www.pulsar.pl
PSDC16128
7
3.1. LED indication (fig. 4.).
•
LED1…LED16
green diodes indicate power at the outputs:
LB8-A AUX1…AUX8, LB8-B AUX1…AUX8.
In case of a power loss at the output (fuse activation), an appropriate diode goes out. (L1 for AUX1, L2 for
AUX2 etc.)
•
L
FPS
red
LED [!]
indicates a failure of at least one AUX output (the output’s number is indicated by the
green diode).
Fig. 4. The view of the PSU panel.
3.2 Technical outputs.
The PSU has indication outputs that allow transferring information about a failure or tampering.
•
FPS
- output indicating a fuse failure (outputs of the LB8/AW A, B fuse strip).
The FPS technical output during correct operation of the PSU is connected to ground (GND). Failure of one
of the fuses opens the output – high impedance state. The failure is also indicated by the L
FPS
red diode.
Fig. 5. Electrical diagram of the OC output.
•
TAMPER –
output indicating unwanted opening of the PSU, contains volt-free (potential-free) contacts
indicating the door status - unit closed: NC, unit opened: NO.
4. Operation and use.
4.1 Overload or short circuit at the PSU output.
The AUX1 ÷ AUX8 PSU outputs of the LB8/AW (A and B) strips are protected against a short circuit by
glass fuses or polymer fuses. If a fuse-assisted protection has been chosen, replace the fuse (of the same
parameters) in case of a failure. If the polymer fuses-assisted protection has been chosen, there will be an
automatic disconnection of the output voltage indicated by the green diode going out. Then, cut off the load from
the PSU output for approx. 1 minute.
4.2. Activation of the OVP system of the PSU.
When the OVP system is activated, the output voltage is automatically cut off. Restart is possible after
disconnecting the PSU from the mains supply 230V for at least 20 seconds.