PCX-EXT-W/BK
External Proximity Tag Reader
0845 6434 999 (UK). +44(0)1709 535 225
www.pyronix.com
Pyronix Limited, Pyronix House, Braithwell Way, Hellaby, Rotherham, S66 8QY, UK
RINS1632-1
EN50131-3:2009
EN50131-1:2006+A1:2009
PD6662:2010
Security Grade 3
Environmental Class IV
E N G L I S H
Installation Notes
References:
Specification
Warranty
Product Warning Information
Compatible Products
.
NOTE
: The reader module can be mounted on typical building materials; such
as wood, PVC, brick or metal etc. If you do encounter any problems with
different surfaces, please contact [email protected]
START
END
Black
: D1-.
Red
: D2+.
Yellow
: D3.
Blue
: D4.
Brown(1), Orange(2), Green(3):
Used for addressing.
Light Blue:
Lock Relay.
Pink:
Request to Exit.
White, Grey:
Door Monitoring.
Purple:
Door Alarm Monitoring
INSTALL KEYPADS/READERS (Programming Menu Required).
Use the
brown, orange and green wires
to address the Reader.
Connecting a Mag Lock:
Use the
light blue
wire. The diagram show the
relay mag lock control switching positive.
Connecting a Request to Exit:
Use the
pink
wire. The diagram shows a
normally open request to exit button, and takes “0V” from the control
panel.
Connecting Door Monitoring:
Use the
white
and
grey
wire. The door
monitor input needs to be programmed as the first input number of the
reader address (programmed as “Entry Delay”). If the door contact is
forced open without presenting a valid tag or pressing the push to exit
button, then the panel will go into an alarm. NOTE: The DEOL values
must be 4K7, 2K2 as shown. This does not affect the control panel DEOL
values.
Connecting Door Alarm Monitoring:
Use the
purple
wire. When the door
monitor exceeds the door open time or if the door is forced open then
the alarm PGM will generate an alarm. The input at the control panel
should be programmed as “24 Hour” or “Day Alarm” and the attribute
programmed as “Normally Open”.
Lock Open Time:
This is the time the door release is going to be active
when a valid tag is presented.
Door Open Time:
This is the time the door is allowed to be open before
triggering an alarm.
The External Prox Reader
D1-
D2+
D3
D4
RS485 BUS: 1km
D1-
D2+
D3
D4
D1-
D2+
D3
D4
D1-
D3
D4
D1- D2+ D3 D4
D1- D2+ D3 D4
D1- D2+ D3 D4
PCX-RIX8+/PSU
PCX-/PSU
PCX-ROX8R8T
PCX-RIX8+
PCX-RIX8i
PCX-LCD/EX
AUX
12V Lock
Relay
PCX-EXT-W
PCX-PROX/INT
PCX-RIX32-WE
D1- D2+ D3 D4
Supply voltage:
9-15VDC
Current consumption:
Max 22mA
Input status when reader is Arm/Disarm or Sub-Area Control:
Input:
Programmable
Input EOL resistor value:
DEOL or SEOL. Alarm=4K7 / Tamper=2K2
Input status when reader is used as Access or Door Entry Control:
Input:
Programmable
Input Function:
Door monitor feature. Door opening time limit is programmable from
the Engineer menu.
Input DEOL resistors:
NC
Input 2:
Not programmable
Output 1:
Not programmable. Activates the Door Lock Relay
Output 2:
Not programmable. Door monitor alarm activation (forced or open for longer
than programmed time).
Output 1/2 Normal state:
Floating
Output 1/2 Active state:
0V
Colour and Casing:
3mm ABS (Black: PCX-EXT-BK, White: PCX-EXT-W)
Temperature
:
Storage:-10°C to 50°C
Certified
:
-10°C to 40°C
Nominal: -25°C to 60°C
Dimensions (H x W x D):
85 x 85 x 21mm
IP65 Rated
If the control panel fails to arm, this is indicated by a broken tone on the external
proximity reader and the red LED will not illuminate. If this occurs, please check the
information at the nearest keypad.
Note: Access control falls outside the scope of EN 50131
This product is sold subject to our standard warranty conditions and is warranted
against defects in workmanship for a period of two years (batteries excluded). In the
interest of continuing care and design, Pyronix Ltd reserves the right to amend
specifications, without giving prior notice.
For electrical products sold within the European Community. At the end of the
electrical products life, it should not be disposed of with household waste. Please
recycle where facilities exist. Check with your Local Authority or retailer for recycling
advice in your country.
The PCX-EXT-W/BK can be connected to the following control panels/devices:
PCX 46, PCX 76i, 162i, 280i,IP and Enforcer 32-WE.
Each control panel/device connects via the RS485 bus terminals: D1-,D2+,D3,D4
NOTE: For information about programming tags to the external reader, please see
the control panel user manual.
Magnetic Contact
Door Monitoring
4
K
7
RS485 BUS: 1km
D1-
D2+
D3
D4
Reader
Addressing
Wires
Door Monitoring
Brown(1):
Orange(2):
Green(3):
Light Blue: Lock Relay
Pink: Request to Exit
White:
Grey:
Purple: Door Alarm Monitoring
0V (D1-)
ID1
0V (D1-)
ID2
0V (D1-)
ID3
0V (D1-)
ID4
0V (D1-)
ID5
0V (D1-)
ID6
0V (D1-)
ID7
1K
2
K
2
INSTALL KEYPADS/
READERS?
Device Type?
Reader [1]
Device Address?
0
Device Arm Area?
[A ]
Device Disarms?
[A ]
Device In Area?
[A ]
Reader is:
Entry Control[4]
Lock Open Time
[005]
Door Open Time
[010]
Door Name?
Enter Number:
Device 1
>5s
5s
>10s
<10s
EXIT TIMER
1K
>5s
>10s
ATE INPUTS
ATE INPUTS
PCX
PCX
ATE INPUTS
PCX
OFFICE
>5s
5s
<10s
5s
D2+