24
PV500-46U 06/12
11.5 To View The Setpoint
Push and release the
SET
key to see the set point value.
To return to normal display, press
SET + UP
or wait 15 seconds without pressing any key.
11.6 To Change The Setpoint
Push
the
SET
key. The upper display will show the “St1” parameter name, while the lower display will show its
value.
Use
the
UP
or
DOWN
key to cycle through the parameter names.
Push
the
SET
key to modify a parameter value. The value starts flashing in the lower display.
To change it push the
UP
or
DOWN
keys. Push the
SET
key again to confirm the value and pass to the setting
of next set point.
Repeat the operations described at points 3, 4, 5.
To Exit:
press
SET + UP
or wait 15 seconds without pressing any key.
NOTE:
Each point has a time out of 15 seconds. If any key is pushed within 15 seconds the controller exits the set
points programming procedure.
NOTE
: The set value is stored even when the procedure is exited by waiting the time-out to expire.
11.7 To Change Other Parameters
Push
the
SET
and
DOWN
arrow simultaneously for 3 seconds.
Select the required parameter. The name of the parameter is on the upper display; its value is on the lower
display.
Press
the
SET
key: the value of the parameter will start blinking.
Use
UP
or
DOWN
to change the value.
Press
SET
to store the new value and move to the following parameter.
To Exit
: Press
SET + UP
or wait 15s without pressing a key.
Содержание 100 LX 125 A-PVIF
Страница 8: ...8 PV500 46U 06 12 300 SERIES ...
Страница 11: ...11 PV500 46U 06 12 SINGLE WATER PIPING SINGLE STORAGE WATER HEATER WITH SUPPLEMENTAL STORAGE TANK ...
Страница 34: ...34 PV500 46U 06 12 16 REPLACEMENT PARTS REPLACEMENT PARTS ...
Страница 35: ...35 PV500 46U 06 12 16 1 Control Panel ...
Страница 37: ...37 PV500 46U 06 12 16 3 Burner Assembly Optional components may or may not be shown ...
Страница 43: ...43 PV500 46U 06 12 ...
Страница 44: ...44 PV500 46U 06 12 PVI INDUSTRIES LLC 3209 Galvez Ave Fort Worth Texas 76111 Phone 1 800 433 5654 www pvi com ...