Deep discharge battery protection UVP  

U<19 

V (± 5%) – disconnect of connection battery 

Sabotage protection: 
- TAMPER output indicating enclosure opening 

 

- microswitch, NC contacts (enclosure closed), 

0,5 A@50 V DC (max.) 

 

 

 

Table 5. Mechanical parameters 

Dimensions 

W=421, H=535, D+D

1

=193+14 [+/- 2mm] 

W

1

=426, H

1

=540 [+/- 2mm] 

The dimensions of the recorder 
compartment 

W

2

=380, H

2

=320, D

2

=65 [+/- 2mm] 

The dimensions of the battery 
compartment 

370x180x80 (WxHxD) 

Gross/Net weight 

10,1 / 10,9 kg 

Enclosure 

Steel plate, DC01 1,0mm color white RAL 9003 

Closing 

Cheese head screw x 2 (at the front) 

The possibility of installing two locks with different codes.

 

Connectors 

Power supply of the cameras:  RJ45 socket 
Power supply for recorder: DC2,1/5,5 plug 
Input 230 V: 

Φ 0,63-2,50 (AWG 22-10), 

Battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not touch the assembly surface so that cables can be led. 

 
Table 6. Operation safety 

Protection class PN-EN 609501:2007  

I (first) 

Protection grade PN-EN 60529: 2002 (U)  

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU  
- between input circuit and protection circuit  
- between output circuit and protection circuit  

 

3000 V AC min. 
1500 V AC min. 

   500 V AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 

100 MΩ, 500 V 

Declarations 

CE 

 

Table 7. Operating parameters

 

Operating temperature 

-

10ºC...+40ºC 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

2.  Installation 

2.1. Installation procedure 

The device should be mounted by a qualified installer, holding relevant permits and licenses (applicable and  required  for  a  
given  country)  for  230 V and  low-voltage  installations. It is required to install an installation switch with a nominal current of 
min. 3 A in the power supply circuits outside the power supply unit. 
 

The  device  shall  be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity 

(RH=90% max. without condensation) and the temperature from -

10°C to +40°C.  

The  switch  shall  work  in  a  vertical  position  that  guarantees  sufficient  convectional  air-flow  through  ventilating  holes  of  the 
enclosure.  
 
 

Содержание S64-CRB

Страница 1: ...date two 17 Ah 12 V batteries and offers the possibility of recorder installation The enclosure construction is compliant with the requirements of the General Data Protection Regulation GDPR the possi...

Страница 2: ...ectricity consumption for own needs and the energy efficiency of the power intake track were taken into account The exact description of how to perform the calculations can be found at Approximate bac...

Страница 3: ...C DC52115 converter 4 DC DC50SD converter 5 Output filter 6 Tamper micro switch terminals of tamper protection NC 7 Space for batteries 2 x 17 Ah 12 V connect the batteries in series 8 Recorder space...

Страница 4: ...2 3x CSMA CD TCP IP Bandwidth 1 6 Gbps Transmission method Store and Forward Optical indication of operation Switch power supply Link Act PoE Status The given value of 30 W per port is the maximum val...

Страница 5: ...PSU between input circuit and protection circuit between output circuit and protection circuit 3000 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or prote...

Страница 6: ...tart 2 3 Installation procedure Before installation cut off the voltage in the 230 V power supply circuit To switch power off use an external switch in which the distance between the contacts of all p...

Страница 7: ...3 1 LED indication of operating status The PSU is equipped with two diodes on the front panel RED LED on the PSU is supplied with 230 V off no 230 V supply GREEN LED on DC voltage in the AUX output o...

Страница 8: ...g short circuit or output overload YELLOW LED LIGHT LINK The connection status of LAN devices 10 Mb s or 100 Mb s and data transmission OFF no connection ON the device is connected 10 Mb s or 100 Mb s...

Страница 9: ...rk The PSU does not require performing any specific maintenance measures however in case of significant dust rate its interior is recommended to be cleaned with compressed air In case of fuse replacem...

Отзывы: