background image

Table 6. Troubleshooting

 

TROUBLESHOOTING

The PumpSaver® will display a fault code alternating with a number or with “run” when it is in a trip

condition. If the unit is showing a fault code (see Table 5) alternating with the word “run”, it has

tripped on a current (amperage) condition. If the fault code is alternating with some number (voltage

reading or zero), the unit will not allow the motor to start because there is a problem with the
incoming voltage. If the display is showing just a fault code, the unit is in a mode that requires a

manual reset. This could be because the number of restarts has expired or is not allowed. If the

display is showing “off,” a stop command was issued through the communications network.

PROBLEM

SOLUTION

The unit will not start. Display
alternates “rP” with the DISPLAY/PROGRAM
switch parameter value.

The voltage inputs are reverse phased. If this is
the initial start up, swap the leads connected to
L1 and L3 on the Model 777-AccuPower to
correct the problem. If the overload relay has
been previously running, the power system has
been reverse phased. Check the phase
sequence of the incoming power lines. Note: L1
must be tapped from conductor Phase A, L2 from
B, and L3 from C for correct kilowatt
measurements.

Display alternates “SP”, “ub”, or
“oc” with “run”

The overload relay has tripped on the fault shown
on the LED display and is timing down RD2
before  restarting.

Display alternates “LPR”
with “run”

The overload relay has tripped on low power
(LPR) and is timing down RD3 before restarting.
If LPR is not a normal condition for this
installation, check for loss of liquid, closed valves,
broken belts, etc.

Display is showing a solid “SP”,
“ub”, or “oc”

The unit has tripped on the fault shown and a
manual reset is required because the
programmed setting in RD2 is 0. Check the
system for problems that would produce the
single-phase, overload  or current unbalance
fault—such as a jam.

Display is showing a solid “LPR”

The unit has tripped on low power and a manual
reset is required because the setting in RD3 is 0.
Check the system for problems that would
produce a loss of load like a broken belt or a
pump is out of liquid.

Display is showing a solid “CF”

Contactor failure – the unit has tripped on a
single-phasing of the current, but was not single-
phased by the incoming voltage. Check for
damaged contacts or loose wiring.

Unit displays currents when the
motor starts but reads “0” kW or HP
and trips on LPR after 4 seconds.

The unit is not wired properly to calculate correct
power factor. See Figures 1, 2 & 3 for proper
wiring and review step 4 in connection
instructions (page 1).

Display alternates “HPR” with “run”

The overload has tripped on high power and is
timing down RD2.

Display is showing solid “HPR”

The overload has tripped on high power and
requires  a manual reset.

Unable to change parameters

See TAMPER GUARD section on page 14

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание 777

Страница 1: ... right motor conductor i e the A phase conductor should go through the A round hole See Figure 1 for a typical wiring diagram B For amperage less than 25 amps 1 2 amps for LR model loop the motor conductors according to Table 1 Figure 2 shows an example of the looping required for current ranging from 8 1 to 12 amps MULT 3 C For amperage greater than 90 amps external CTs current transformers are r...

Страница 2: ...2 00 10 0 1 1 2 2 5 2 00 10 0 10 10 2 5 3 2 22 11 1 9 9 3 3 5 2 50 12 5 8 8 3 5 4 2 85 14 2 7 7 4 5 3 33 16 6 6 6 5 6 4 00 20 0 5 5 6 8 5 00 25 0 4 4 8 12 6 66 33 3 3 3 12 25 10 0 50 0 2 2 25 90 20 0 100 1 1 uExternal CTs Requiredu 80 110 80 140 5 100 100 5 110 160 120 210 5 150 150 5 160 220 160 280 5 200 200 5 220 320 240 420 5 300 300 5 320 420 320 560 5 400 400 5 400 520 400 700 5 500 500 5 48...

Страница 3: ...xample Showing Three Conductors MULT 3 from Table 1 No other necessary connections are shown Figure 3 Typical Wiring Diagram Using External CTs Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 4: ...ated and set when HP and FLA are programmed so if FLA is not entered EFF must be programmed manually EFF PF EFF PF efficiency power factor can be found on the motor s nameplate or manufacturer s specification sheet If the efficiency rating is available it is best to enter it and FLA should be set to 0 If the efficiency is not available it will automatically be calculated and set according to the H...

