8. Check the output voltage (the PSU voltage without load and without a battery should amount to 27,5 V ÷ 27,7 V, 
with a battery or during battery charging process: 22 V÷27,6 V). If the value of the voltage requires adjustment, it 
should be set by the V

ADJ

 potentiometer, monitoring the voltage at the AUX output of the PSU. 

9. Connect the batteries in accordance with the markings: +BAT red to 'plus', -BAT black to 'minus’. The LB diode 
should be on during battery charging process. 
10. With the STOP button, activate or deactivate a dynamic battery test. Deactivating the test turns out the PSU 
failure indication at the APS FLT output, but it does not affect the protection system against complete battery 
discharge. 
11. Check the current consumption of the receivers allowing of the battery charging current no to exceed the total 
current efficiency of the PSU. 
12. Once the tests and operation control have been completed, the enclosure can be locked. 
 
 

8. Operation and use. 

 

8.1. Over voltage protection OVP at the PSU output. 
In  case  of  voltage  exceeding  31V±0.5V  at  the  regulator’s  output,  the  system  cuts  off  the  power  at  the 

outputs to protect the battery and the receivers from damage. The outputs will be battery-powered. The protection 
system is indicated by illuminating of the OVP red LED on the pcb board, PSU FLT output status change opening 
state,  acoustie and appropriate message on the PSU front panel. 

 
8.2 Overload of the PSU. 
The  PSU  has  been  equipped  with  a  LED  OVL  (overload)  indicator  light  on  the  pcb.  It  informs  about  the 

output  overload  status.  If  the  nominal  current  of  the  PSU  is  exceeded,  the  indicator  light  will  be  lit  and  the 
microprocessor  will  proceed  to  a  specially  implemented  procedure.  If  the  overload  threatens  the  PSU’s  power 
grade, the control system will decide about a disconnection of the AUX output. Restart will occur after 1 minute.  

 
8.3 Short circuit at the PSU output. 

 

In the case of a short circuit at the AUX, BAT output (load 200% ÷ 250% of the PSU power) or a reverse 

polarity  connection,  the  F

BAT

  fuse  in  the  battery  circuit  becomes  permanently  damaged  and  the  restoration  of  the 

voltage at the BAT output requires replacement of the fuse. 

 
8.4 Battery replacement. 

The battery replacement of the LCD panel should be done when the PSU is supplied from mains or a battery. This 
will prevent the time settings from erasing 

 
CAUTION! 
The  removed  batteries  ought  to  be  stored  in  a  dedicated  place.  The  poles  should  not  be 
reversed. The use of the batteries of a different kind is forbidden. Tampering with the battery 
may lead to its explosion. 

 

8.5. Maintenance. 
Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU      does  not  require  performing  any  specific  maintenance  measures.  However,  in 
the  case  of  significant  dust  level,  clean  its  interior  with  compressed  air.  In  the  case  of  a  fuse replacement,  use  a 
replacement of the same parameters. 

 
 
 
 
 
 
 
 
 
 
 

 

 

 
 

Содержание PSBEN 5024C

Страница 1: ...PSBEN 5024C LCD v 1 0 PSBEN 27 6V 5A 2x17Ah EN LCD Buffer switched mode power supply unit EN Edition 2nd 14th Sep 2012 Supersedes the 1st 25th April 2012 edition...

Страница 2: ...17 Setting the communication address 18 3 4 3 Desktop 18 Setting the language of messages 19 Setting the date 19 Setting the time 20 Setting the highlighting 20 Setting the contrast 21 3 5 ACOUSTIC IN...

Страница 3: ...S 29 7 2 INSTALLATION PROCEDURE 29 8 OPERATION AND USE 30 8 1 OVER VOLTAGE PROTECTION OVP AT THE PSU OUTPUT 30 8 2 OVERLOAD OF THE PSU 30 8 3 SHORT CIRCUIT AT THE PSU OUTPUT 30 8 4 BATTERY REPLACEMENT...

Страница 4: ...f access password protected PSU s operation history failure history real time clock battery backed optical indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC...

Страница 5: ...2 6A 3A battery charge Total current of the receivers battery 5 6A max In case of power decay a battery back up is activated immediately The PSU is housed in a metal enclosure colour RAL 9005 black w...

