[ Table 7-12 : Battery Operation General Events List ]
B46P
BAT5 CEL
OT P
BAT5 Cell Over Temp
Protection
When the maximum cell temperature is
above protection level, thus terminating the
system.
Automatically returns to normal when the
maximum cell temperature goes below
the limit value.
WEB Display
HMI Display
Description
Measures
B47P
BAT5 COM P
BAT5 Communication
Protection
Power reset of the system is required. If the
symptom persists after reset, replace the
cable connecting the Battery pack and the
INVERTER. After replacement, repair of BMS
or PCS Control Board is necessary.
B48P
BAT5 ADD P
BAT5 Additional
Protection
Power reset of the system is required.
If the symptom still occurs after reset, repair
of BMS or PCS Control Board is necessary.
Message Description
I
60