Page 28
7047-148C
December 20, 2011
R
51I ACC Wood Insert
Recommended
Location
Marginal
Location
Location
Not
Recommended
Recommended
Location
Location NOT
Recommended
Multi-level Roofs
Windward
Leeward
Outside Termination Cap
Figure 28.1
E. Chimney Termination Requirements
Follow manufacturer’s instructions for clearance, securing
flashing and terminating the chimney.
•
Must have an approved and Listed cap
•
Must not be located where it will become plugged by
snow or other material
• Must terminate at least 3 feet (91cm) above the roof
and
at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
• Must be located away from trees or other structures
D. Locating Your Stove & Chimney
Location of the appliance and chimney will affect perfor
-
mance. As shown in
Figure 28.1
the chimney should:
• Install through the warm space enclosed by the build
-
ing envelope. This helps to produce more draft, espe
-
cially during lighting and die down of the fire.
• Penetrate the highest part of the roof. This minimizes
the affects of wind turbulence and down drafts.
• Consider the appliance location in order to avoid
floor and ceiling attic joists and rafters.
•
Locate termination cap away from trees, adjacent
structures, uneven roof lines and other obstruc
-
tions.
Your local dealer is the expert in your geographic area and
can usually make suggestions or discover solutions that will
easily correct your flue problem.
NOTICE
:
• Chimney performance may vary.
• Trees, buildings, roof lines and wind conditions affect
performance.
• Chimney height may need adjustment if smoking or
overdraft occurs.
NOTICE: Locating the appliance in a basement or in a location
of considerable air movement can cause intermittent smoke
spillage from appliance. Do not locate appliance near
• Frequently open doors
• Central heat outlets or returns