Figure 4.4   

V

= VENT TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

A

= 12 inches ............. clearances above grade, veran-

da, porch, deck or balcony

B

= 12 inches ............ clearances to window or door

that may be opened, or to per-
manently closed window. (Glass)

D*

= 18 inches ............. vertical clearance to unventilat-

ed soffit or to ventilated soffit lo-
cated above the terminal

*30 inches ............ for vinyl clad soffits and below

electrical service

F

=

9 inches .............. clearance to outside corner

G

= 6 inches ............... clearance to inside corner

H

= 3 ft. (Canada) ...... not to be installed above a gas

meter/regulatorassembly within 3
feet (90cm) horizontally from the
center-line of the regulator

I

= 3 ft. ....................... clearance to gas service regula-

tor vent outlet

J

= 9 inches (U.S.A.)

12 inches (Canada)clearance to non-mechanical air

supply inlet to building or the
combustion air inlet to any other
appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance to a mechanical

(powered) air supply inlet

L** = 7 ft. ......................... clearance above paved

sidewalk or a paved driveway
located on

public

property

M*** = 18 inches .............. clearance under veranda ,

porch, deck, balcony or over-
hang

42 inches .............. vinyl

** a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings and
serves both dwellings.

*** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor, or meets Note 2.

(See Note 1)

(See Note 1)

(S

Note 2)

S =

6 inches ................. clearance from sides of

electrical service

T = 12 inches ................ clearance above electrical

service

(See Note 3)

(See Note 3)

___________________________________________________________________

_

___________________________________________________________________

_

___________________________________________________________________

_

_

Q

MIN

R

MAX

1 cap

3 feet

2 x Q

ACTUA L

2 caps

6 feet

1 x Q

ACTUA L

3 caps

9 feet

2/3 x Q

ACTUA L

4 caps

12 feet

1/2 x Q

ACTUA L

Q

MIN

= # termination caps x 3

R

MAX

= (2 / # termination caps) x Q

ACTUAL

N

= 6 inches ................. non-vinyl sidewalls

12 inches ............... vinyl sidewalls

P

= 8 ft.

Alcove Applications

NOTE 1:

On private property where termination is less than 7 feet above

a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed
cap is suggested.  (See vents components pages.)

NOTE 2:

Termination in an alcove space (spaces only open on one side

and without an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits.

1.

There must be at least 3 feet

minimum between termination caps.

2.

All mechanical air intakes within

10 feet of a termination cap must be a minimum of 3 feet below the
termination cap.

3.

All gravity air intakes within 3 feet of a termination cap

must be a minimum of 1 foot below the termination cap.

NOTE 3:

Location of the vent termination must not interfere with access

to the electrical service.

NOTE:

Local codes or regulations may require different

clearances.

NOTE:

Termination caps may be hot. Consider their proximity to

doors or other traffic areas.

WARNING: In the U.S.:

Vent system termination is

NOT

permitted

in screened porches.

You must follow side wall, overhang and

ground clearances as slated in the instructions.

In Canada:

Vent system termination is

NOT

permitted in screened

porches. Vent system termination is permitted in porch areas with
two or more sides open. You must follow side wall, overhang and
ground clearances as stated in the instructions.

Quadra-Fire assumes no responsibility for the improper perfor-
mance of the appliance when the venting system does not meet
these requirements.

v

v

v

v

(See Note 2)

CAUTION: IF EXTERIOR WALLS ARE FINISHED 
WITH VINYL SIDING, IT IS SUGGESTED THAT A 
VINYL PROTECTOR KIT BE INSTALLED (part #VPK-
DV).

Содержание Hudson Bay Direct Vent Gas Appliance...

Страница 1: ...n manufactured home USAonly or mobile home and must be installed in accordance with the manufacturer s instructions and the manufactured home con struction and safety standard Title 24 CFR Part 3280 o...

Страница 2: ...TEMENTS LES MEUBLES LA GAZOLINE ET LES AUTRES LIQUIDES DE VAPEUR INFLAMMABLE LOIGN S CAUTION DO NOT OPERATE THIS APPLIANCE WITH GLASS REMOVED CRACKED OR BROKEN REPLACEMENT OF THE PANEL S SHOULD BE DON...

