70
Figure 5
More than 30cm
More than 200cm
More than 60cm
More than 30cm
More than 60cm
Fence or barrier
•
When determining the location of the exterior unit take into account the possible location of the
interior unit. The interior and exterior units must be connected by pipes and cables.
G
TAKE CARE
For the SC42xx & SC52xx models: The length of the piping is 4 metres.
For the S42xx & S52xx(B) & SJA2519 models: For units with a capacity of up to 6.0 kW, the
maximum pipe length between the inside and the
outside part is 20 metres. For units with a capacity
> 6.0 kW, the maximum pipe length between the
inside and the outside part is 30 metres.
For units with a capacity of up to 6.0 kW, the
maximum difference in height between the inside
and the outside part is 8 metres. For units with a
capacity > 6.0 kW, the maximum difference in height
between the inside and the outside part is 20 metres.
•
Do not place animals and plants or other obstacles in the path of the air inlet or outlet.
•
Always install the air conditioner at an easily accessible location.
•
Consult and follow local legislation regarding mounting and installation of air conditioner equip-
ment.
•
In the case that the installation place is exposed to strong wind such as a seaside, make sure the fan
is operating properly by putting the unit lengthwise along the wall or using a dust or shield plates.
See picture 6.
Strong
wind
Strong
wind
Barrier
Incorrect
Correct
Figure 6
Strong
wind
Strong
wind
Wall
Incorrect
Correct
•
If the exterior unit is installed on a roofing structure or exterior wall then it can result in bothersome
noise and vibrations.
•
Ensure that the exterior unit can be attached to a stable substructure.
4
70