Fig 3. Mechanical view of the PSU. 

 
 

 
3. Operating status indication. 

 

3.1. LED indication 

 

The PSU is equipped with 3 LEDs on the PCB board:

 

 - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is 
indicated by the AC diode going out.  
Caution! LED indicates power absence if the outage lasts >10s. 

 

-  green  LED  (Fig.2,  element  2)  indicates  DC  power  at  the  PSU  output.  Under  normal  status  the  diode  is 
permanently illuminated. In case of a short circuit or an overload, the diode is off. 
 
- green LED  (Fig.2, element 3) indicates battery voltage level. Under normal status (U

BAT

 > 11,5V) the diode is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 11,5V) the diode is off. 

 
 
 
 
 
 
 
 
 
 

Содержание PSBOC751250

Страница 1: ...PSBOC751250 v 1 0 PSBOC 13 8V 5A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 1 from 28 03 2014 Supercedes edition...

Страница 2: ...ption 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indica...

Страница 3: ...sence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 FPS outpu...

Страница 4: ...y connection polymer fuse Surge protection varistors Surge over voltage protection OVP 16V automatic recovery Deep discharge protection UVP U 9 5V 5 disconnection of the battery terminal Technical out...

Страница 5: ...tion and temperature from 10 C to 40 C The device shall be mounted in a metallic enclosure a cabinet an intended case In order to fulfil LVD and EMC requirements the rules for power supply encasing an...

Страница 6: ...by the AC diode going out Caution LED indicates power absence if the outage lasts 10s green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illum...

Страница 7: ...voltage OC type output Under normal status UBAT 11 5V the output is connected to ground L level 0V In case of decrease of battery voltage UBAT 11 5V the output is switched into high impedance state h...

Страница 8: ...t within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs o...