Castile-B FS Pellet Stove 

We recommend a minimum of 60 in. 
(1.5m) vertical, however above the eave 
is preferred. 

Both installations are approved for 
mobile home installations.  Must use 
3 or 4 inch (76 to 102mm) “L” or “PL” 
listed pellet venting or listed double 
wall pipe and Quadra-Fire Outside Air 
Kit  in mobile homes.  Single wall pipe 
is approved for residential installations 
only.

C.  Vertical

D. Through The Wall & Vertical

Firestop 

Flashing 

Rain Cap 

6 in. 

(152mm) 

Min. 

Non-combustible Hearth Pad

3 in. (76mm)

 

Min. 

Clean-out Cover

24 in. (610mm)

 

Minimum 

Ceiling Support 

6 in. (152mm) Flue 
Connector

6 in. (152mm) Class A 
Chimney Connector 
Adapter 

 

3 in. to 6 in. 
(76-152mm) 
Top Vent Kit

Figure 15.1

Figure 15.2

Non-combustible Hearth Pad

Clean-out Cover

Support Bracket
every 60 in. (1.5m)

24 in. (610mm) minimum

Rain Cap

Flashing

2 in. (51mm) minimum

6 in. (152mm)
minimum

Tee

Wall Thimble

Содержание CASTILE-MBK-B

Страница 1: ...requirements in your area CAUTION Tested and approved for wood pellets and shelled field corn fuel only Burning of any other type of fuel voids your warranty CAUTION WARNING Hot glass will cause burns...

Страница 2: ...des codes locaux pour les pr cautions requises pour passer une chemin e travers un mur ou un plafond combustibles et les compensations maximums Inspectez et nettoyez la chemin e fr quemment Ne pas co...

Страница 3: ...n A Chimney Exhaust Connection 11 B Venting Termination Requirements 11 C Equivalent Feet of Pipe 12 D Pipe Selection Chart 12 Section 5 Venting Systems A Alcove 13 B Through the Wall 14 C Vertical 15...

Страница 4: ...e Technologies Operate the appliance without fully assembling all components Overfire Install any component not approved by Hearth Home Technologies Install parts or components not Listed or approved...

Страница 5: ...loca tion of the vent termination CAUTION If burning shelled field corn you must use ap proved venting specifically designed for corn to prevent corro sion or degradation Follow the instructions from...

Страница 6: ...appliance is drafting successfully all combustion byproducts are exiting the home through the chimney Considerations for successful draft include Preventing negative pressure Location of appliance and...

Страница 7: ...ials have been met 8 The masonry chimney is inspected by a profes sional and is clean or the factory built metal chimney is installed according to the manufac turer s instructions and clearances 9 The...

Страница 8: ...nsions Figure 8 2 Front View Figure 8 1 Top View Figure 8 3 Side View Figure 8 4 Side View with Top Vent Adapter 24 in 609mm 24 5 8 in 626mm 12 in 305mm 24 in 609mm 28 9 16 in 725mm 15 15 16 in 405mm...

Страница 9: ...Appliance 2 51 H Side Wall to Flue Pipe 3 76 Alcove Installation Inches Millimeters Minimum Alcove Height 43 1092 Minimum Alcove Side Wall 6 152 Minimum Alcove Width 38 965 Maximum Alcove Depth 36 91...

Страница 10: ...required with hori zontal venting or under the Top Vent Adapter with vertical installation Must extend 2 inches 51mm beyond each side of pipe shaded area C Hearth Pad Requirements UL and ULC Use a no...

Страница 11: ...otruding parts of the structure roof overhang plants and shrubs etc 6 Termination Cap Location Home Electrical Service Side to side clearance is to be the same as minimum clearance to vinyl inside cor...

Страница 12: ...ere above the diagonal line a 4 inch 102mm diam eter pipe is required The chart reveals that a 90 elbow is 5 times as restrictive to the flow of exhaust gases under positive pressure as 1 foot of hori...

Страница 13: ...S ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference A Alcove Figure 13 1 All minimums listed are to a combustible surface Minimum Maxi...

Страница 14: ...ust be a minimum of 6 inches 152mm from the wall Approved for mobile home instal lations Must use 3 or 4 inch 76 102mm L or PL listed pellet venting or listed double wall pipe and a Quadra Fire Outsid...

Страница 15: ...Single wall pipe is approved for residential installations only C Vertical D Through The Wall Vertical Firestop Flashing Rain Cap 6 in 152mm Min Non combustible Hearth Pad 3 in 76mm Min Clean out Cov...

Страница 16: ...nry Figure 16 1 Figure 16 2 Non combustible Hearth Pad Airtight Clean out Door Clean out cover Sheathing 3 in 76mm minimum 1 in 25mm clearance Flashing Fireclay flue liner with airspace Concrete Cap 1...

Страница 17: ...ling the vent system for use in a mobile home 8 Installation shall be in accordance with the Manufactur ers Home Safety Standard HUD CFR 3280 Part 24 Installation must comply with Manufactured Home an...

