Overload protection OLP 

105-150% of power supply, automatic recovery

 

Battery circuit protection SCP and reverse 
polarity connection

 

polymer fuse 

Surge protection 

varistors 

Overvoltage protection OVP

 

>16V  (automatic recovery) 

Excessive discharge protection UVP 

U<9,5 V (± 5%) – 

disconnect of connection battery

 

Tampering protection system: 
- TAMPER – indicating unwanted opening of the 
PSU’s enclosure

 

- microswitch, NC contacts (enclosure closed), 
0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 
- AUX diode indicating DC power status at 
the PSU output 

- red, normal status – on, failure: off 
- green, normal status – on, failure: off 

F1÷F5 fuse 

F 1A/250V 

 
Mechanical parameters (tab. 4) 

Enclosure dimensions 

280 x 292 x 88  (285 x 297 x 80+8) (WxHxD)

 

Fixation 

se figure 3 

Fitting battery 

17Ah/12V (SLA) max. 

Net/gross weight 

2.29kg / 2.49kg 

Enclosure 

Steel plate, DC01 0,7mm colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front), lock assembly possible 

Connectors 

Power supply: Φ0,63-2,50 (AWG 22-10) 
OutputsФ0,41÷1,63 (AWG 26-14), battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 

Operation safety (tab.5) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

     Operating parameters (tab.6) 

Operating temperature 

-10ºC...+40ºC (see: chart 1) 

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

 

 

 

 

 

Содержание PSDCB05125C

Страница 1: ...PSDCB05125C v 1 0 PSDCB 13 8V 5A 5x1A 17Ah Buffer switch mode power supply for CCTV EN Edition 2 from 25 11 2013 Supercedes the edition 1 from 31 01 2013 GREEN POWER CCTV ...

Страница 2: ...ts and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices r...

Страница 3: ...of the fuse block LB5 Tabela 2 Description of PSU components and connectors fig 3 Element no Fig 3 Description 1 PSU module 2 L N power supply connector 230V AC PE protection connector 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT red GND black 6 TAMPER contact of sabotage protection NC 7 Additional connector for LED indication 8 Ibat Sel...

Страница 4: ...tage 11V 13 8V DC buffer operation 9 5V 13 8V DC battery assisted operation Output current 5x1A 1A battery charge 5x1A 2A battery charge Output current tAMB 30 C 5x1 A 1A battery charge refer to chart 1 5x1 A 2A battery charge refer to chart 1 Output current tAMB 40 C 5x0 8 A 1A battery charge refer to chart 1 5x0 6A 2A battery charge refer to chart 1 Voltage adjustment range 12 14VDC Ripple 120mV...

Страница 5: ...0 7mm colour RAL 9003 Closing Cheese head screw x 2 at the front lock assembly possible Connectors Power supply Φ0 63 2 50 AWG 22 10 OutputsФ0 41 1 63 AWG 26 14 battery output BAT 6 3F 2 5 TAMPER output wires Notes The enclosure does not adjoin the assembly surface so that cables can be led Operation safety tab 5 Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 ...

Страница 6: ...circuit Moreover the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 Connect the power cables 230VAC...

Страница 7: ...se of fuse damage the replacement of the same parameters is required In case of overload the output voltage is automatically shut off and so is the LED indicator The restoration of the voltage takes place immediately after the failure overload is over 4 2 Battery assisted operation In case of a main power outage the device is immediately switched into a battery assisted operation The PSU is equipp...

Страница 8: ...hat within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of th...

Отзывы: