PUREGAS, LLC
P1500W2 Series Air Dryers User’s Guide
Page 39 of 100
P012253 – Rev. H
8.9 Setting the System Pressure
With Compressor running:
8.9.1
Open Front Panel (section
8.9.2
Pull the Capacity Control
Valve knob out.
8.9.3
Turn the knob until the
reading on the Pressure
Gauge is:
552 kPa
for W and WLP
621 kPa
for WHP
8.9.4
Push the knob in to lock.
8.9.5
Close Front Panel.
8.10 Setting the Static Pressure
8.10.1
Open Front Panel (section
8.10.2
Pull the Static Pressure
Regulator knob out.