Страница 6: ...on on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZZER acoustic indicator 8 FBAT fuse in the battery circuit 9 Connectors AC AC power input BAT DC power...

Страница 7: ...ement no Description 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector P...

Страница 8: ...atus indication 3 1 Control panel The PSU is equipped with a panel with buttons and an LCD display which enables reading all available parameters of the device The buttons are for selecting and approv...

Страница 9: ...lay The main screen of the LCD display shows basic electrical parameters and informs about the current PSU state Fig 5 The main screen Table 4 Description of the symbols on the main screen Screen fiel...

Страница 10: ...status during operation Highlighting of an element informs about an active state and reflects the status of LEDs on the pcb of the PSU see table 1 12 Fig 7 Screen parameters of the PSU Table 5 Descrip...

Страница 11: ...analysis of the values shown on the chart the time range of the chart screen can be adjusted in the bottom axis Here are the available ranges 8h 24h 2days week weekly In order to change the displayed...

Страница 12: ...erates 3 levels of access to configuration which limit the possibility of changing the PSU s settings from the level of the LCD desktop They are protected with separate passwords Keypad password locks...

Страница 13: ...ear with or choose the right level of the password confirm your choice with the SET button with or enter the first digit confirm your choice with the SET button with or enter the second digit confirm...

Страница 14: ...swords have been lost there is a procedure that will allow reassigning the passwords Please do as follows a unplug the PSU from the AC network and the battery for at least 10 seconds b press the STOP...

Страница 15: ...to the PSU NO battery not connected to the PSU see chapter 4 6 Battery test YES battery test on NO battery test off see chapter 4 3 Battery protection YES battery protection function disconnection on...

Страница 16: ...onfirm your choice with the SET button Setting the battery test with or choose the Battery test menu press the SET button you will see the prompt at the end of the line with or set YES or NO YES batte...

Страница 17: ...nction disconnection on NO battery protection function disconnection off confirm your choice with the SET button Setting the EPS output lag with or choose the EPS output lag menu press the SET button...

Страница 18: ...mputer confirm your choice with the SET button 3 4 3 Desktop The facility is only available after entering the correct user s or installer s password The Desktop menu enables setting the current date...

Страница 19: ...you will see the prompt at the end of the line with or choose the language of messages confirm your choice with the SET button Setting the date with or choose the Date menu press the SET button the pr...

Страница 20: ...ection with or set the minutes press the SET button the prompt will move to the second section with or set the seconds approve the settings with the SET button Setting the highlighting Intensity of th...

Страница 21: ...t to the constant option with or change the setting into 60 s press the SET button the prompt will move to the end of the line with or set the demanded screen brightness approve your choice with the S...

Страница 22: ...se In case of a power failure the PSU will switch the output into the open state after a period of time determined by the EPS output lag facility see 3 4 2 table 7 APS FLT output indicating battery fa...

Страница 23: ...IN technical input has been implemented with galvanic isolation between the PSU s systems and the devices attached Fig 16 Electrical diagram of the EXT IN input The electrical diagram below shows the...

Страница 24: ...ET button Then choose PSU Battery protection YES NO see chapter 3 4 2 table 7 or from the pcb level during mains powered PSU operation press the STOP button on the main board and hold it for 3 seconds...

Страница 25: ...age of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 19 WI FI communication with the use of the WI FI INTW interface 5 2 Commun...

Страница 26: ...USB TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 22 USB TTL communicatio...

Страница 27: ...put voltage adjustment range 24V 29 V Ripple voltage 160 mV p p max Current consumption by the PSU systems during batter assisted operation I 26mA I 17 mA highlighting of the LCD desktop is off Batter...

Страница 28: ...cables can be led Convectional cooling Table 12 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input ne...

Страница 29: ...3 7 and guarantees indication in case of any attempts of detaching the device from the mounting surface Fig 24 Fixing a tamper grip 2 Connect the power cables 230Vac to L N terminals of the PSU Connec...

Страница 30: ...tie and appropriate message on the PSU front panel 8 2 Overload of the PSU The PSU has been equipped with a LED OVL overload indicator light on the pcb It informs about the output overload status If t...

Страница 31: ...high output voltage Output voltage 29 4V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 28V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of...

Страница 32: ...eriod mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by th...

Отзывы: