Terminal block
Wire cover
Screw
Cable clamp
Fig. 3.9
The Wiring Diagram is located
on the inside of the indoor unit’s
wire cover.
Figure 19
d.
The cable can be fed through from the back of the interior unit to the terminal strip.
e.
Connect the electrical wires to the terminal strip, for the correct location see fig 20.
f.
Attach the cable of the indoor unit. Remove the cover plate of the terminal strip of the outdoor unit.
g.
Connect the connection cable to the terminal strip (zie picture 21). Attach the cables so that the
position of the wires matches the connection of the cables to the indoor unit.
h.
The earth cable must be connected directly to the metal plate on which the terminal strip is mounted.
The location is indicated with the symbol
i.
In models with a capacity of up to 6.0 kW, the supply cable is already preassembled on the inside part.
j.
Only connect the power supply cable once the entire installation of the air conditioner has been
completed.
G
TAKE CARE
For models with a capacity < 4.5 kW plug the plug into a wall socket.
11. EVACUATING THE COOLING SYSTEM OF THE S 3825 & S 3832 MODELS
Air and moisture that remain in the refrigerant system, e.g. after installation, can cause undesirable effects
or damage as indicated below:
•
Pressure in the system rises.
•
Operating current rises.
•
Cooling or heating efficiency drops.
•
Moisture in the refrigerant circuit may freeze and block capillary tubing.
•
Water may lead to corrosion of parts in the refrigeration system.
•
Damage of the compressor.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must always be leak tested
and evacuated with aid of a vacuum pump to remove any noncondensables and moisture from the system.
G
TAKE CARE
Evacuating the coolant piping and the interior unit of the air conditioner must in accordance with
the applicable national regulations and laws. Evacuating the coolant piping and the interior unit
may only be carried out by a certified air conditioner fitter.