Страница 3: ...on 12 G Vertical Termination 15 Section 6 Gas Information A Fuel Conversions 22 B Gas Pressures 24 C Gas Connection 25 Section 7 Electrical Information A Recommendation for Wire 26 B Connecting to the...

Страница 4: ...Home installation may occur only after the home is site located and must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or when such a standard is not appli...

Страница 5: ...st vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF AL...

Страница 6: ...o tective surface Remove log set and component pack from firebox Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before startin...

Страница 7: ...ions in manual WARNING B Clearances Figure 3 1 NOTE Flooring beneath appliance may reach 90 degrees plus room ambient temperature Check with flooring manufacturer for maximum temperature allowed on fl...

Страница 8: ...Measure horizontal clearances from this surface See Figure 4 4 for specific clearances Opening HORIZONTAL OVERHANG VERTICAL WALL GAS DIRECT VENT TERMINATION CAP 12 X ROOF PITCH IS X 12 LOWEST DISCHARG...

Страница 9: ...__________________________________________ _ _ QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMA X...

Страница 10: ...flue WARNING Diagonal runs have both vertical and horizontal vent aspects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 5 1 Two 45...

Страница 11: ...914mm VERTICAL DISTANCE FROM APPLIANCE TO TO THE 90 ELBOW TOTAL HORIZONTAL RUN TO OUTSIDE OF EXTERIOR WALL INCLUDING ELBOWS EX 2 EX 1 11 2 4 6 8 10 12 14 15 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0...

Страница 12: ...r installation instructions Connect vent sections per installation instructions Maintain all clearances to combustibles Do NOT allow vent to sag below connection point to appliance Maintain specified...

Страница 13: ...tic around its outside edges so as to make a seal between it and the wall attach termination cap to the exterior wall with the four wood screws provided The arrow on the vent cap should be pointing up...

Страница 14: ...hment from the vent pipe to the vent termination cap must be sealed with silicone Termination caps shall not be recessed into a wall or siding FOLD STRAP HERE WALL THIMBLE COVER CEILING FIRESTOP AS RE...

Страница 15: ...for required 1 in 25mm clearances air space to combustibles when passing through ceilings walls roofs enclosures attic rafters or other nearby combustible surfaces See page 17 Figure 5 16 Check the in...

Страница 16: ...outlined in the current CAN CGA B149 Installation Codes in Canada the National Fuel Gas Code NFPA 54 ANSI Z223 1 in USA or local codes Note that for steep roof pitches the vent height must be increase...

Страница 17: ...sheetrocked with standard construction materials however refer to these installation instructions for the minimum allowable clearance between the outside of the vent pipe and the combustible surfaces...

Страница 18: ...p edges of the support box to make a seal between it and the roof Clean out any combustible material from inside the support box Step 7 Complete the cathedral ceiling installation by following the sam...

Страница 19: ...nto the ceiling support box center the retro connector and attach it to the support box with sheet metal screws Step 7 The connection between the appliance and the retro connector may be completed wit...

Страница 20: ...framed a wall thimble is required This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles Figure 5 25 Step 4 To determine the length of flex...

Страница 21: ...Figure 5 25 page 20 If needed add a section of direct vent pipe to the retro connector in order to extend through the opening in the wall thimble cover Step 8 Secure the top adapter to the flashing U...

Страница 22: ...t and socket Figure 6 2 Lift burner up and out of the firebox opening Figure 6 3 Remove the three screws on the front of the burner support Set screws aside Figure 6 4 Slide the burner support to the...

Страница 23: ...rn off gas supply to unit before proceeding if converting fuel on an appliance already fully installed WARNING Figure 6 5 With a 5 8 in wrench remove the orifice retaining nut Replace with appropriate...

Страница 24: ...LP Minimum Inlet Pressure 4 5 inches w c 11 0 inches w c Maximum Inlet Pressure 7 0 inches w c 14 0 inches w c Manifold Pressure on HI 3 5 inches w c 10 0 inches w c WARNING Verify inlet pressures Hi...

Страница 25: ...d and Commonwealth of Massachusetts approved 1 2 inch 13mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 inch 13mm control valve inlet If substituting for these co...

Страница 26: ...ostat 5 Use the following chart for wire sizing 6 Keep wire lengths as short as possible by removing any excess wire length 7 Low voltage and 110 VAC voltage cannot be shared within the same wall box...

