Net/gross weight 

0,48 / 0,52 [kg] 

0,58 / 0,64 [kg] 

1,08 / 1,13 [kg] 

Optional equipment: 

optional equipment: set of external LED indicators: PKAZ168, mounting plate DIN 4 

Connectors 

Power supply: 0,5 

– 2,5 mm

2

 (AWG 26 

– 12) 

AUX outputs and technical outputs: 0,5 

– 2,5 mm

2

 (AWG 26 

– 12) 

Notes 

Convectional cooling 

Forced cooling (fan) 

 
 

        

Table 4. Operation safety. 

 
         Table 5. Operating parameters. 

      

  

 

 

 Fig. 2 Dimensions of the power supply unit

 

 
2. Installation. 

 
2.1. Requirements. 

PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required for a given 

country)  for  230  V  in  and  low-voltage  installations.  Unit  should  be  mounted  in  confined  spaces,  in  accordance,  with  normal 
relative  humidity  (RH=90%  maximum,  without  condensing)  and  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a 

vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure.  

The unit should be mounted in a metal enclosure (cabinet) in a vertical position so as to ensure free, convection air flow 

through the vents. In order to meet the EU requirements, follow the guidelines on: power supply, enclosures and shielding:  
- according to application.   

As  power  supply  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch,  therefore,  an 

appropriate  overload  protection  in  power  supply  circuit  should  be  provided.  Moreover,  the  user  shall  be  informed  about  the 
method  of  unplugging  (most  frequently  through  separating  and  assigning  an  appropriate  fuse  in  the  fuse-box).  The  electrical 
system shall follow valid standards and regulations.

  

 
 

2.2. Installation procedure.

  

 

CAUTION! 
Before  installation,  cut  off  voltage  in  230  V  power-supply  circuit.  To  switch  power  off,  use  an 
external  switch,  in  which  distance  between  contacts  of  all  poles  in  disconnection  state  is  not  less 
than 3mm. 
 

         It is required to install an installation switch with a nominal current of min. 6 A in the power supply circuits 
outside the power supply unit.

 

Protection class EN 62368-1 

I (first) 

Electrical strength of insulation: 
-

 

between input and output circuits of PSU 

- between input circuit and protection circuit 
- between output circuit and protection circuit   

 
2500 V AC min. 
1500 V AC min. 
  500 V AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500 V DC  

Operating temperature 

-

10ºC...+40ºC  

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 