puroflux PF-50 Series Скачать руководство пользователя страница 15

O P E R A T I O N   A N D   M A I N T E N A N C E   M A N U A L

PF-50 Series Filter (ver. 4/5/05)

PAGE # 15

FILTER VESSEL

The filter vessel is constructed of carbon steel with a fusion bonded epoxy lining and  polyester coating.
The vessel is designed with a handhole/manhole located in the upper head for service. The internals are 
constructed of  corrosion resistance sch. 80 PVC plastic. The underdrain assembly is a header lateral 
configuration design to help induce even flow through the media. The underdrain laterals can be removed
individually by rotating each lateral counter clockwise until all threads are disengaged. The 3 point
overdrain assembly is designed to distribute the influent evenly over the top of the filter media. The 
internal assembly should be thouroghly inspected before adding media. To inspect the internals follow the
shutdown procedure. Carefully remove the filter vessel handhole by removing the hex nut on the crab
clamp of the filter vessel (do not drop the handhole into the filter vessel.) Refer to Loading Media (page 7). 

BACKWASH CYCLE

When the pressure drop across the media bed reaches its terminal differential pressure (16 psid), it is 
necessary to initiate a backwash. The backwash cycle must be completed in order to keep the media from
becoming contaminated. Higher differential pressures drive the debris deep into the media bed where they
cannot be flushed out. Over a period of time, the buildup of debris will cause a media failure and 
channeling or plugging of the media will occur.

Automatic Units

Controls are furnished with a factory preset pressure differential switch, manual backwash override push
button and a 24 hour time clock to activate a backwash cycle. Upon an initation of a backwash cycle the 
electric valve actuator will reposition the valves into the backwash mode.The backwash cycle is preset from
the factory for three minutes. After completion of the backwash cycle the valve actuator will reposition the
valves into the filter mode. The duration of the backwash time may be adjusted if necessary. Please 
consult the factory before adjusting the backwash timer. It is essential that the backwash time remain at a
minimum of three minutes to insure that the media is cleaned properly.

Manual Units

The manual units function in the same manner as the automatic units except the valves have to be manually
repositioned into and out of the backwash cycle. The filter unit will need a backwash cycle when the 
differential pressure reaches 16 psid or a minimum of every 24 hours. For units supplied with pump, the 
operator must shut off the pump before repositioning the valves into or out of the backwash cycle. For filter units
utilizing the system for a backwash supply, reposition the valves, and then turn pump back on. The backwash
cycle should run three minutes. After completing a backwash cycle, the pump should be turned off and the
valves repositioned to the filter cycle. Once the valves are repositioned the pump can be turned back on. For
filter units utilizing an external source for a backwash supply the pump must remain off during the three minute
backwash cycle. After three minutes, the valves are repositioned into the filter position and the pump can be
turned back on.

NOTE: 

Always relieve any trapped air in the filter vessel.

NOTE: 

Always relieve internal vessel pressure before attempting any repairs or adjustments on the filter unit.

Содержание PF-50 Series

Страница 1: ...OPERATION AND MAINTENANCE MANUAL PF 50 Series Permanent Media Filters PUROFLUX FILTRATION AND CONTROL SYSTEMS C O R P O R A T I O N...

Страница 2: ...and related equipment If there are any questions on the procedures or performance of the PF 50 series filters contact the local factory representative or call the factory direct at 805 579 0216 Do No...

Страница 3: ...Loading Media 7 Electrical Controls 8 Wiring Requirements 9 SECTION 2 Theory of Operation 10 Operation and Maintenance 10 General Maintenance 10 24 Hour Time Clock Settings 11 Pump Pre Strainer 12 Pu...

Страница 4: ...and Table I for components to be inspected upon receiving Check the model and serial number against the packing slip Serial and model numbers can be found on a nameplate inside the control cabinet au...

Страница 5: ...d drawing for locations of anchor holes NOTE The PF 50 filter should not be installed more than 8 feet above the process liquid operating level NOTE Never install the PF 50 series filter in an applica...

Страница 6: ...lumes The maximum backwash supply pressure for the PF 50 filter is 50 psi Run a line to the connection labeled BACKWASH If public or municipal water is used for backwash a backflow preventer is requir...

Страница 7: ...H 12 1 FPT 1 FPT 1 FPT 1 FPT 18 1 1 2 FPT 1 1 2 FPT 1 1 2 FPT 1 1 2 FPT 24 1 1 2 FPT 1 1 2 FPT 1 1 2 FPT 1 1 2 FPT 30 2 FPT 2 FPT 2 FPT 2 FPT 36 2 1 2 FPT 2 1 2 FPT 2 21 2 FPT 2 1 2 FPT 42 3 FPT 3 FPT...

Страница 8: ...over lifting it through the tank ring Inspect the internals for damage before continuing 2 Fill the vessel with water until the underdrain assembly is completely submerged in water Load the support gr...

Страница 9: ...O P E R A T I O N A N D M A I N T E N A N C E M A N U A L PAGE 9 PF 50 Series Filter ver 4 5 05...

Страница 10: ...disconnect switch with motor circuit protection MCP control transformer primary 120v secondary adjustable backwash timer 24 hour backwash time clock magnetic motor starter external backwash source un...

Страница 11: ...anual Units 1 Install a circuit breaker between the closest branch distribution panel and the pump motor if supplied See Table V for amperage draw by motor horsepower 2 Install an externally operated...

Страница 12: ...NANCE MANUAL thoroughly and understand all safety related issues before attempting any work on the PF 50 series filters GENERAL MAINTENANCE PROCEDURES Always follow the start up and shut down procedur...

Страница 13: ...Pins pulled out consecutively will initiate a backwash once and then lock out any further backwash cycle 15 minutes for each consecutive pin pulled out In order to eliminate the 24 hour time clock fro...

Страница 14: ...tor bracket which is bolted directly to the pump volute The pump shaft slides over the motor shaft and is held in place with three set screws The pump impeller is threaded or keyed on to the end of th...

Страница 15: ...witch manual backwash override push button and a 24 hour time clock to activate a backwash cycle Upon an initation of a backwash cycle the electric valve actuator will reposition the valves into the b...

Страница 16: ...e arrow on the pump volute DO NOT run the pump for an extended period of time in reverse direction or dry Have a qualified electrician change leads to correct rotation 8 Open the service valves in the...

Страница 17: ...leave the valve open 5 Drain all external piping to and from the filter 6 Remove the drain plug on the filter vessel Allow the liquid to drain After all liquid has drained replace the drain plug If su...

Страница 18: ...s a chemical treatment program must be employed by a competent professional Such treatment should be initiated before the system start up and continued regularly thereafter SAFETY All electrical mecha...

Страница 19: ...ase order must be issued to cover the cost of each replacement part and shipping Upon inspection and an issue of credit of the defective items by PUROFLUX and or PUROFLUX S vendor s credit will be iss...

Страница 20: ...PAGE 20 PF 50 Series Filter ver 4 5 05 P U R O F L U X C O R P O R A T I O N FIGURE 3...

Отзывы: