QSK USKI-5 Скачать руководство пользователя страница 8

USKI-5 Universal Sequencer & Keying Interface 

 

© Copyright 2015 QSK, llc 

www.qskllc.com 

Page 7 

 

 

FIGURE 4 

 

 

USKI-5  PROGRAM  (D)

 is  similar  to  Program (A)  and  applies  to  stations configured  as 

shown in Figure 2 but has no provision for CW break-in operation. In some applications 
the required sequencing delays are of sufficient length that CW break-in operation at any 
reasonable  speed  is  not  possible.  In  these  cases  Program  (D)  can  be  used  with  only 
PTT control of transmit-receive operation. CW keying is still  connected to input J1T, as 
shown  in  Figure  2,  but  CW  keying  output  from  the  sequencer  is  only  applied  to  the 
transmitter  if  PTT  is  activated  via  input  J1R.  With  no  CW  activation  of  the  timing 
sequence, Program (D) only requires setting of PTT sequencing delays.

 

TIMING CONSIDERATIONS 

If the sequencer is controlling RF sensitive devices such as TMAs or transverters, make 
sure to allow a sufficient amount of time for switching to avoid component damage from 
transmitter power output. If in doubt, add extra time to be on the safe side!! The user is 
responsible for correct programming and use of the USKI-5 sequencer. 

During normal receive-transmit-receive sequencing, the transmitter will be the last device to be 
turned on (started) and first to be turned off (ended). In CW operation it is important to have the 
transmitted  signal’s  time  duration  the  same  as  that  of  the  control  signal.  Therefore  it  is 
necessary to compensate for the time lost in the START delays. This is easily done by simply 
setting END_DEL_5 equal to the sum of all the START DELAYS. 

For modes of operation other than CW, timing delays for  various components  during transmit-
receive switching is not usually as important. Tens or hundreds of milliseconds delays can often 
be  tolerated  without  adversely  affecting  operations.  For  CW  full  break  in  (QSK)  operation 
however,  proper  timing  is  critical.  Sequencing  delays  are  necessary  but  in  the  interest  of 
maximizing receive time, it is important that the delays be as short as possible consistent with 
proper operation.  

For  a given  sum  of  START  and  END  delays,  there  is  a  maximum  CW speed  possible  without 
introducing errors. If the sum of is too long, the control signal could go low or “key down” before 

 

Содержание USKI-5

Страница 1: ...QSK llc USKI 5 Universal Sequencer and Keying Interface Rev D...

Страница 2: ...bit capability Non volatile memory Five output channels four input control channels Delays programmable from zero to minutes and more in 1 ms steps Silent high speed opto isolated solid state relay co...

Страница 3: ...r inverted normally closed operation Once programmed the USKI 5 can be operated with or without connection to the programming computer The stored program is nonvolatile and no backup batteries are req...

Страница 4: ...ter begins the attack portion of a symbol and must remain on until after decay is complete This same principal also applies to any power amplifier or antenna switching that may occur along with transm...

Страница 5: ...upt is activated transmitting will be inhibited regardless of the state of other inputs If the program has already begun the transmitting sequence an interrupt condition will cause the program to imme...

Страница 6: ..._3 the program will immediately switch off OUTPUT 3 disregarding the time remaining of TX_START_DEL_3 and will continue by switching off OUTPUT 2 and 1 in sequence with delays TX_END_DEL_2 and TX_END_...

Страница 7: ...nction Several station configurations are suitable for control with Program C Probably the most common is shown in figure 3 the order of connections for outputs 1 4 may be different depending on the s...

Страница 8: ...me to be on the safe side The user is responsible for correct programming and use of the USKI 5 sequencer During normal receive transmit receive sequencing the transmitter will be the last device to b...

Страница 9: ...operation up to 50 WPM the sum of START and END delays must be less than 24 ms USKI 5 PREPARATION FOR USE The USKI 5 is shipped without the output relays installed Remove the four 1 Pozidriv screws a...

Страница 10: ...t File Save As and add the extension bas to the file name as indicated below and then select Save The file will be saved with the proper extension Connect the sequencer to the computer with the USB ca...

Страница 11: ...e called CW_START_DEL PTT_START_DEL or TX_START_DEL for example It may be helpful to first fill out a timing delay work sheet shown in the notes section at the end of this document Change the START an...

Страница 12: ...gram they may include cwstart cwend pttstart pttend txstart or txstend routines For any inverted channel change high to low in the start routines of the program and low to high in the end routines of...

Страница 13: ...g input devices connected to the sequencer and without the outputs connected to the station equipment Once the correct relative sequencing has been confirmed the sequencer can be reprogrammed with the...

Страница 14: ...g delays Remember that for Programs A B or C the sequence will progress from left to right for the start delays and from the right to the left for the end delays For the output connections shown in pr...

Страница 15: ...t to be on the safe side it is the first device switched off or out of circuit In this example it is assumed that there are mechanical relays which do this switching and transition in 10 ms In case th...

Страница 16: ...CW mode particularly QSK operation Since transmitter PTT is not connected to the sequencer this allows for up to five other external devices to be controlled This example is for a station with separat...

Страница 17: ...ch CW symbol envelope before turning off the VFO If the VFO turns off its RF output quickly the RX mute end delay can be set to zero If not and sometimes for cleaner sounding QSK operation sometimes a...

Страница 18: ...RING 5 C 2 OUTPUTS OUTPUT NUMBER 14M2 PIN NUMBER PIN PROGRAM DESIGNATION 1 12 B 1 2 11 B 2 3 10 B 3 4 9 B 4 5 8 B 5 USEFUL INFORMATION Enhanced switching capabilities over what is possible with the st...

Отзывы: