20
PREVENTIVE MAINTENANCE
PWCs are designed to last a long time and to give maximum performance and reliability with
minimum maintenance. To prolong the life of the unit, regular maintenance must be performed
as specified below:
OFF SEASON STORAGE—WINTERIZATION
Before placing the unit into storage for the off-season, it is recommended to thoroughly clean the
unit, and remove all water in the CONDENSER COIL, WATER LINES, DRAIN PAN and CON-
DENSATE PUMP to avoid damage to the unit from freezing water or
contamination.
DRAINING THE CONDENSER COIL, AND INTERIOR WATER LINES
To drain the condenser coil, detach the WATER IN and WATER OUT lines. Using a Shop-Vac
or similar devise, vacuum the WATER OUT line and start the unit. The water valve will open,
allowing you to vacuum the water out of the condenser coil. Eventually, the High Pressure Cut-
Out will shut down the compressor. Wait 15 minutes, depress the HI PRESSURE RESET and
repeat this process until ALL of the water is out of the system. When completed, depress the
HIGH PRESSURE RESET one final time to make sure that it is reset.
BLOWER MOTOR
The evaporator motor on all units have permanently lubricated bearings. No oiling is necessary
FILTER
A clogged filter will cause the unit to operate at greatly reduced efficiencies. We recommend that
the filter be inspected on a regular basis
(every six weeks or less)
depending on the
environment. The evaporator filter is located behind the return air grille and can be easily
removed and cleaned. The filter must be washed periodically as needed by placing it in a
dishwasher or soaking in a solution of warm water and detergent for 10 minutes. Then rinsing
clean with hot water and shaking excess moisture from filter.
DRAINING THE HOSE KIT
To drain the hose kit, disconnect all hoses, and allow the hoses to gravity drain.
EVACUATING THE CONDENSATE PUMP
Using a Shop-Vac or similar device, vacuum all water out of the condensate pump reservoir.
Condensate pumps come standard on all PWC models. When servicing pump, follow these
steps:
1. Make certain that the unit is disconnected from the power source before attempting to
service or remove any component.
2. Be sure the floats move freely. Clean as necessary.
3. Remove the pump housing and check for obstructions. Clean as needed.
4. Clean the housing with warm water and mild soap when mineral deposits are visible.
5. Check the inlet and outlet piping. Clean as necessary. Be sure there are no kinks in the lines
that would inhibit flow.
GENERAL
OceanAire products are NOT approved for outdoor use. Therefore, off-season storage should
be indoor, protected from weather conditions.
When necessary maintenance steps outlined above are followed, the air conditioner will provide
long and reliable service. The refrigeration and electrical circuits of the system should only be
serviced by a fully qualified service technician.
Содержание PWC series
Страница 24: ...22 WIRING SCHEMATIC FOR PWC1211 PWC1811 PWC2412 and PWC3612 07182016 ...
Страница 25: ...23 WIRING SCHEMATIC FOR PWC6012 07182016 ...
Страница 27: ...25 WIRING SCHEMATIC FOR PWC3632 ...
Страница 28: ...26 WIRING SCHEMATIC FOR PWC6032 ...
Страница 29: ...27 WIRING SCHEMATIC FOR PWC3634 and PWC6034 ...
Страница 32: ...TECH NOTES Form EISM PWC 02272017 ...