3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

EPS - absence of AC supply output

:  

-  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 
connected to ground (L level 

– 0V). In case of power loss, the PSU will switch the output into high impedance 

state hi-Z. 

relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the relay 

contacts. 

 

CAUTION!

  In  Fig.5.  the  contact  set  in  the  potential-free  status  corresponds  to  a  state  with  no  AC 

power (AC power failure). 
 
 

 

PSU 

– technical output indicating absence of DC voltage at the PSU

- OC type output indicating the PSU failure. In normal state (during correct operation) the output is connected to 
ground (L level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the output is switched 

into high impedance state 

– hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!

  In  the  Fig.5.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

LoB 

– technical output indicating battery voltage

:  

- OC type output. Under normal status (U

BAT

 > 46V) the output is connected to ground (L level 

– 0V). In case of 

decrease of battery voltage (U

BAT

 < 46V) the output is switched into high impedance state 

– hi-Z. 

     - relay output. In case of a battery voltage drop U

BAT

 < 46V, the contacts of the relay change over. 

The  power  supply  unit  does  not  feature  a  battery  detection  function.  In  the  case  of  no  battery  or  non  battery 
connected, the output is in the normal mode. 

 

 

CAUTION!

 In the Fig.5. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <46V). 

 
 

 

 

Fig. 4. Electrical diagram of OC outputs. 

 

Fig. 5. Electrical diagram of relay outputs. 

 

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU module output 

In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The 

voltage is restored automatically after removing the failure (overload). 

 
4.2 Battery-assisted operation.  

In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 

The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted operation, reducing voltage below 38V at the battery terminals will cause 
battery disconnection. 

 

 
4.3 Maintenance 

Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU  does  not  require  performing  any  specific  maintenance  measures.  However,  in 
case of significant dust ingress, it is recommended to clean the PSU with compressed air. 

 

Содержание PSBOC754813

Страница 1: ...PSBOC754813 v 1 0 PSBOC 54V 1 3A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 13 05 2016 ...

Страница 2: ...TS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Maintenanc...

Страница 3: ...bsence technical output relay type 5 PSU output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB output indicating battery low voltage OC type 10 V V DC supply output 11 L N 230V AC power connector PE protection connector 12 LED indication on the...

Страница 4: ...oad protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection polymer fuse Surge protection varistors Surge over voltage protection OVP 62V automatic recovery Deep discharge protection UVP U 38V 5 disconnection of the battery terminal Technical outputs EPS output indicating AC power failure PSU output indicating DC absence PSU failure ...

Страница 5: ...ounted in confined spaces in accordance with the 2nd environmental class with normal relative humidity RH 90 maximum without condensation and temperature from 10 C to 40 C The device shall be mounted in a metallic enclosure a cabinet an intended case In order to fulfil LVD and EMC requirements the rules for power supply encasing and screening shall be followed according to application During norma...

Страница 6: ...ted AC power absence is indicated by the AC diode going out green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short circuit or an overload the diode is off green LED Fig 2 element 3 indicates battery voltage level Under normal status UBAT 46V the diode is permanently illuminated In case of decrease of battery voltag...

Страница 7: ...rease of battery voltage UBAT 46V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 46V the contacts of the relay change over The power supply unit does not feature a battery detection function In the case of no battery or non battery connected the output is in the normal mode CAUTION In the Fig 5 the set of contacts shows a potential free st...

Страница 8: ...days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer...

Отзывы: