PSBS2024B
BLUE POWER
7
W
H
D
Table 4. Mechanical parameters
.
Enclosure dimensions
260 x 300 x 90+8 (WxHxD) [mm] (+/- 2)
Mounting
See Fig., 3
Battery housing
2x7Ah/12V (SLA) max.
195x160x85mm (WxHxD) max
Net/gross weight
3,43kg / 3,7kg
Enclosure
Steel plate, DC01 0,7mm color RAL 9003
Closing
Cylindrical screw (at the front) (lock assembly possible)
Terminals
Mains supply 230V AC:
Ф0,51÷2 (AWG 24-12)
Outputs
: Ф0,41÷1,63 (AWG 26-14)
BAT battery outputs: 6,3F-2,5, 30cm
TAMPER output: cables, 25cm
Notes
The enclosure does not adjoin the mounting surface so that cables can be led.
Convection cooling.
Table 5. Safety of use.
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Table 6. Operation parameters.
Environmental class
II
Operating temperature
-
10ºC...+40ºC
Storing temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, no condensation
Vibrations during operation
unacceptable
Surges during operation
unacceptable
Direct insolation
unacceptable
Vibrations and surges during transport
According to the PN-83/T-42106 standard
2. Installation.
2.1 Requirements.
The buffer PSU should be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC and low-voltage installations. The unit should be
mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative humidity
(RH=90% maximum, no condensation) and temperature range from -
10°C up to +40°C. The power supply should
operate in a vertical position in order to provide free and convectional air flow through ventilating holes of the
enclosure.
The power supply load balance should be done before installation:
1. Output current 2A + 0,2A battery charging
2. Output current 1,7A + 0,5A battery charging
Total current of the rec battery is max. 2,2A
The power supply is designed for a continuous operation and is not equipped with a power-
switch. Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the
user should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an
appropriate fuse in the fuse box). The electrical system shall be made in accordance with applicable standards and
regulations.