Operating parameters (tab.6). 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

2. Installation. 

 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate  permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that 
guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 
   

During normal operation, the total current drawn by the equipment may not exceed I = 1,0A. 
Maximum battery charging current: 0,2A. Total device c battery: 1,5A max. 

 

 

As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
2.2 Installation procedure. 

 

1. Before installation, cut off the voltage in the 230V power-supply circuit.

 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE. Use a three-core cable (with a yellow and green PE protection wire) to make the connection. 
Lead the cables to the appropriate clips through the bushing of the connection board. 
 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and 

fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  a  device 
failure or an electric shock. 

 
4. Connect the receivers’ cables to the +AUX, -AUX connectors of the terminal block on the PSU board. 
5. If necessary, connect the device conductors to the technical outputs:  
 -  FAC; AC status indication (alarm panel, controller, indicator, LED, etc.)

 Use the 

T

AC

 (J1,J2) 

jumper to determine 

the indication time lag.

 

 - TAMPER; the indicator preventing the PSU from unwanted opening 
6. Allowing of the battery parameters, determine the maximum charging current using the I

BAT 

pins.  

7. Using the P

BAT

 pins, determine whether the function of disconnecting the discharged battery U<10V (+/-5%) is to 

be on or off. 

The battery protection is on

 

if the P

BAT

 jumper is removed.

 

8. Activate the ~230V/AC supply (the AC red diode and AUX diode should be permanently illuminated) 
9. Check the output voltage (the PSU voltage without load should amount to 13,6 V÷ 13,9 V, during battery 
charging 11 V÷ 13,8 V). If the value of the voltage requires adjustment, it should be set by the V

ADJ

 potentiometer, 

monitoring the voltage at the AUX output of the PSU. 
10. Connect the battery in accordance with the signs: +BAT red to ‘plus’, -BAT black to ‘minus’, (the LB diode light 
should fade throughout the time of charging). 
11. Once the tests and control operation have been completed, close the PSU. 

 
 
 
 
 

Содержание PSBS 1512A

Страница 1: ...PSBS 1512A v 1 0 PSBS 13 8V 1A 1 2Ah Buffer switch mode power supply unit EN Edition 3 from 16 09 2013 Supersedes edition 2 from 18 09 2012...

Страница 2: ...1 Overloads or short circuits 4 2 Battery powered operation 4 3 Maintenance 1 Technical description 1 1 General description The buffer PSU is used for an uninterrupted supply to alarm systems devices...

Страница 3: ...n J1 J2 time lag T 5s J1 J2 time lag T 140s J1 J2 time lag T 1040s 17m 20s J1 J2 time lag T 2h 20m 30s Legend jumper installed jumper removed 2 START button launching from battery 3 VADJ potentiometer...

Страница 4: ...Part no Description 1 Isolation transformer 2 Power upply unit board tab 1 fig 2 3 TAMPER microswitches contacts for sabotage protection NC 4 FMAIN fuse in the power supply circuit 230V AC 5 L N conn...

Страница 5: ...eplacement required Excessive discharge protection UVP U 10 0 V 5 disconnection of BAT battery configuration by the PBAT jumper Technical outputs FAC indicates AC power failure TAMPER indicates enclos...

Страница 6: ...N clips of the PSU Connect the ground wire to the clip marked by the earth symbol PE Use a three core cable with a yellow and green PE protection wire to make the connection Lead the cables to the ap...

Страница 7: ...e output indicate the door status unit closed NC unit opened NO 4 Operation and use 4 1 Overloads or short circuits The AUX output of the PSU is equipped with the PTC polymer fuse protection If the lo...

Страница 8: ...ies to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out...

Отзывы: