38: ...ng exhaust gases back into the system Check for proper vent connection at flue collar and all vent joints c Horizontal vent improperly pitched The horizontal vent cap should slope down only enough to...

Страница 39: ...rd water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL Remove and clean glass assembly Replace glass assembly and op...

Страница 40: ...as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for p...

Страница 41: ...ce Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For clearances refer to Section 3 Figure 12 1 Appliance Dimensions Location Inches Millimeter A 22 3 8 568 B 9 3...

Страница 42: ...184 mm 7 1 4 in 184 mm 5 1 4 in 133 mm 25 1 4 in 641 mm 37 1 4 in 946 mm 49 1 4 in 1251 mm 13 1 4 in 337 mm 13 1 4 in 337 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm SLP45 SLP9...

Страница 43: ...Page 43 Quadra Fire Hudson Bay 7003 121_R20 11 14 B Vent Components Diagrams continued 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm Figure 12 3 SLP Series Vent Components...

Страница 44: ...SLP FS Ceiling Firestop SLP WS Wall Firestop SLP HVS Pipe Support Hanger 950 Vinyl Protector Kit SL Pipe DRC RADIUS Decorative Radius Cover RF4 8 Roof Flashing TERMINATION KITS SLP TRAP2 Trapezoid Ter...

Страница 45: ...0021621084 7003 117 3 Latch Assembly Stationary Qty 2 req 7003 006 Y 4 Refractory Assembly 7008 002 5 Grill Bar Assembly BLACK Pre SN 0021621084 SRV7008 010 Post SN 0021621084 7008 010 Grill Bar Asse...

Страница 46: ...bly Qty 2 reg 7003 005 Y 12 2 Blower 812 4900 Y Blower Plate 457 0560 Blower Bracket 474 0210 13 3 Pedestal Door Pre SN 0021621084 SRV7003 107 Post SN 0021621084 7003 107 12 4 Air Shutter Assembly 468...

Страница 47: ...8 7010 172 Brick Retainer 479 0190 Electrode EZ Flush 42 842 4580 Y Fan De ector 468 0190 Flex Line 3 8 comp x 30 200 2940A Y Flex Line 24 2098 034 Y Mineral Wool 050 721 Ori ce LP 076 Port 29388 Y Or...

Страница 48: ...rchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer...

Страница 49: ...IFIED ABOVE WARRANTY EXCLUSIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior s...

Страница 50: ..._ DATE INSTALLED __________________ R CONTACT INFORMATION Quadra Fire a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www quadrafire com This product may be covered by on...

Отзывы: