1. Treated Water Line
This line is to be connected to a manifold that feeds reclaim water to the wash equipment.
Valves need to be installed. Some are controlled by the wash controller. Some are
controlled by tank level (Ex: toilet bowl float) when water is demanded by the wash.
Do not
reduce the line size until reaching the wash equipment to prevent flow restriction
and pressure reduction.
(See page 22 on direct feed concept for high pressure pumps.)
2. City Water Line
City water is to be connected, which will then provide fresh water for a bypass function to
the wash and the pump prime sequence. The city water supply line needs to be 1” for the
PW50 / 100 series and 2” for larger units to ensure enough pressure and flow are available.
City water should not exceed a pressure of 65 psi.
High incoming city water pressure
can prevent the Prime and / or Bypass Valves from closing completely.
Cyclonic
Separators
Pump/Motor
and Basket
Strainer
1. Treated
Water Line
2. City Water
Line
3. Recirculation
Line
4. Pump Suction
Line
5. Underflow
Line
Ozone
Generator
Oxygen
Concentrator