Chapter 

1

Introduction

t

he

 rsm-5

C

 

anD

 rsm-5

The RSM-5c and RSM-5 products are single-tenant digital electric meters 
used for commercial, residential or industrial applications.  The meters record 

interval data from hourly down to 15 minutes which allows flexible load profiling 

and Time-of-Use (TOU) billing options.  They also measure four-quadrant 
energy, power-down events, frequency, etc. enabling the user to analyze power 
quality.

Using a Pulse Datalogger the RSM-5c and RSM-5 are capable of collecting pulse 
data from any device capable of dry contact outputs, such as water, gas, or BTU 
meters.  The Pulse Datalogger can count pulses for up to 4 discrete meters, 
even during power loss events.

P

oWer

 l

Ine

 C

ommunICatIons

 (PlC)

Power Line Communications, or PLC, is a method of transferring meter data 
via the existing electric power wires that serve each tenant in a building. 
Quadlogic employs a patented method of PLC to move large amounts of 
metered data for residential and commercial and industrial (C&I) customers to 
a central collection point.  All Quadlogic meters can communicate over power 
lines. For more information about Quadlogic’s PLC please visit our website at 
www.quadlogic.com.

1

I

nstallatIon

 C

autIons

 

anD

 W

arnIngs

• 

Do not install if the device is damaged.  Inspect the meter box for obvious 

defects such as dents or cracks in the housing.

• If the device is installed or used in a manner not specified by the 

accompanying documents, the safety of the device may be impaired.

• 

If the device functions abnormally, proceed with caution.  The safety of 

the device may be impaired.

• 

Do not install the meter in the presence of explosive or combustible gas or 

gas vapor.

• 

Do not install the meter on an electrical service with current or voltage 

outside of the specified limits of the device.

• 

Do not operate the meter with the cover removed.

• 

To avoid electric shock, disconnect mains before replacing fuses.

• 

Beware of working around the meter when the voltage is live. There is a 

risk of electric shock.  

• For protection against fire, replace only with fuses of the specified voltage 

and current rating.

• 

Installation should be done by persons who have received training and 

are qualified to work with electricity and electrical metering equipment.  

All applicable national and local electrical codes and standards must be 
followed.  Failure to follow proper procedures may result in damage to the 
equipment and/or serious bodily harm including death.

• 

See instructions for connection diagrams.

Protective Conductor Terminal   

Securely fasten one end of the grounding wire (#12 AWG recommended) so 
that the grounding screw cuts the paint on the back box.  Securely fasten other 
end of the wire to true ground connection.  When grounding to the electrical 
conduit, use continuous metallic pipes, bending when necessary instead of 
using couplers.

Step 1: Mount the box

The RSM-5c or RSM-5 back box is the enclosure for the meter head.  The back 
box is supplied with the RSM-5c or RSM-5 fuse block installed in the box.  

1. Choose a section of wall to mount the meter.  This should be as close as 

possible to the distribution panel (preferably within 24”).  The RSM-5c and 
RSM-5 meters mount in a single metal box that must be attached to the 
wall and connected by conduit.  

RSM-5c and RSM-5 Installation

Chapter 

2

2

Содержание RSM-5c

Страница 1: ...Table of Contents Manual 3 Phase kWh 3 Phase Demand Single Phase kWh...

Страница 2: ...RSM 5c RSM 5 Installation Manual Power Line Communications Metering Systems...

Страница 3: ...6 Chapter 4 Menu Navigation 11 Chapter 5 Verifying Meter Functionality 15 Chapter 6 Resetting Demand Values For D Models 18 Chapter 7 Reading the Display 19 Chapter 8 Metering Specifications 21 Chapte...

Страница 4: ...raining and are qualified to work with electricity and electrical metering equipment All applicable national and local electrical codes and standards must be followed Failure to follow proper procedur...

Страница 5: ...abnormally proceed with caution The safety of the device may be impaired Do not install the meter in the presence of explosive or combustible gas or gas vapor Do not install the meter on an electrical...

Страница 6: ...on with a 12 AWG stranded wire with white insulation These voltage connections can be made in any way that meets local codes and requirements A service disconnect switch for the hot wires is required...

Страница 7: ...nd 4 above for each CT until all CTs have been installed and connected to the MCI screw terminals Chapter 2 RSM 5c and RSM 5 Installation 5 The following diagrams show the necessary fuse block connect...

