www.pulsar.pl 

 

 

 

 

PSBOC502418 

 

 

 

 

 
 

 
3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

EPS - absence of AC supply output

:  

-  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 
connected  to  ground  (L  level 

–  0V).  In  case  of  power  loss,  the  PSU  will  switch  the  output  into  high 

impedance state hi-Z. 

relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the 

relay contacts. 
 

 

CAUTION!

 In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 
 

 

PSU 

– technical output indicating absence of DC voltage at the PSU

-    OC  type  output  indicating  the  PSU  failure.  In  normal  state  (during  correct  operation)  the  output  is 
connected to ground (L level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the 

output is switched into high impedance state 

– hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!

  In  the  Fig.2.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

LoB 

– technical output indicating battery voltage

:  

-  OC  type  output.  Under  normal  status  (U

BAT

  >  23V)  the  output  is  connected  to  ground  (L  level 

– 0V). In 

case of decrease of battery voltage (U

BAT

 < 23V) the output is switched into high impedance state 

– hi-Z. 

      -  relay output. In case of a battery voltage drop U

BAT

 < 23V, the contacts of the relay change over. 

The power supply unit does not feature a battery detection function. In the case of no battery or non battery 
connected, the output is in the normal mode. 

 

 

CAUTION!

 In the Fig.2. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <23V). 

 

Fig. 4. Electrical diagram of OC outputs. 

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU module output 

In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The 

voltage is restored automatically after removing the failure (overload). 

 
4.2 Battery-assisted operation.  

In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 
 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted operation, reducing voltage below 19V at the battery terminals will cause 
battery disconnection. 

 
4.3 Maintenance 

Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU  does  not  require  performing  any  specific  maintenance  measures.  However,  in 
case of significant dust ingress, it is recommended to clean the PSU with compressed air. 

 

Содержание PSBOC502418

Страница 1: ...PSBOC502418 v 1 1 PSBOC 27 6V 1 8A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016...

Страница 2: ...S 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Ope...

Страница 3: ...sence technical output relay type 5 PSU output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU outpu...

Страница 4: ...oad protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection polymer fuse Surge protection varistors Surge over voltage protection OVP 3...

Страница 5: ...able Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a qualified installer holding relevant permits and licenses applicab...

Страница 6: ...ccordance with the signs colours 7 Once the tests and operation control have been completed the enclosure cabinet can be locked Fig 3 Mechanical view of the PSU 3 Operating status indication 3 1 LED i...

Страница 7: ...el 0V In case of decrease of battery voltage UBAT 23V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 23V the contacts of the relay change ove...

Страница 8: ...e and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the applicable...

Отзывы: