In normally smoky atmospheres the detector will not
go into alarm as long as the concentration is less
than the fixed sensitivity of the detector.  This results
in a sensitive and positive response with the lowest
potential for unwanted alarms.

The main enclosure of the detector contains the elec-
tronic circuitry, alarm relay, and supervision relay.  

FAILSAFE OPERATION

To ensure reliable operation, the Model 30-3003 is
equipped with self-checking circuitry.  A regulation
photodiode, which is matched to the smoke detec-
tion circuit, continuously monitors the output intensity
of the IRED and adjusts it as necessary to compen-
sate for an accumulation of dust or other contami-
nants, or any other variation that can occur with tem-
perature and time.  A power supervision relay in the
detector provides a trouble output signal in the event
of an input power failure.

The detector uses extensive filtering against RF and
transient interference.  In addition, there is a 2 sec-
ond time delay before an alarm is generated.

The printed circuit board inside the detector is coat-
ed to minimize the possibility of problems caused by
moisture accumulation.

DETECTOR OUTPUTS

The detector provides a set of Form A (SPST) NO
contacts for connection to the alarm output circuitry
and a set of SPST NC contacts for supervision of
input power.  An auxiliary set of Form C (SPDT)
NO/NC alarm relay contacts is also provided for con-
trolling remote annunciation devices.

The alarm output latches on in the event of an alarm
and an LED located on the outer surface of the hous-
ing is illuminated to provide a visual indication that an
alarm condition has occurred.  The detector is reset
by momentarily interrupting input power.

SPECIFICATIONS

OPERATING VOLTAGE—

20 to 28 vdc filtered supply, with less than 1.4 vpp at
60 to 120 Hz.

OPERATING CURRENT—

Standby:

10 milliamperes.

Alarm:

35 milliamperes.

TEMPERATURE RANGE—

Operating: –13°F to +140°F  (–25°C to +60°C).
Storage:

–67°F to +185°F  (–55°C to +85°C).

ALARM AND SUPERVISORY RELAY CONTACT
RATING—

1.0 ampere at 30 vdc, SPST.

AUXILIARY ALARM RELAY CONTACT RATING—

2.0 amperes at 30 vdc, Form C, SPDT.

JUNCTION BOX—

Body material:

Copper-free aluminum.

Cover:

Feraloy.

Conduit Fitting:

25 mm (female).

CERTIFICATIONS—

CSA Certified for use in Class I, Division 2, Groups A,
B, C and D hazardous locations.

DIMENSIONS—

See Figure 2.

WEIGHT—

2 pounds (0.91 kilogram)

INSTALLATION

The Model 30-3003 is intended for surface mounting.
See Figure 2.  The mounting screw holes are counter-
bored for No. 8 flat-head screws.  Electrical equip-
ment that is used in conjunction with the smoke
detector is connected to the detector using a termi-
nal strip located in the junction box that is furnished
with the unit.

DETECTOR LOCATION

The smoke detector is normally mounted on the ceil-
ing not less than six inches from a side wall.  The
exact location of the detector must be determined by
an evaluation based on engineering judgment sup-
plemented, if possible, by field tests.

For additional information on detector location and
spacing, contact the National Fire Protection
Association, Batterymarch Park, Quincy, Mass.
02269, and request a copy of NFPA Number 72, the
Standard on Automatic Fire Detectors.

2

Содержание 30-3003

Страница 1: ...ector reverts to normal sensitivity INSTRUCTIONS Explosion Proof Smoke Detector Model 30 3003 PHOTOVOLTAIC SENSOR CELL LENS IRED LIGHT SOURCE ALARM LED LENS SMOKE CHAMBER B1178 Figure 1 Cross Section of Sensing Chamber Assembly Detector Electronics Corporation 2000 8 00 95 8366 03 O2 6K 6K J 6K 7 6K 6K 6K 6K 6K 6K 6K 6K 6K 6K 6X K 6K 6X K 6X K 6X X X O2 6X X O2 1 X O2 O2 hf I4 K O2 O2 I4 6X O2 O2 ...

Страница 2: ...ent of an alarm and an LED located on the outer surface of the hous ing is illuminated to provide a visual indication that an alarm condition has occurred The detector is reset by momentarily interrupting input power SPECIFICATIONS OPERATING VOLTAGE 20 to 28 vdc filtered supply with less than 1 4 vpp at 60 to 120 Hz OPERATING CURRENT Standby 10 milliamperes Alarm 35 milliamperes TEMPERATURE RANGE ...

Страница 3: ...e junction box cover See Figures 3 4 and 5 for wiring details DETECTOR CONNECTIONS The detector contains two sets of relay contacts 1 One set of NO Alarm contacts close upon detec tion of smoke 2 One set of NC Trouble contacts close when the detector is powered 3 95 8366 12 3 4 INCHES 325 MM 8 1 16 INCHES 205 MM 3 1 2 INCHES 89 MM 4 1 2 INCHES 114 MM A1967 120 5 32 INCH DIA 3 2 7 16 INCHES 62 MM 5...

Страница 4: ...atement describing the malfunction must accompany the returned device or component to expedite finding the cause of the fail ure Return all equipment transportation prepaid to the factory in Minneapolis 1 2 3 4 5 AUXILIARY ALARM CONTACTS C NO NC TB 2 TB 3 POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND LISTED CONTROL PANEL EOL DEVICE SUPPLIED BY PANEL MANUFACTURER ADD JUMPER GROUND STUD B1193 6...

Отзывы: