www.pulsar.pl

    

 

 

 

RAC24P 

 

 

 

RACK POWER CCTV

 

 

       Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

Operating parameters (tab.5). 

Environmental class 

II 

Operating temperature 

-10ºC...+45ºC 

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 
2.  Installation. 
 

2.1.  Requirements. 
The PSU RACK shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without condensation) and the temperature from -10°C do +45°C.  

 

During normal operation the total current consumption of the receivers cannot exceed I=8A. 

 

As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations.  

 

2.2. Installation procedure. 

 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 
2. Mount the power supply in a RACK 19" cabinet as shown below: 

 

 

- Mount M6 cage nuts 

 

- Secure the enclosure with 4xM6 screws 

 
3. Connect the receivers’ cables to the terminals AUX1...AUX8. 
4. If needed, the following technical connections can be made: 
- ALARM – technical output of collective failure 
5. Connect the ~230V AC power cord with the IEC C13 plug (included) to the 230V AC power supply and turn on 
the power (~230V). 
6. Check the PSU operation indicator. 

Содержание RAC24P

Страница 1: ...RAC24P v 1 0 RAC 24VAC 8x1A PTC RACK mounted power supply for up to 8 cameras with galvanic isolation EN Edition 1 from 28 01 2016 Supercedes the edition ...

Страница 2: ...ion of the RACK power supply unit CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical output 3 3 Acoustic indication 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 ...

Страница 3: ...rature of the power supply 70 C Green LED AUX1 AUX8 voltage indication at the AUX outputs LED ALARM red LED failure indication AUX1 AUX8 independently protected outputs ALARM technical output of collective failure relay BUZZER micro switch turning ON OFF of acoustic indication switch in the top position indication ON switch in the down position indication OFF 230V AC INPUT power socket 230V AC pow...

Страница 4: ...s Overheat protection OHP internal transformer Optical indication of operation LED AC TEMP ALARM AUX1 AUX8 Acoustic operation indication Piezoelectric indicator 75dB 0 3m The ALARM technical output of collective failure Relay type 1A 30VDC 50VAC The FMAINS fuse in the 230V power supply circuit T 6 3A Mechanical parameters tab 3 Enclosure dimensions W 19 H 2U 482 x 88 x 223 mm WxHxD Fixation four p...

Страница 5: ...ed and necessary for a given country The device shall be mounted in confined spaces according to the environment class II with normal air humidity RH 90 max without condensation and the temperature from 10 C do 45 C During normal operation the total current consumption of the receivers cannot exceed I 8A As the PSU is designed for a continuous operation and is not equipped with a power switch ther...

Страница 6: ...n the AUX1 AUX8 output off no DC voltage in the AUX1 AUX8 output 3 2 Technical output The power supply is fitted with the ALARM output of collective failure relay type A collective failure can be triggered by the following events 230V AC mains power failure Activation of the PTC polymer fuse in the camera power supply circuits Too high temperature of the power supply 70 C Fig 4 Electrical diagram ...

Страница 7: ...nd use 4 1 Overload or short circuit of the PSU output The AUX1 AUX8 power supply outputs are protected against short circuit with PTC 1A polymer fuses In the case of fuse activation disconnect the load from the power supply output for approximately 1 minute 4 2 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The ...

Страница 8: ... are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper storage ...