Pulsar PSBS 2024B Скачать руководство пользователя страница 7

www.pulsar.pl                                                       

PSBS2024B                                                                  

BLUE POWER

     

 

W

H

D

Table 4. Mechanical parameters

.

 

Enclosure dimensions 

260 x 300 x 90+8  (WxHxD) [mm] (+/- 2) 

Mounting 

See Fig., 3 

Battery housing 

2x7Ah/12V (SLA) max. 
195x160x85mm (WxHxD) max  

Net/gross weight 

3,43kg / 3,7kg 

Enclosure 

Steel plate, DC01 0,7mm color RAL 9003 

Closing 

Cylindrical screw (at the front) (lock assembly possible) 

Terminals 

Mains supply 230V AC: 

Ф0,51÷2 (AWG 24-12) 

Outputs 

: Ф0,41÷1,63 (AWG 26-14) 

BAT battery outputs: 6,3F-2,5, 30cm 
TAMPER output: cables, 25cm 

Notes 

The enclosure does not adjoin the mounting surface so that cables can be led. 
Convection cooling. 

Table 5. Safety of use.

 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Insulation electrical strength: 
- between input (network) circuit and the output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit  (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Table 6. Operation parameters. 

Environmental class 

II 

Operating temperature 

-

10ºC...+40ºC  

Storing temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, no condensation 

Vibrations during operation 

unacceptable 

Surges during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and surges during transport 

According to the PN-83/T-42106 standard 

 
 

2. Installation. 

 

2.1 Requirements. 

The  buffer  PSU  should  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable and  required  for  a  given  country)  for  230V/AC  and  low-voltage  installations. The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, no condensation) and temperature range from -

10°C up to +40°C. The  power  supply  should  

operate  in  a  vertical position in order to provide free and  convectional  air  flow  through ventilating holes of the 
enclosure. 

 
The power supply load balance should be done before installation: 

 

1.  Output current 2A + 0,2A battery charging 
2.  Output current 1,7A + 0,5A battery charging 

 

Total current of the rec battery is max. 2,2A 

 

The    power    supply    is    designed    for    a    continuous    operation    and    is    not    equipped    with    a    power-

switch. Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the 
user should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an 
appropriate fuse in the fuse box). The electrical system shall be made in accordance with applicable standards and 
regulations. 

 
 
 
 
 
 

Содержание PSBS 2024B

Страница 1: ...PSBS 2024B v 1 0 PSBS 27 6V 2A 2x7Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 1 from 05 05 2014 Supercedes edition...

Страница 2: ...te TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Install...

Страница 3: ...Buffer power supply PSBS 27 6V relay module MPSBS 2x7Ah PSBS 2024B MPSBS 2x7Ah 2 Buffer power supply PSBS 27 6V 4x0 5A 2x7Ah PSBS 2024B LB4 4x0 5A AWZ574 AWZ576 2x7Ah 3 Buffer power supply PSBS 27 6V...

Страница 4: ...stment FBAT fuse in the battery circuit F3 15A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical outp...

Страница 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T1A 250V L N power supply connector 230V AC PE p...

Страница 6: ...reverse polarity connection F3 15A current limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 20V 0 5V disconnection...

Страница 7: ...Vibrations during operation unacceptable Surges during operation unacceptable Direct insolation unacceptable Vibrations and surges during transport According to the PN 83 T 42106 standard 2 Installati...

Страница 8: ...type page 9 section 3 3 6 Use the IBAT jumper to set the maximum battery charging current taking into account the battery parameters 7 Use the PBAT jumper to set to turn on off deep discharge battery...

Страница 9: ...hi Z high impedance state PSU failure can be caused by the following events Short circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output...

Страница 10: ...e battery The power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Dee...

Страница 11: ...y repairs at the earliest convenienve however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if ther...