Страница 18: ...interior wall Tools Needed Phillips headscrewdriver wire cutters hole saw or jig saw CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or gar...

Страница 19: ...tion Figure 19 5 Figure 19 4 Installing the Top Vent Adapter Top Vent Adapter 3 to 3 inch Rear Exhaust Outlet Use hole on each side as drilling guide Offset Collar 3 to 6 inch Mount with 4 screws Clea...

Страница 20: ...overed under warranty Any placement varia tion other than shown here can cause excessive heat and shall void the appliance warranty Figure 20 2 1 Open door to expose the firebox 2 Install the left log...

Страница 21: ...he thermostat should be mounted on an inside wall and not in direct line with the appliance convection air NOTE If the thermostat is located too close to the appliance you may need to set the temperat...

Страница 22: ...ood pellets should be left in their original sealed bag until using This will prevent moisture absorption Shelled corn should be stored in a tight container where it will not absorb moisture from damp...

Страница 23: ...nutes after start up and again in 5 minutes This will fill the feed system and allow the appliance to begin dropping pellets The appliance will continue to run as long as the thermostat is calling for...

Страница 24: ...ped calling for heat until the appliance has cooled down 3 Occasionally the appliance may run out of fuel and shut itself down When this happens the red call light will be on Figure 24 1 To restart it...

Страница 25: ...does not affect the operation or longevity of your appliance 2 Ash buildup on glass 2 This is normal Clean the glass 3 Glass has turned dirty 3 Excessive build up of ash The lower burn settings will p...

Страница 26: ...clean Make sure front door is closed Replace control box Call light on No fire Partially burned fuel in firepot Firepot clean out plate not closed Firepot is dirty missed ignition Check that firepot...

Страница 27: ...s of vacuum Empty hopper of fuel Use a wet dry vacuum cleaner to remove remaining fuel from hopper including feed tube Check feed chute for obstructions Loosen 2 feed assembly mounting screws and ligh...

Страница 28: ...less steel baffle from firebox to clean ash from on top of baffle Clean behind rear brick panels Change fuel brand to premium Check that firepot clean out plate is fully closed Reduce feed rate using...

Страница 29: ...Removal from Firebox More frequently depending on the fuel type or ash build up OR X Beneath Heat Exchanger Every 1 ton of fuel OR X Blower Combustion Exhaust More frequently depending on the fuel ty...

Страница 30: ...sal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container until all cinders have thoroughly cooled Other waste shall not be plac...

Страница 31: ...left behind from the use of the cleaning rods for the heat exchanger tubes c The ash will be resting on the back of the baffle This will require removing the cast baffle Please refer to page 35 for a...

Страница 32: ...on adjustable but the gasketing between the glass and firebox should be inspected periodically to make sure there is a good seal 16 Preparing Firebox for Non Burn Season Frequency Yearly By Homeowner...

Страница 33: ...An inefficient and non economical method of burning of fuel caused by poor quality pellet fuel is shown in Figure 33 2 The correct flame size when good quality premium pellet fuel is burned is shown i...

Страница 34: ...the thermostat block and disconnect the 2 yellow wires e Remove the 2 screws from the power inlet and rotate it through the hole and out of the screen leaving the wires attached f Disconnect the vacuu...

Страница 35: ...ont of the housing and very carefully bend the 2 housing sides out and bend the back of the housing away from the blower This allows for room to access the back 2 screws and nuts 4 total that is secur...

Страница 36: ...el by loosening 2 screws do not remove and pull side panel away 3 The wire leads to the igniter are connected to the wire harness black wires with 1 4 inch male female spade connectors Disconnect the...

Страница 37: ...for 120 volt 60 Hz standard current Make sure the outlet is grounded and has the correct polarity A good surge protector is recommended When operating with a generator you need a least 600 watts of p...

Страница 38: ...ly reset itself 19 Snap Disc 3 Back Burn Protector 250 F Snap disc 3 is mounted on the back of the auger tube in the center of the appliance and has a red reset button To access it remove the right si...

Страница 39: ...vection Blower Housing Feed Motor High Med Low Heat Output Switch Reset Button Reset Button Combustion Blower TERMINAL BLOCK CENTER 2 SCREWS FOR THERMOSTAT WIRES POWER OUTLET FUSE Fuse Red Call Light...

Страница 40: ...chase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer d...

Страница 41: ...Pellet Stove R Castile Pellet Insert WARRANTY CONDITIONS This warranty is void if LIMITATIONS OF LIABILITY 8 K N N OQ R U Z 8 88 U 8 U Q 8 N N Q Z R N U Q 8 R Z N N 88 N U Q 8 N O K WARRANTY EXCLUSION...

Страница 42: ...Page 42 7021 130F May 12 2014 Castile B FS Pellet Stove...

Страница 43: ...May 12 2014 7021 130F Page 43 Castile B FS Pellet Stove...

Страница 44: ...502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 6769426 6774802 6796302 6840261 6848441 6863064 6866205...

Отзывы: