4.8 Fine Tuning during Test Runs (Adjust the Control Function)
160
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
◆
Closed Loop Vector Control Method
Table 4.19 Parameters for Fine Tuning the Drive (Closed Loop Vector Control Method)
Issue
Parameter
Number
Solution
Default
Setting
Recommended Setting
•
Torque or speed response are slow.
•
Hunting or oscillation
•
High speed
C5-01 [ASR
PGain 1]
•
Low speed
C5-03 [ASR
PGain 2]
•
If torque or speed response are slow, increase the setting
value in increments of 5.00.
•
If hunting or oscillation occur, decrease the setting
value.
20.00
10.00 - 50.00
•
High speed
C5-02 [ASR
ITime 1]
•
Low speed
C5-04 [ASR
ITime 2]
•
If torque or speed response are slow, decrease the
setting value.
•
If hunting or oscillation occur, increase the setting
value.
0.500 s
0.300 to 1.000 s
The drive cannot find ASR proportional
gain or integral time for low speed or
high speed.
C5-07 [ASR Gain
Switch Frequency]
Change the ASR proportional gain and ASR integral time
to conform to the output frequency.
0.0 Hz
0.0 Hz to maximum output
frequency
Hunting or oscillation
C5-06 [ASR Delay
Time]
•
If torque or speed response are slow, decrease the
setting value in increments of 10 ms.
•
If the rigidity of the machine is unsatisfactory and
vibration is possible, increase the setting value.
4 ms
4 to 20 ms
•
The volume of the motor excitation
sound is too high.
•
Hunting or oscillation at low speeds
(3 Hz or lower)
C6-02 [Carrier
Frequency Selection]
•
If the volume of the motor excitation sound is too high,
increase the carrier frequency.
•
If hunting or oscillation occur at low speeds, decrease
the carrier frequency.
1 (2.0 kHz)
2.0 kHz to upper limit value
*1
Refer to the section on C5: ASR - SPEED REGULATION parameters for more information about speed control (ASR).
*2
Default value changes when
o2-04 [Drive KVA Selection]
and
C6-01 [ND/HD Duty Selection]
values change.
◆
Advanced Open Loop Vector Control Method
Table 4.20 Parameters for Fine Tuning the Drive (Advanced Open Loop Vector Control Method)
Issue
Parameter Number
Solution
Default
Setting
Recommended Setting
•
oS [Overspeed]
occurs.
•
Hunting or oscillation.
T1-01 [Auto-tuning Mode
Selection]
•
Make sure that the output of the drive and the motor
are connected correctly.
•
Decouple the motor and machine and do Rotational
Auto-Tuning.
-
0
The volume of the motor excitation
sound is too high.
C6-02 [Carrier Frequency
Selection]
If the volume of the motor excitation sound is too high,
increase the carrier frequency.
1 (2 kHz)
1 to upper limit value
Speed precision is unsatisfactory
E2-02 [Mot Rated Slip]
•
Decouple the motor and machine and do Rotational
Auto-Tuning.
•
If the motor speed is slow, increase the value of
E2-
02
in small increments (approximately 0.1% of the
default setting value).
•
If the motor speed is fast, decrease the value of
E2-
02
in small increments (approximately 0.1% of the
default setting value).
Set to a value that is ±5% of
the current value.
•
Torque or speed response are
slow.
•
Hunting or oscillation
•
High speed
C5-01 [ASR PGain 1]
•
Low speed
C5-03 [ASR PGain 2]
•
If torque or speed response are slow, increase the
setting value in increments of 5.00.
•
If hunting or oscillation occur, decrease the setting
value.
20.00
10.00 - 50.00
•
High speed
C5-02 [ASR ITime 1]
•
Low speed
C5-04 [ASR ITime 2]
•
If torque or speed response are slow, decrease the
setting value.
•
If hunting or oscillation occur, increase the setting
value.
0.500 s
0.300 to 1.000 s
The drive cannot find speed response
for low speed or high speed.
•
C5-07 [ASR Gain Switch
Frequency]
•
High speed
C5-01 [ASR PGain 1]
C5-02 [ASR ITime 1]
•
Low speed
C5-03 [ASR PGain 2]
C5-04 [ASR ITime 2]
Change the ASR proportional gain and ASR integral
time to conform to the output frequency.
0.0 Hz
0.0 to maximum output
frequency
Hunting or oscillation
C5-06 [ASR Delay Time]
•
If torque or speed response are slow, decrease the
setting value in increments of 10 ms.
•
If the rigidity of the machine is unsatisfactory and
vibration is possible, increase the setting value.
4 ms
4 to 20 ms
*1
Default value changes when
o2-04 [Drive KVA Selection]
and
C6-01 [ND/HD Duty Selection]
values change.
*2
Default value changes when
o2-04 [Drive KVA Selection]
value changes.
*3
Refer to the section on C5: ASR - SPEED REGULATION parameters for more information about speed control (ASR).
*4
The best values for a no-load operation are different than the best values for actual loading operation.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...