stopped (the display will be flashing during the
movement of the motor).
That function is very important during start-
up processes.
2. START-UP
Prior to initiate the start-up of the system is very
important to be sure that the installation of the
softener is correctly made according to local
regulations.
1. Check that inlet and outlet valves are
completely closed. Moreover confirm that
by-pass valve is opened to ensure water to
the installation during start-up process.
2. Connect the power adapter to the power
source.
3. The timer will be placed in service position.
4. Press REGEN key during three seconds to
start regeneration.
5. After some seconds the system will be
placed in Backwash position.
6. Open inlet valve up to ¼ of it’s total
aperture. Water will start to enter into the
softener. Water flow at this moment should
be little to avoid damages to top nozzle.
7. When water comes through the drain with a
continuous flow open please open inlet
valve completely.
8. Some coloration (yellow or brown) could be
observed in drainage flow. That coloration is
originated by resin preservatives. It’s
necessary to maintain this position until
coloration disappears.
9. Close inlet valve for five minutes, all the air
trapped with the resin will float to the upper
part of the vessel.
10. Open inlet valve one more time for five
minutes more to ensure that all the air inside
the vessel has been removed.
11. Cancel the current stage of the regeneration
until refill stage.
12. Let refill stage end by itself. In this moment
the system will end the regeneration started
in point 4.
13. Start another regeneration. Wait until the
system is placed in Backwashing position
and cancel this stage by pressing any key.
14. The softener will be placed in Brining
position and will start to suction water from
the tank.
15. Check that the softener suctions water from
the tank.
16. Cancel the remaining stages of the
regeneration.
17. Open by-pass valve and fill the tank with
salt.
18. Start-up process has ended.