Страница 5: ...bled OFF RD1 RD1 restart delay one is the rapid cycle timer in seconds This timer is initiated when power is first applied to the unit If no SP or RP conditions exist when power is applied to the device the output relay will energize the NO contact will close and the NC will open once the RD1 timer expires Typically this is set to 20 30 seconds This will provide adequate protection for successive ...

Страница 6: ...the 4 20 mA module or to set the Modbus address A01 A99 FS 20 mA 16 mA 4 mA 0 kW 6 FS 8 Example if motor is running at 6 kW Desired mA output 4 20 4 X Running hp kW X FS Output FS full scale setting is required when utilizing a 4 20 mA module PWS should already be set according to the correct hp kW operating range of the motor this will automatically establish the range for FS Set FS according to ...

Страница 7: ...PLAY PROGRAM knob until the proper setting for the parameter that is being programmed is displayed 4 Release the RESET PROGRAM button This stores the new parameter in the nonvolatile memory If a setting jumps back to its previous setpoint when changed the tamper guard is locked and must be unlocked before programming can be completed see page 14 for tamper guard procedures 5 Continue steps 1 4 unt...

Страница 8: ...ip Most NEMA rated general purpose motors will be protected by this setting 30 Slow Trip Motors with long acceleration times 10 seconds or high inertia loads J prefix Programming any of the trip classes with the J Prefix will enable jam protection This additional protection is enabled 1 minute after the motor starts and provides a 2 second trip time for motors exceeding 400 of the OC setting regar...

Страница 9: ...rs E88 OC Service Factor Amperage 8 2 TC General purpose motor 20 CUB Standard NEMA motor 5 PWS 2 1 0 9 95 LPR Normal pumping operation reads 2 86 kW Pump with a momentarily restricted flow dead head reads 1 8 kW Therefore setting is 2 0 kW see PWS for proper range HPR Typically not used set to OFF RD1 To protect the pump from accidental rapid cycling RD 20 seconds RD2 Because the motor may be hot...

Страница 10: ...nce LPR Tripped on low power HPR Tripped on high power CF Tripped on contact failure RP Incoming phases have been reversed motor may run backwards if started OFF A stop command was issued from a remote source Table 5 Fault Codes COMMUNICATIONS PORT REMOTE RESET The unit comes with a 9 pin sub D connector for remote communications and or for using a remotely located reset button If communication is...

Страница 11: ... down RD2 before restarting Display alternates LPR with run The overload relay has tripped on low power LPR and is timing down RD3 before restarting If LPR is not a normal condition for this installation check for loss of liquid closed valves broken belts etc Display is showing a solid SP ub or oc The unit has tripped on the fault shown and a manual reset is required because the programmed setting...

Страница 12: ...Over Setpoint Trip time Over Setpoint Trip time 1 30 seconds 5 6 seconds 2 15 seconds 6 5 seconds 3 10 seconds 10 3 seconds 4 7 5 seconds 15 2 seconds Safety Marks UL UL508 UL1053 CSA LR46510 CE IEC 60947 1 IEC 60947 5 1 Standards Passed Electrostatic Discharge ESD IEC 1000 4 2 Level 3 6kV contact 8kV air Radio Frequency Immunity RFI Conducted IEC 1000 4 6 Level 3 10V m Radio Frequency Immunity RF...

Страница 13: ...nd 4 100 650 kW HPR to off to disable these features 5 0 01 1 30 hp 6 1 34 13 3 hp 7 13 4 133 hp 8 134 871 hp LPR Low Power Range determined by PWS HPR High Power Range determined by PWS RD1 Rapid Cycle Timer 0 2 500 Seconds RD2 Restart Delay After All Faults Except Underload motor cool down timer 0 2 500 Minutes RD3 Restart Delay After Underload low flow recovery timer 0 2 500 Seconds A Automatic...

Страница 14: ...ppears in the display 4 Release the RESET button 5 Turn MODE SELECT to RUN The program is now locked but all settings can be viewed The unit can be unlocked by following the procedure above except step three adjust DISPLAY PROGRAM until unL appears SymCom warrants its microcontroller based products against defects in material or workmanship for a period of five 5 years from the date of manufacture...

Страница 15: ...s above the case ground The 4 20mA module has optical isolation chips to isolate the 4 20mA output from the AC line voltages The signals from the microprocessor go through resistors to provide current limiting before connecting to the 9 pin external connector Therefore the 9 pin SUB D connector on the SymCom unit provides un isolated CMOS signals and is NOT RS232 or TTL compatible Note Do not plug...

Отзывы: