Pulsar PSBS 1012B Скачать руководство пользователя страница 2

www.pulsar.pl                                                       

PSBS1012B                                                                  

BLUE POWER

     

 

PSU features: 

 

 

uninterruptible power supply DC 13,8V/1A  

 

battery housing: 7Ah/12V 

 

supply voltage AC 230V  

 

high efficiency 71% 

 

low voltage ripple 

 

battery charging and maintenance control 

 

deep discharge battery protection (UVP)  

 

battery charging current 0,2A/0,5A, jumper 
selectable  

 

START button to start the battery  

 

battery output protection against short-circuit and 
reverse connection  

 

LED indication  

 

EPS technical output of 230V power failure 
– OC type 

 

PSU technical output indicating PSU failure 

– OC type 

 

LoB technical output indicating low battery voltage 

 

– OC type  

 

Optional installation of the MPSBS relay module  
changing technical outputs of the OC type to relay 
type  

 

adjustable times of 230V AC failure indication 

 

Protection type: 

 

SCP short-circuit protection 

 

Overheat protection OHP 

 

surge protection  

 

overload protection OLP 

 

Tamper protection: enclosure opening and 

detachment from the wall 

 

warranty - 5 years from the production date 

 
TABLE OF CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of components and connectors 
1.4 Technical parameters 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Power supply operation indication. 

3.1 Optical indication of operation 
3.2 Technical outputs 
3.3 Relay technical outputs 

4. Service and operation 

4.1 Overload or short-circuit the power supply output (SCP activation) 
4.2  Running the PSU from the battery. 
4.3  Deep discharge battery protection UVP. 
4.4  Maintenance 
 

 

1. Technical description. 
 

1.1 General description. 

A  buffer  PSU  is  designed  for  uninterrupted  supply  of  devices  requiring  stabilized  voltage  of 

12V  DC  (+/-

15%).

 The PSU supplies voltage of 

U=13,8V DC 

and total current capacity of

 

1. Output current 1A + 0,2A battery charging 

 

 

 

2. Output current 0,7A + 0,5A battery charging 

 

 

 

 
Total c battery is max. 1,2A 

 

In  case  of  mains  power  loss,  the  unit  will  instantly  switch  to  battery  operation.  The  PSU  is  enclosed  in  a 

metal  casing  (color  RAL  9003)  with  battery  housing  for  7Ah/12V  batteries.  The  enclosure  is  fitted  with  a  micro 
switch indicating door opening (front cover) and the detachment from the wall. 

 
 
 
 
 
 
 
 
 
 

Содержание PSBS 1012B

Страница 1: ...PSBS 1012B v 1 0 PSBS 13 8V 1A 7Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 2 from 14 04 2015 Supercedes edition 1 from 05 05 2014...

Страница 2: ...ate TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Instal...

Страница 3: ...586 MPSBS 7Ah 3 Buffer power supply PSBS 13 8V 12V 1A MPSBS 7Ah PSBS 1012B RN250 13 8V 12V MPSBS 7Ah 4 Buffer power supply PSBS 13 8V 12V 2x0 5A MPSBS 7Ah PSBS 1012B RN250 13 8V 12V LB2 2x0 5A AWZ586...

Страница 4: ...ustment FBAT fuse in the battery circuit F2A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output...

Страница 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T315mA 250V L N power supply connector 230V AC PE...

Страница 6: ...reverse polarity connection F2A current limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 10V 0 5V disconnection of...

Страница 7: ...brations during operation unacceptable Surges during operation unacceptable Direct insolation unacceptable Vibrations and surges during transport According to the PN 83 T 42106 standard 2 Installation...

Страница 8: ...y type page 9 section 3 3 6 Use the IBAT jumper to set the maximum battery charging current taking into account the battery parameters 7 Use the PBAT jumper to set to turn on off deep discharge batter...

Страница 9: ...i Z high impedance state PSU failure can be caused by the following events Short circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output in...

Страница 10: ...e power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge...

Страница 11: ...to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been condit...

Страница 12: ...www pulsar pl PSBS1012B BLUE POWER 12 Pulsar Siedlec 150 32 744 apczyca Poland Phone 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl...

Отзывы: