background image

www.pulsar.pl   

 

 

 

PSBS2512B 

 

 

 

 

 
 

1.4 Specifications:  

- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operating parameters (tab.6) 

 
Electrical parameters (tab. 3) 

Mains supply 

230V/AC  (-15%/+10%) 

Current up to 

0,3 A  

Power frequency 

50Hz 

Supply power 

34 W 

Efficiency 

71% 

Output voltage 

11,0 V÷ 13,8 V DC – buffer operation 
10,0 V÷ 13,8 V DC – battery-powered operation 

Output current 

2,0A + 0,5A battery charge 
2,0A + 0,2A battery charge 

Output voltage setting, escalation and keeping 
time 

20ms / 30ms / 10ms 
 

Voltage adjustment range 

12,0 V÷ 14,5 V  

Ripple  

40 mV p-p max. 

Current consumption by PSU systems 

16 mA – battery assisted operation 

Battery charge current 

0,2A / 0,5A - configuration with jumper 

I

BAT 

 

Short-circuit protection SCP  

200% ÷ 250% of supply power – current limitation and/or 
fuse damage in the battery circuit (fuse-element replacement 
required) 

Overload protection OLP 

110% ÷ 150% (@25ºC) of power supply - limitation with the 
PTC  automatic fuse, manual restart (the fault requires the 
disconnection of the DC output circuit) 

Battery circuit SCP and reverse polarity 
protections 

3,15A - current limitation, F

BAT

 fuse (in case of a failure, fuse-

element replacement required) 

Excessive discharge protection UVP 

U<10,0 V (± 5%) – disconnection of (- BAT) battery, 
configuration by the P

BAT

 jumper 

Technical outputs: 
- FAC; indicates AC power failure 
 
- TAMPER indicates enclosure opening 

 
- R-relay type, 1A@ 30Vdc/50Vac max. 
time lag about 5s/140s/1040s/2h20m30s (+/-5%) 
- microswitch, NC contacts (enclosure closed),  
0,5A@50V DC (max.) 

F

BAT 

fuse 

F

MAIN 

fuse 

F3,15A / 250V 
T500mA / 250V 

Mechanical parameters (tab. 4). 

Enclosure dimensions 

235 x 235 x 88 (230 x 230 x 80+8) (WxHxD) [mm] (+/- 2)

 

Fixation 

175 x 203 x Φ 6 x4 pcs (WxH)   

Fitting battery  

7Ah/12V (SLA) max. 

Weight 

2,15/2,3 kg 

Enclosure colour 

RAL 9003 

Closing 

Cheese head screw (at the front) 

Connectors 

Power-supply: Φ0,63÷2,50 (AWG 22-10) 
Outputs: Ф0,41÷1,63 (AWG 26-14),  
Battery output BAT: 6,3F-2,5, 30cm,  
TAMPER output: wires, 30cm 

Notes 

Leave some space between the enclosure and the wall for the cables. 

Operation safety (tab.5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Содержание PSBS 2512B

Страница 1: ...PSBS 2512B v 1 0 PSBS 13 8V 2A 7Ah Buffer switch mode power supply unit EN Edition 2 from 16 09 2013 Supercedes the edition 1 from 17 11 2011...

Страница 2: ...escription 1 1 General description The buffer PSU is used for an uninterrupted supply to alarm systems devices requiring stabilized voltage of 12V DC 15 The PSU provides voltage of 13 8 V DC Current e...

Страница 3: ...nd jumper installed jumper removed 2 START button launching from battery 3 VADJ potentiometer voltage adjustment DC 4 FBAT fuse in the battery circuit 5 Connectors BAT DC supply output of the battery...

Страница 4: ...Part no Description 1 Isolation transformer 2 Power upply unit board tab 1 fig 2 3 TAMPER microswitches contacts for sabotage protection NC 4 FMAIN fuse in the power supply circuit 230V AC 5 L N conn...

Страница 5: ...case of a failure fuse element replacement required Excessive discharge protection UVP U 10 0 V 5 disconnection of BAT battery configuration by the PBAT jumper Technical outputs FAC indicates AC powe...

Страница 6: ...Connect the ground wire to the clip marked by the earth symbol PE Use a three core cable with a yellow and green PE protection wire to make the connection Lead the cables to the appropriate clips thr...

Страница 7: ...n the output indicate the door status unit closed NC unit opened NO 4 Operation and use 4 1 Overloads or short circuits The AUX output of the PSU is equipped with the PTC polymer fuse protection If th...

Страница 8: ...ies to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out...

Отзывы: