AN-X-TI-MAS Page
35
AN-X supports RPIs from 5 to 750 ms.
Select an RPI appropriate to the remote I/O network scan time. You can
use the diagnostic counters (see page 29) to obtain the network scan
time.
IMPORTANT!
Ensure that any check box that refers to Unicast connections is
unchecked.
Input Only Connections
The AN-X-TI-MAS supports one input only connection from a
ControlLogix processor. The ControlLogix will be able to read the same
input data as the ControlLogix processor with the exclusive owner
connection to the AN-X-TI-MAS.
To configure the input only connection to the AN-X-TI-MAS in
RSLogix 5000:
1.
Right click on the ControlLogix Ethernet module that will be
communicating with the AN-X and select
Add Module
. Add a
1756-ENBT/A module. Set the Major Rev to 1.