Pulsar PSBOC501235 Скачать руководство пользователя страница 3

www.pulsar.pl 

 

 

 

 

PSBOC501235 

 

 

 

 

 
 

1.2 Block diagram. (fig.1). 

 

Fig.1. Block diagram of the PSU. 

 

1.3 Description of PSU components and connectors.  

 

Table 1.  Elements of the PSU (see fig. 2).

 

Element no. 

Description 

[1] 

LED indicating presence of AC power

  

[2] 

LED indicating presence of DC power 

[3] 

LED indicating correct battery voltage 

[4] 

EPS -

 AC absence technical output 

– relay type 

[5] 

PSU -

 output indicating DC absence/PSU failure 

– relay type

 

[6] 

LoB-  

output indicating battery low voltage 

– relay type 

[7] 

EPS -

 AC absence technical output 

– OC  type

 

[8] 

PSU -

 output indicating DC absence/PSU failure - OC  type

 

[9] 

LoB - 

output indicating battery low voltage - OC  type 

[10] 

+V ,-V-

 DC supply output

 

[11] 

L-N  

230V/AC power connector, 

 PE protection connector 

[12] 

Connector of extra LED indication

 

[13] 

Battery connectors: +BAT =red, - BAT = black 

[14] 

V

ADJ

 - potentiometer,

 DC

 voltage adjustment

 

 

Fig. 2. The view of the PSU. 

Содержание PSBOC501235

Страница 1: ...PSBOC501235 v 1 1 PSBOC 13 8V 3 5A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 8 from 01 06 2016 Supercedes edition 7 from 10 04 2015...

Страница 2: ...TENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3...

Страница 3: ...sence technical output relay type 5 PSU output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU outpu...

Страница 4: ...d protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection polymer fuse Surge protection varistors Surge over voltage protection OVP 16V...

Страница 5: ...in confined spaces in accordance with the 2nd environmental class with normal relative humidity RH 90 maximum without condensation and temperature from 10 C to 40 C The device shall be mounted in a m...

Страница 6: ...AC power absence is indicated by the AC diode going out green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short circ...

Страница 7: ...0V In case of decrease of battery voltage UBAT 11 5V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 11 5V the contacts of the relay change ov...