www.pulsar.pl 

 

 

 

 

PSBOC3004850 

 

 

 

 

 
 

2.2. Installation procedure. 

1. Before installation of the power supply unit, make sure that 230VAC power if cut off.  
2. Mount the unit in the intended location.  
3. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to an appropriate PSU 
terminal (marked with 

 - earth symbol).

 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the ‘PE’ terminal. Using the PSU 
without a properly made and fully operational shock protection circuit is UNACCEPTABLE! 
It can cause a device failure or an electric shock. 
 

 

 

4. Connect load/loads to proper output connectors of the power supply (positive pole is marked as +V, 
negative pole as -V) 
5. Connect the technical outputs to the central or other device. 
6. Connect the battery in accordance with the signs (colours). 
7. Once the tests and operation control have been completed, the enclosure/cabinet can be locked. 

 

 

Fig 3. Mechanical view of the PSU. 

 
3. Operating status indication. 

 

3.1 LED indication 

 

The PSU is equipped with 3 LEDs on the PCB board:

 

 - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is 
indicated by the AC diode going out.  

 

-  green  LED  (Fig.2,  element  2)  indicates  DC  power  at  the  PSU  output.  Under  normal  status  the  diode  is 
permanently illuminated. In case of a short circuit or an overload, the diode is off. 
 
- green LED  (Fig.2, element 3) indicates battery voltage level. Under normal status (U

BAT

 > 46V) the diode is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 46V) the diode is off. 

 

 

Содержание PSBOC3004850

Страница 1: ...PSBOC3004850 v 1 0 PSBOC 54V 5A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 13 05 2016...

Страница 2: ...escription of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Techn...

Страница 3: ...tput indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC typ...

Страница 4: ...PSU systems 150 mA Battery charging current 0 5A 1A 2A jumper selectable Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery...

Страница 5: ...ature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse...

Страница 6: ...ly positive pole is marked as V negative pole as V 5 Connect the technical outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operat...

Страница 7: ...ease of battery voltage UBAT 46V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 46V the contacts of the relay change over The power supply un...

Страница 8: ...ays from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equi...

Отзывы: