background image

  Recoveries based on 83% thermal efficiency.  ASHRAE 90.1 compliant for efficiency and standby loss. 
   "J" dimension is for the burner housing only.  

 

Dimensions are in inches unless otherwise specified. 

 

For standard and optional equipment, see form PV 6006.  

 

Model 

Number 

Recovery gph 

 

Input 

Btu/h 

Dimensions 

(inches) 

Blower  

Motor 

Shipping 

Weight 

lbs  

40°- 120°F  40°- 140°F 

 

HP 

Volt/Ph/Amps 

250 PHE 125A-TPO 

250 

200 

199,000 

24 

17 

1/3 

115/1

/8 

970 

500 PHE 125A-TPO 

500 

400 

399,000 

24 

17 

1/2 

115/1

/10 

990 

750 PHE 125A-TPO 

750 

600 

600,000 

27 

17 

1/2 

115/1

/10 

1070 

1000 PHE 125A-TPO 

1000 

800 

800,000 

27 

17 

1/2 

115/1

/10 

1110 

1250 PHE 125A-TPO 

1250 

1000 

1,000,000 

27 

17 

1/2 

115/1

/10 

1350 

1500 PHE 125A-TPO 

1500 

1200 

1,200,000 

27 

17 

1/2 

115/1

/10 

1360 

Gph 

#2 Oil 

1.4 

2.8 

4.3 

5.7 

7.2 

8.6 

TURBOPOWER

®

  OIL 

 

PACKAGED WATER HEATER 

POLYSHIELD

®

 

POLYMER-LINED STORAGE TANK

 

TANK SERIES 125 GALLONS HORIZONTAL 

PV 5458  04/05 

PVI INDUSTRIES, LLC 

FORT WORTH, TEXAS 76111 

(800) 784-8326 

 

(817) 335-9531 

 

www.pvi.com 

Product is patented in the U.S., Canada, and Mexico. 

VENTING REQUIREMENTS 

-.02" TO -.06" W.C. (NEGATIVE PRESSURE) 

 

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED 

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.  

FOR PROPER SIZING, CONSULT VENTING SUPPLIER. 

STANDARD ELECTRICAL REQUIREMENTS 

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS. 
  MOTOR VOLTAGE:  
  208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL 
  REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR 
  AN OPTIONAL CONTROL CIRCUIT TRANSFORMER. 

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN 

AND SPECIFICATION WITHOUT NOTICE. 