Your Pump House Condensate Pump is designed as an automatic condensate

removal pump for pumping away room temperature condensate water dripping

from air conditioner/refrigeration evaporative coils. The pump is controlled by a

float/switch mechanism which turns the pump on to discharge the water when

approximately 55mm depth of water collects in a tank.  The pump automatically

switches off when the tank drains to approximately 30mm deep.
The  Pump  House  Condensate  Pump  you  have  purchased  is  a  high  quality

product that has been engineered to give you long and reliable service.
This pump is carefully packaged, inspected and tested to ensure safe operation

and  delivery.  When  you  receive  the  pump,  examine  it  carefully  to  determine

there  are  no  broken  or  damaged  parts  that  may  have  occurred  during

shipment.  If  damage  has  occurred,  please  contact  your  supplier.  They  will

assist you in replacement or repair, if required.
READ  INSTRUCTIONS  CAREFULLY  BEFORE  ATTEMPTING  TO  INSTALL,

OPERATE  OR  SERVICE  THE  PH-2L  PUMP.  KNOW  THE  PUMP  APPLICATION,

LIMITATIONS AND POTENTIAL HAZARDS. PROTECT YOURSELF AND OTHERS

BY  OBSERVING  ALL  SAFETY  INFORMATION.    FAILURE  TO  COMPLY  WITH

INSTRUCTIONS  COULD  RESULT  IN  PERSONAL  INJURY  AND/OR  PROPERTY

DAMAGE! RETAIN INSTRUCTIONS FOR FUTURE REFERENCE. INSTALLATION

AND CONNECTIONS ARE TO BE MADE BY A QUALIFIED PERSON.

SAFETY GUIDELINES

DO  NOT  USE  TO  PUMP  FLAMMABLE  OR  EXPLOSIVE  FLUIDS  SUCH  AS

PETROL,  FUEL  OIL,  KEROSENE,  ETC.  DO  NOT  USE  IN  EXPLOSIVE

ATMOSPHERES.  PUMP  SHOULD  BE  USED  WITH  LIQUIDS  COMPATIBLE

WITH PUMP COMPONENT MATERIALS.
DO NOT HANDLE PUMP WITH WET HANDS OR WHEN STANDING ON WET

OR  DAMP  SURFACE,  OR  IN  WATER.  THIS  PUMP  IS  SUPPLIED  WITH  AN

EARTHING CONDUCTOR AND/OR EARTHING TYPE ATTACHMENT PLUG. TO

REDUCE  THE  RISK  OF  ELECTRICAL  SHOCK,  BE  CERTAIN  THAT  IT  IS

CONNECTED TO A PERMANENT EARTH. 
FOR  INSTALLATIONS  WHERE  PROPERTY  DAMAGE  AND/OR  PERSONAL

INJURY MIGHT RESULT FROM AN INOPERATIVE OR LEAKING PUMP DUE TO

POWER CUTS, DISCHARGE LINE BLOCKAGE, OR ANY OTHER REASON, A

BACKUP SYSTEM(S) AND/OR ALARM SHOULD BE USED. 
SUPPORT  THE  PUMP  AND  PIPING  WHEN  ASSEMBLING  AND  WHEN

INSTALLED. FAILURE TO DO SO MAY CAUSE PIPING TO BREAK, PUMP TO

FAIL, MOTOR BEARING FAILURES, ETC.

INSTALLATION

1.  Carefully unpack the pump.   Remove the cardboard packing from the motor

cover  air  slots.  Carefully  slide  the  packing  away  from  the  pump.  This

packing is used to prevent switch movement during shipment (Fig. 1).

INTRODUCTION

2. 

Mounting the pump: The tank has two slots provided to mount the unit

on a vertical surface such as an adjacent wall.  The slots are located on

the ends of the tank (Fig. 2). Pump must be level and the inlet must be

below the coil drain.   Conduit fittings are not compatible with the plastic

pump housing.

3.  The  pump  should  not  be  installed  in  a  manner  that  will  subject  it  to

splashing or spraying.

4.  This pump is not intended for use inside air plenums.

ELECTRICAL CONNECTIONS

1. Shut off electrical power at fuse box before making any connections. All wiring

must comply with local codes.

2.

Line  voltage: Connect  pump  to  voltage  specified  on  label  located  on

pump. Wiring is as follows:

Live (Line) - Brown
Neutral - Blue 
Earth - Yellow/Green

3. If fused plug is used, a 1.0 amp fuse is recommended.

WATER DRAIN CONNECTIONS

Inlet Water Connections
1.  Position  pump  beneath  a/c  or  refrigeration  condensate  drain  so  that

condensate  water  flows  into  pump  inlet  freely  (use  any  of  the  three
openings provided).

2.  The pump will accept up to three drain lines, although care should be

used to make certain that total inflow does not exceed outflow of pump.
If more water drains into the pump than the rated output of the pump,
tank may overflow.

3.  Keep plugs in unused pump inlet openings to prevent debris from falling

into the pump tank.

Outlet Water Connections
1.  Connect 3/8" I.D. tubing to the discharge adapter (item 5, figure 4). For best

results, secure tubing with clamps (not provided) but do not pinch collapse
or otherwise restrict the tubing.

2.  Tubing  should  rise  vertically  but  not  exceed  the  maximum  shut  off  head

(pumping height) of 4.8 metres above the pump.

3.  At highest point angle tubing horizontally and create a downward slope

to drainage point. Do not sharply bend or twist the tubing in a way that
might  result  in  collapse  or  restriction  of  the  tubing.    Creating  a
downward  slope  will  allow  water  to  drain  by  gravity  and  keep  tubing
empty of water.

4. If it is not possible to create a downward slope, try to create an inverted “U”

trap directly above the pump at the highest point.

1

CONDENSATE

REMOVAL PUMP

PH-2L

Figure 1.

Figure 2.

Remove cardboard insert.

Check Valve

Mounting Slots