2.4 ASSIGNING 

TEMPTRAC 

ADDRESS FOR MODBUS-RTU 

 
The first step to interfacing a BAS (Building Automation Control) with a water heater or group of water heaters will be the 
assignment of the address number for each heater.  
 

 

 

1.  Enter the Programming mode by pressing the Set and DOWN key for 3s.  

    (lead with the SET key) 

2.  Press the DOWN key. 

3.  Select “

Pr2

” – “

PAS

” parameter and press the “SET” key. 

4.  The value “0 - -” with a flashing zero is displayed. 

5.  Use UP or DOWN keys to input the Passkey in the flashing digit; confirm the figure by 
pressing “SET”. The Passkey is “321“. 

6.  Once you have entered the Pr2 menu press the DOWN key three times and the 
parameter

 Adr

 will appear on the screen as follows: 

7.  Now press the SET key once and the number will begin to blink. Use the arrow key to 
set the address. Each TempTrac on a RS-485 network must have a different address 

8.  Each water heater should be assigned a different address in order for proper 
communication to occur. 

Note: The default for each TempTrac is Address #1.  You can assign them to any number in the range of 1-247, this is the 
limitations of the MODBUS RTU standard. 

3. ALARMS 

Alarm messages are displayed in the upper LED readout and alternate with the default display.  
An alarm LED icon is also illuminated. 
 

Message  Cause 

Results of alarm condition 

“P1” 

Probe 1 failure 

Call for heat and burner second stage interrupted; 
modulation output % will be the PP4 parameter 
(generally low fire) 

“P2” 

Probe 2 failure 

Output 3 is open 

“P3” 

Probe 3 failure 

Dynamic reset of Set1 disabled. 
Outdoor reset is disabled (if used) or Flue gas 
temperature protection is disabled (if used) 

“HA” 

High-temperature limit set point exceeded 

Audible alarm sounds, operation continues 

“LA” Low-temperature 

alarm 

Audible 

alarm sounds, operation continues 

“AL2” 

Digital Input 2 is activated for one or more of 
the conditions listed in section 3.1 

Unit de-energized after time delay. Audible alarm 
sounds.  On some products, the alarm contacts may 
close for remote indication of alarm.  Internal alarm 
register will communicate an alarm condition through 
the Modbus RTU communication link (if equipped) 

“AL3” 

Digital Input 3 is activated for one or more of 
the conditions listed in section 3.1 

Unit de-energized after time delay. 

“Mn1” 

Maintenance alert for call-for-heat 

Audible alarm sounds, operation continues 

“Mn2” 

Maintenance alert for second stage   

Audible alarm sounds, operation continues 

“Mn3” 

Maintenance alert for freeze protection 

Audible alarm sounds, operation continues 

“rtc” 

The real time clock has lost the setting  

Energy saving functions disabled 

“rtF” 

Real time clock failure 

Energy saving functions disabled 

“AL1” 

Digital Input 1 Alarm 

Output 1 open. 

Adr         

Содержание PV500-40

Страница 1: ...Page 1 7 PV500 40 04 2013 WATER HEATER ELECTRONIC CONTROLLER USER MANUAL PVI Industries LLC 3209 Galvez Dr Fort Worth Texas 76111 800 784 8326 UPPER LED READOUT LOWER LED READOUT LED ICONS ...

Страница 2: ...NS To lock and unlock the keyboard To enter the programming mode To exit the programming mode 1 3 LED ICON LEGEND LED MODE Function ON Temperatures are displayed in degrees Fahrenheit ON Temperatures are displayed in degrees Celsius Flashing Call for heat time delay or remote enable disable is in standby disabled ON Call for heat is on Flashing Second stage time delay On 2 stage units only ON Seco...

Страница 3: ...ure All of the display information described above is available for monitoring through the optional MODBUS RTU interface 1 5 LOWER LED READOUT The default display of this readout is the temperature sensed at Probe 1 Probe 1 will be inserted into the appropriate area of the storage tank to provide effective temperature response for the heat source this may not be at the top of the tank Refer to you...

Страница 4: ...mperature or operating parameters that the user can adjust St 1 This setpoint temperature should be considered the F or C temperature threshold to activate the energy source The setpoint corresponds directly to the temperature sensed by probe 1 The St 1 setpoint is programmed as an absolute temperature for example 120 F St 2 This setpoint corresponds to either the threshold for second stage burner...

Страница 5: ...procedure The set value is stored even when the procedure exits due to the 15 second expiration 2 2 HOW TO LOCK THE KEYBOARD 1 Push and hold the keys for more than 3 seconds 2 The POF message will be displayed and the keyboard is locked At this point it is only possible to view the set point 3 Repeat step 1 to unlock the keyboard 2 3 HOT KEY PROGRAMMING FOR FACTORY SUPPORTED FIELD REPROGRAMMING To...

Страница 6: ... alarm LED icon is also illuminated Message Cause Results of alarm condition P1 Probe 1 failure Call for heat and burner second stage interrupted modulation output will be the PP4 parameter generally low fire P2 Probe 2 failure Output 3 is open P3 Probe 3 failure Dynamic reset of Set1 disabled Outdoor reset is disabled if used or Flue gas temperature protection is disabled if used HA High temperat...

Страница 7: ...m condition still present 3 2 ALARM RECOVERY 1 Probe failure alarm automatically ends after normal operation is re established Check connections before replacing the probe 2 Temperature alarms HA and LA automatically stop as soon as probe 1 senses temperatures within normal operating parameters 3 Digital input 2 3 alarms recover when condition s listed above are normalized and any button is presse...