Страница 27: ...improper and dangerous operation Verify proper operation after servicing Shock hazard Replace damaged wire with type 105O C rated wire Wire must have high temperature insulation CAUTION RED 28 IN 711...

Страница 28: ...all fingerprint oils from the gold or nickel surface of crown PRIOR to lighting the appliance Figure 8 1 Open lower access panel Pull out and unhook the two spring latches on the bottom of the applian...

Страница 29: ...f firebox Holding against heat exchangers slide baffle towards front of appliance D Grille Installation Figure 8 5 Following instructions stated above remove the door of appliance Remove the four scre...

Страница 30: ...still breakable the logs do not become fragile until after the appliance is burned and they have cured After curing any handling must be done with care as breakage can easily occur PLEASE NOTE Logs h...

Страница 31: ...he right rear log and the left front log G Mineral Wool Follow ember placement instructions in manual Do NOT place embers directly over burner ports Replace ember material annually Explosion Risk WARN...

Страница 32: ...om the bracket The blower motor comes standard with two male spade wire connectors If your appliance has a different con nection use the two female spade wire connectors pro vided to modify the applia...

Страница 33: ...a horizontal termination After adjustment tighten nut to lock in place K Glass Replacement 1 Turn off gas to appliance 2 Remove door from the appliance and set on a protec tive surface 3 Remove door c...

Страница 34: ...that there are no gas leaks Ensure that the glass is sealed and in the proper posi tion Ensure that the flow of combustion and ventilation air is not obstructed front grilles and vent caps B Controls...

Страница 35: ...the power from the appliance 4 Open the door of the appliance May need to remove face front first 5 Push in gas control knob slightly and turn clockwise to the OFF position Do not force 6 Wait five 5...

Страница 36: ...detectors Smoke and odors may be irritating to sensitive individuals CAUTION Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if app...

Страница 37: ...e thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocoupl...

Страница 38: ...ng exhaust gases back into the system Check for proper vent connection at flue collar and all vent joints c Horizontal vent improperly pitched The horizontal vent cap should slope down only enough to...

Страница 39: ...ching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL...

Страница 40: ...as neces sary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for...

Страница 41: ...ence Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For clearances refer to Section 3 Figure 12 1 Appliance Dimensions Location Inches Millim...

Страница 42: ...n 184 mm 7 1 4 in 184 mm 5 1 4 in 133 mm 25 1 4 in 641 mm 37 1 4 in 946 mm 49 1 4 in 1251 mm 13 1 4 in 337 mm 13 1 4 in 337 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm SLP45 SLP...

Страница 43: ...ling Firestop SLP WS Wall Firestop SLP HVS Pipe Support Hanger 950 Vinyl Protector Kit SL Pipe DRC RADIUS Decorative Radius Cover HTI DV WT Wall Thimble RF4 8 Roof Flashing TERMINATION KITS SLP TRAP2...

Страница 44: ...03 121 Rev i D Service Parts List R HUDBAY FS Service Parts Diagram Part number list on following page Log Set Assembly Hudson Bay Free Standing 1 2 3 4 5 6 10 9 8 7 Beginning Manufacturing Date April...

Страница 45: ...0110 10 Valve Cover 7003 119 Adaptor Inner 4 200 2470 Adaptor 6 5 8 7000 162 Brick Retainer 479 0190 Electrode EZ Flush 42 842 4580 Y Fan Deflector 468 0190 Flex Line 3 8 comp x 30 200 2940 Y Flex Lin...

Страница 46: ...0730 Y 3 Piezo Ignitor 291 513 Y 4 Knob On Off 571 534 Y 5 Knob Hi Lo 571 533 Y 6 Valve NG 842 0240 Y Valve LP 842 0230 Y Valve Bracket 7003 118 7 Latch Assembly Qty 2 reg 7003 005 Y 8 Blower 812 490...

Страница 47: ...ble under this warranty is limited to the purchase price of the product In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regular...

Страница 48: ...ed and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warra...

Страница 49: ...___________ Hudson Bay Direct Vent Gas Appliance Do NOT discard this manual CAUTION Important operating and maintenance instructions included Read understand and follow these instruc tions for safe in...

Отзывы: