5100 Insert ACC

The  following  modifications  of  factory-built  fireplaces  are 

permissible:

• 

The fireplace must not be altered. Cutting any sheet 

metal parts of the fireplace in which the fireplace insert 

is to be installed is prohibited per 

ANSI Z21.88

 except 

that the damper may be removed to accommodate a 

direct-connect starter pipe or chimney liner,

• 

External trim pieces which do not affect the operation 

of the fireplace may be removed providing they can be 

stored on or within the fireplace for reassembly if the 

insert is removed.

• 

The permanent metal warning label provided in the 

component pack must be attached to the back of the 

fireplace, with screws or nails, stating that the fireplace 

may have been altered to accommodate the insert, 

and must be returned to original condition for use as a 

conventional fireplace (

Figure 16.1)

.

• 

If the hearth extension is lower than the fireplace 

opening, the portion of the insert extending onto the 

hearth must be supported. 

• 

Manufacturer designed adjustable support kit can be 

ordered from your dealer.

• 

Final approval of this installation type is contingent 

upon the authority having jurisdiction.

M. Altering The Fireplace

WARNING

THIS FIREPLACE MAY HAVE BEEN ALTERED

TO ACCOMMODATE AN INSERT. IT MUST BE 

RETURNED TO ITS ORIGINAL CONDITION 

BEFORE USE AS A SOLID FUEL BURNING 

FIREPLACE.

250-2061

Figure 16.1

Ovalizing round stainless steel liners to accommodate the 

liner passing through the damper region of a fireplace is an 

allowable and acceptable practice.

Ensure that the ovalization is minimized to the extent 

required to fit through the damper.

L. Ovalizing Round Stainless Steel Liners

N. Zero-Clearance Fireplace

A permit may be required for installations, final approval is 

contingent of the authority having local jurisdiction. Consult 

insurance carrier, local building, fire officials or authorities 

having jurisdiction about restrictions, installation inspection, 

and permits.

Inspect the existing fireplace and chimney for any damage 

or flaws such as burnouts, metal or refectory warping.

Inspection to a minimum of 

NFPA 211

 Level II is 

recommended. All repairs must be made prior to installing 

an insert. The fireplace must be structurally sound and be 

able to support the weight of the solid-fuel insert

The factory-built chimney must be listed per 

UL 127 or 

ULC 610-M87

 for all installations. Install thermal protection 

per this appliance listing requirements.

A full height 6 inch diameter stainless steel full height 

listed chimney liner must be installed meeting type HT 

(2100°F) requirements per

 UL 1777 (USA) or ULC S635 

with “0” clearance to masonry (Canada). The full liner must 

be attached to the insert flue collar and to the top of the 

existing chimney. 

The flue liner top support attachment must not reduce the 

air flow for the existing air-cooled chimney system. Re-

install original factory-built chimney cap only; see section 

on 

Prefabricated Metal Chimney

 on page 15.

To prevent room air passage to the chimney cavity of the 

fireplace, seal either the damper area around the chimney 

liner or the insert surround. Circulating air chamber (i.e. in a 

steel fireplace liner or metal hearth circulatory) may not be 

blocked. The air flow within and around the fireplace shall 

not be altered, blocked by the installation of the insert. (i.e. 

no louvers or cooling air inlet or outlet ports may be blocked 

by the insert or the insert surround. 

See 

Altering the Fireplace

 on page 16 for modifications 

allowed for factory-built fireplaces.

The following parts may be removed:

Damper

Smoke Shelf or Baffle

Ember Catches

Fire Grate

Viewing Screen/Curtain

Doors

Asphyxiation Risk.

DO NOT connect this appliance to a chimney 

flue servicing another appliance or to any air 

distribution duct or system.

This may allow flue gases to enter the house.

WARNING

Содержание 51I-ACC-BK

Страница 1: ...as specified Failure to comply may cause house fire NOTE To obtain a French translation of this manual please contact your dealer or visit www quadrafire com Pour obtenir une traduction fran aise de c...

Страница 2: ...rculating Masonry 15 K Prefabricated Metal Chimney 15 L Ovalizing Round Stainless Steel Liners 16 M Altering The Fireplace 16 N Zero Clearance Fireplace 16 5 Appliance Set Up 17 A Outside Air Kit Inst...

