B07P
BAT1 COM P
BAT1 Communication
Protection
Power reset of the system is required.
If the symptom persists after reset, replace
the cable connecting the Battery pack and
the INVERTER. After replacement, repair
of BMS or PCS Control Board is necessary.
WEB Display
HMI Display
Description
Measures
B08P
BAT1 ADD P
BAT1 Additional
Protection
Power reset of the system is required.
If the symptom still occurs after reset, repair
of BMS or PCS Control Board is necessary.
B11P
BAT2 CHG
OC P
BAT2 Charge Over
Current Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
B12P
BAT2 DCHG
OC P
BAT2 Discharge Over
Current Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
B14P
BAT2 CEL
OV P
BAT2 Cell or Rack
Over Voltage Protection
When the maximum cell or rack voltage is
above protection level, thus terminating
the system.
Automatically returns to normal when the
maximum cell or rack voltage goes below
the limit value.
B15P
BAT2 CEL
UV P
BAT2 Cell or Rack
Under Voltage
Protection
When the minimum cell or rack voltage is
below protection level, thus terminating
the system.
Automatically returns to normal when the
minimum cell or rack voltage goes above
the limit value.
B13P
BAT2 CEL V
HOLD P
BAT2 Cell Voltage
Sensing Data Hold
Protection
Power reset of the system is required. If the
symptom still occurs after reset, repair of
BMS or PCS Control Board is necessary.