Q6S    

AC POWER SUPPLY 50W–300W

© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com 

Specification subject to change. Rev-12-23-20

COMPLIANT

Part Number Builder

The Q6S is a surface mount power supply center capable of mounting 

in all 6 planes. It is available from 50W-300W in 12 or 24V.

Technical Information

Mounting

• 

6 plane surface mount 

• 

Rod suspension (Two -1/4" threaded rods) 

Q6S

CK-S

Product

Size

1

Prim. V

Sec. V

No.

Brk. Amp

2

Choke

Color

3

50DT

100DT

150DT

300DT

120 (60Hz)

277 (60Hz)

12V

24V

1

2

3

5

10

12.5

15

20

25

WH (Standard)

BK

Secondary Breaker Amperage

Amps

Max 12V  

Load

Max 24V  

Load

5

60W

120W

10

120W

240W

12.5

150W

300W

15

180W

360W

20

240W

480W

25

300W

600W

Color

WH

  White (Standard)

BK

  Black Powder Coat Finish

Choke
CK-S

 150W-300W

Choke not required from 50W-100W

     1                2                 3              4                 5                 6

 W

ALL

CEILING

   

FLOOR

Size

Size

Max Load  

(Watts)

PSC  

Efficiency

Max PSC  

Rating 

(Watts)

Max PSC 

Rating 

(VA)

Max Prim 

Amps @ 

120V

Max Prim 

Amps @ 

277V

50DT

50W

92%

54

58

0.5 A

0.2 A

100DT

100W

92%

108

115

1.0 A

0.4 A

150DT

150W

92%

163

173

1.4 A

0.62 A

300DT

300W

92%

324

345

2.9 A

1.2 A

Содержание Q6S

Страница 1: ...Prim V Sec V No Brk Amp2 Choke Color3 50DT 100DT 150DT 300DT 120 60Hz 277 60Hz 12V 24V 1 2 3 5 10 12 5 15 20 25 WH Standard BK 2 Secondary Breaker Amperage Amps Max 12V Load Max 24V Load 5 60W 120W 10 120W 240W 12 5 150W 300W 15 180W 360W 20 240W 480W 25 300W 600W 3 Color WH White Standard BK Black Powder Coat Finish Choke CK S 150W 300W Choke not required from 50W 100W 1 2 3 4 5 6 WALL CEILING FL...

Страница 2: ...e connected to one 1 of the primary taps up to the full watt rating of the PSC 20 derating required The advantage is that the PSC can be tapped to recover voltage drop and produce between 85 100 light output NOTE See Voltage Drop Calculator at www q tran com Secondary Circuit Up to three 3 magnetic circuit breaker Amps 5A 10A 12 5A 15A 20A 25A NOTE Breakers are sized to the feed load per N E C Art...

Страница 3: ...age reading at the lamps CONNECT SECONDARY For detailed look at secondary see Diagram B Connect low voltage fixtures in one of the following methods CONNECT PRIMARY For detailed look of primary see Diagram A NOTE Voltages are fixed and can only be changed at the factory Voltages come in 120V 230V or 277V 1 3 5 4 2 Rod Suspension Surface Wall Surface Ceiling Surface Floor NOTE Rods not included 120...

Страница 4: ... AWG 14 AWG 12 AWG 10 AWG Max Load 12V 60W 120W 180W 240W 300W Max Load 24V 120W 240W 360W 480W 600W 12V 25A 120V 2 5A Transformer 300VA 10 AWG min 2 5A 25A 300VA 120V 300VA 12V ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF NOTE Switch or dimmer are always on the primary 15A circuit breaker use 14 AWG minimum 20A circuit breaker use 12 AWG minimum The neutral must be clean ...

Страница 5: ...d A number 6 or 8 gauge wire for instance can not be terminated on most L V products Diagram A For 12V track rail or cable system that is rated for 25A requires a minimum of 10 gauge wire Runs should be approximately the same length Diagram B For LV cove lighting the VDC might show you to vary the wire gauge to equalize the voltage at the lamp Running the same gauge wire to all runs may be wrong D...

Страница 6: ...OWN BLUE YELLOW VIOLET Tp Bkr s PRIMARY VOLTAGE SECONDARY 24 VAC Ɣ USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS Ɣ DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING L O A D L O A D OR TAP2 120V GREY RED 277V 4 50 Q6 WIRING DIAGRAM 3 50 If a transformer is wired from the factory for 12V for 24V secondary wiring Disconnect the blue and yellow wires from terminal blocks and connect together ...

Страница 7: ...our information on the lines provided Manufacturer Model number ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Risk of Fire Electric Shock Transformer should be installed by a Licensed electrician in accordance with the N E C and all local codes in force Wear rubber shoes and work on a sturdy wooden or fib...

Отзывы: