Mechanical specifications (tab. 3). 

Enclosure dimensions 

199 x110 x 50 +23 [mm] (LxWxH)  (+/- 2) 

Net/gross weight 

0,89kg / 0,94kg 

Connectors 

power supply, technical outputs

: Φ0,63÷2,5   I/O PCB: Φ0,41÷1,63   

BAT battery outputs: 6,3F-2,5/40cm, 
Led indication output: 3-pin 5 mm connector 

Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Degree of Protection PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between PSU input circuit and output circuits (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Operating specifications (tab.5). 

Operating temperature 

-

10ºC...+40ºC  

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

2. Installation. 
 

2.1 Requirements 

The buffer PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable 

and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, without condensation) and temperature from -

10°C to +40°C. 

 
The  device  shall  be  mounted  in  a  metallic  enclosure  (a  cabinet,  an  intended  case).  In  order  to  fulfil  LVD 

and  EMC  requirements,  the  rules  for:  power-supply,  encasing  and  screening  shall  be  followed,  according  to 
application. The PSU provides voltage of 

U=54V DC 

current efficiency: 

  
                               1. Output current 2,3A + 0,5A battery charging

*

 

                               2. Output current 1,8A + 1A battery charging

                                

                 Total device c battery charging current: 2,8A max

.

*

 

 
 

2.2. Installation procedure. 

1. Before installation of the power supply unit, make sure that 230VAC power if cut off.  
2. Mount the unit in the intended location.  
3. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to an appropriate PSU 
terminal (marked with 

 - earth symbol).

 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall s

tick to one side of the ‘PE’ terminal. Using the PSU 

without a properly made and fully operational shock protection circuit is UNACCEPTABLE! 
It can cause a device failure or an electric shock. 
 

 

 

4. Connect load/loads to proper output connectors of the power supply (positive pole is marked as +V, 
negative pole as -V) 
5. Connect the technical outputs to the central or other device. 
6. Connect the battery in accordance with the signs (colours). 
7. Once the tests and operation control have been completed, the enclosure/cabinet can be locked. 

                                                 

*

 

See chart 1

 

Содержание PSBOC1554828

Страница 1: ...PSBOC1554828 v 1 0 PSBOC 54V 2 8A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 13 05 2016...

Страница 2: ...description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indi...

Страница 3: ...ating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB ou...

Страница 4: ...ection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection polymer fuse Surge protection...

Страница 5: ...paces in accordance with the 2nd environmental class with normal relative humidity RH 90 maximum without condensation and temperature from 10 C to 40 C The device shall be mounted in a metallic enclos...

Страница 6: ...ted AC power absence is indicated by the AC diode going out green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short c...

Страница 7: ...ease of battery voltage UBAT 46V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 46V the contacts of the relay change over The power supply un...

Страница 8: ...ays from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equi...