Страница 8: ...nnections Figure 3 3 1 Phase 3 Wire 120 240V 120 208V or 277 480V Network Fuse Block Connections Chapter 3 Fuse Block Connections 8 Figure 3 4 RSM 5 3 Phase 4 Wire Wye with High Current Adapter HCA 16...

Страница 9: ...ogic com COPYRIGHT 2008 www quadlogic com Figure 3 6 RSM 5 3 Phase 4 Wire Wye with High Current Adapter HCA All CTs must be the same primary amperage and secondary amperage must be 5 Amp 9 10 Chapter...

Страница 10: ...hown in figure 4 3 Each main menu heading will be displayed in two second intervals Note that the RSM 5c and RSM 5 default to the kWh register Figure 4 2 Meter LCD Main Menu headings Chapter 4 Menu Na...

Страница 11: ...COPYRIGHT 2008 www quadlogic com COPYRIGHT 2008 www quadlogic com Chapter 4 Menu Navigation Figure 4 4 Display Menu Structure For an RSM 5c and RSM 5 Meter 13 Chapter 4 Menu Navigation 14...

Страница 12: ...Display Scroll button Scroll down by pressing and releasing the Display Scroll button until the following screen is displayed The A mperage reading is the indication of current The A mperage reading...

Страница 13: ...as above 17 Resetting Demand Values For D Models Chapter 6 BE CERTAIN TO RECORD THE CURRENT PEAK DEMAND WITH THE TIME AND DATE BEFORE RESETTING THE DEMAND Once the user resets the demand according to...

Страница 14: ...ge How CT multipliers are calculated 0 1 Amp CTs The multiplier values for CTs with 0 1A secondary ratings are derived by dividing the primary side rating by 100 For example a 50 0 1A rated CT will ha...

Страница 15: ...r off 500msec Max Pulse Rate Power on 10pulses sec max Power off 1 pulse sec max 21 Chapter 8 Metering Specifications When RSM 5 loses power the pulse accumulator still has the capability to record pu...

Страница 16: ...for the RSM 5c and RSM 5 products and include the complete meter assembly meterhead fuse block and back box as well as the required current transformers CTs for operation Meters CTs not included page...

Страница 17: ...s RSM5c 120200 3SL includes 3 SOLID CORE CTs RSM5c 277100 3SL includes 3 SOLID CORE CTs RSM5c 277200 3SL includes 3 SOLID CORE CTs 25 Chapter 9 Ordering Information RSM 5 Meter Kits kWh for Large Serv...

Страница 18: ...alog 120 208V 277 480V 1600 3200 1600 3200 3 SPLIT CORE Figure 3 4 Volts Amps kWh and Demand CTs included Diagram 3 Phase Demand Meter Delta DTA RSM5 480DTA1600 2D RSM5 480DTA3200 2D Catalog 1600 3200...

Страница 19: ...mand kWh Demand 4 Pulse Inputs Diagram 3 Phase Meter DELTA DTA A B C N Single Phase kWh Meter Wye RSM5c 120 2PH RSM5c 277 2PH Catalog 120 208V 277 480V 0 1A Figure 3 3 Volts Amps kWh Only Diagram C A...

Страница 20: ...ts Diagram 3 Phase Meter DELTA DTA 0 1Amp A B C N C A B Dimension 13 5 X 8 5 X 4 5 RSM5 480DTA01A D RSM5 480DTA01AMD RSM5 480DTA01ARSD RSM5 480DTA01A PD Catalog 480V 0 1A Figure 3 2 Volts Amps kWh Dem...

Страница 21: ...and 4 Pulse Inputs Diagram 3 Phase Meter DELTA DTA CL10 accepts one or two sets of 5Amp CTs A B C N B C A RSM5 480DTACL10 D RSM5 480DTACL10MD RSM5 480DTACL10RSD RSM5 480DTACL10 PD Catalog 480V 10A Fig...

Страница 22: ...Added clarifying note Correction of memory size to 512 kilobyte Meets ANSI C12 1 Correction of voltage to 480V Delta Qualified fuse type Use shielded twisted pair for 50 CT extensions Deleted amperage...

Страница 23: ......

Страница 24: ...QUADLOGIC 33 00 Northern Blvd Long Island City NY 11101 Tel 212 930 9300 Fax 212 930 9394 www quadlogic com RSM5 5c MANR2 0 R...

Страница 25: ...3 Phase kWh...

Страница 26: ......

Страница 27: ......

Страница 28: ...3 Phase Demand...

Страница 29: ......

Страница 30: ......

Страница 31: ...Single Phase kWh...

Страница 32: ......

Страница 33: ......

Отзывы: