Installation and Operation Manual
Q
F
ire – Fire Brigade Switch
7
TROUBLESHOOTING AND REMEDY
Contact our service to troubleshoot faults and errors, see chapter 6.3 TECHNICAL SUPPORT, page 23.
SYMPTOM
POSSIBLE CAUSE
REMEDY (contact service)
Q
F
ire system can not be turned-
on with the control box main
switch „on“ = „1“
LED Power : off
LED SPD : off
LED Error : off
LED Power : off
LED SPD : red
LED Error : red
Emergency stop:
•
connector was not plugged in
•
connector was not bridged (in
case option not available)
•
wrongly installed as opener ins-
tead of closer
•
Plug-in emergency stop connector
•
Bridge the connector
•
Correct installation
•
Control line broken
•
Undervoltage on control lines
(system partly off)
•
Check control lines and replace, if nee-
ded
•
Installed control lines to long or less dia-
meter – Replace control lines with ca-
bles of right length and diameter
Q
F
ire system can not be turned-
off with the control box main
switch „off“ „0“
LED Power : green
Q
F
ire control box defective
•
Deinstall control box
•
Bridge the PV strings (for continuing
operation of the PV generator)
•
Replace control box
LED Power : green
LED SPD : red
LED Error : off
SPD tripped due to overvoltage
Shut-down PV generator:
•
Turn control box main switch to „off“ „0“.
•
Check all PV strings.
No connection on remote output
•
Check wiring of SPD block
– measurement must show low impen-
dance
SPD component in switch box de-
fective
•
Check switch boxes SPD components
for red LED indication.
•
Pull out and replace defective SPD
bock.
Emergency stop does not work
Plug contact still bridged
•
Remove bridge contact.