Страница 3: ...hted average HHV efficiency using Douglas Fir dimensional lumber and data collected during EPA emissions test A range of BTU outputs based on EPA Default Efficiency and the burn rates from the low and...

Страница 4: ...ance without fully assembling all components Operating appliance without legs attached if supplied with appliance Do NOT Over fire If appliance or chimney connector glows you are over firing Any such...

Страница 5: ...draft should be approximately 10 inch W C Measure the W C at 6 inches 152mm above the top of the appliance after one hour of operation at each burn setting B Draft Check building codes prior to instal...

Страница 6: ...2 3 4 in length 6 or 8 self drilling screws Fire Risk Inspect appliance and components for damage Damaged parts may impair safe operation Do NOT install damaged components Do NOT install incomplete c...

Страница 7: ...appliance and given to the party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this c...

Страница 8: ...mm 29 1 8 in 740mm 17 5 8 in 448mm 13 1 8 in 333mm Figure 8 5 Side View with Steel Surround and Optional Offset Adapter OFFSET ADAPT Figure 8 4 Side View with Steel Surround Figure 8 2 Front View with...

Страница 9: ...pth 17 7 8 454 B Clearances to Combustibles United States and Canada UL and ULC In Canada a full length 6 inch 152mm S635 flue liner required as per ULC S628 In USA a minimum 5 ft length 1 82m 6 inch...

Страница 10: ...eat transfer R value is convenient when more than one material is used since you can add the R values together whereas you can not do this for k value The HIGHER the R factor means less heat is being...

Страница 11: ...arm space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wi...

Страница 12: ...there are other factors that affect flue draft B Chimney Termination Requirements Follow manufacturer s instructions for clearance securing flashing and terminating the chimney Figure 12 1 12 2 Must h...

Страница 13: ...configuration the greater the likelihood it may affect performance Chimney height may need to be increased by 2 3 per each 1000 feet above sea level It is not recommended to use offsets or elbows at...

Страница 14: ...nimum Clearance in Accordance with Insert Listing Floor Protection in Accordance with Insert Listing Follow Manufacturer s Instructions for Maximum Liner Extension Above Chimney Maximum 30 Degrees Off...

Страница 15: ...with Non Combustible Material Minimum Clearance in Accordance with Insert Listing Floor Protection in Accordance with Insert Listing Combustible Floor Airtight Insulated Clean Out Stainless Steel Chi...

Страница 16: ...Consult insurance carrier local building fire officials or authorities having jurisdiction about restrictions installation inspection and permits Inspect the existing fireplace and chimney for any dam...

Страница 17: ...fireplace is sufficient to feed the 4 inch flex 4 After sliding can into fireplace feed flex into cut opening to obtain outside combustion air 5 Level outer can and install appliance 6 Remove 4 bolts...

Страница 18: ...Appliance Dimensions page for the amount of distance this accessory can telescope between the flue collar and stove pipe liner 1 Remove the cast iron flue collar from the appliance and flip it upside...

Страница 19: ...the surround set 6 Install the surround set and trim set to the outer can Place the hook in the surround sides over the surround attachment screws 2 on each side Figure 19 5 7 Place top on top of app...

Страница 20: ...ons tat are made to the snap disc Disconnect the wires that attach to the snap dis Figure 20 4 8 Using pliers pry on the tabs that retain the harness enough to remove the harness Do not disconnect the...

Страница 21: ...13 2020 7047 910J 21 5100 Insert ACC Figure 21 1 Figure 21 2 Remove Control Plate Remove Strain Relief Disconnect Wires to theSnap Disc Figure 21 3 Figure 21 4 Place Harness Under Tabs Figure 21 5 Fig...

Страница 22: ...t metal shears cut trim along the marked edge The cut edge fits under lip of top trim so it allows for some variance in your straight edge 5 The double sided tape that holds front and side trims to sc...

Страница 23: ...tside combustion air supply to the fireplace fire chamber and the chimney must be listed to UL103 HT or a listed UL 1777 full length six inch 152mm diameter liner must be used It must be equipped with...

Страница 24: ...24 7047 910J January 13 2020 5100 Insert ACC A Service and Maintenance Log Date of Service Performed By Description of Service 7 Reference Materials...

Страница 25: ...January 13 2020 7047 910J 25 5100 Insert ACC B Accessories List...

Страница 26: ...and maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this applianc...

Отзывы: