The main panel of the program has been formulated in such a way that it is possible to divide it into smaller 

areas, depending on the number of power supplies.  

The program enables both a visualisation and an analysis of the received data. Exceeding of the acceptable 

parameters  is  indicated  by  highlighting  in  red  the  appropriate  area  or  by  twinkling  of  the  indicator.  Particular  tabs 
contain a chart with an overview of the PSU parameters and failure memo along with the information about status 
and the electrical specifications of the technical outputs. 

 

The ”Power Security” program is available on our website: 

www.pulsar.pl

  

Its detailed description can be found in the manual of the program. 

 

 
6. Technical specifications.  

Electrical specifications (tab.10). 
Mechanical specifications (tab.11). 
Operation safety (tab.12). 
Operating specifications (tab.13). 
Factory settings (tab. 14). 

 

Table 10. Electrical specifications. 

PSU type 

A, protection grade 1÷3, II environmental class 

Mains supply 

230V/AC  (-15%/+10%) 

Current consumption 

0,6 A  

Power frequency 

50Hz 

PSU’s power 

78 W 

Efficiency 

70% 

Output voltage 

11,0V÷13,8 V DC – buffer operation 
10,0V÷13,8 V DC – battery-assisted operation 

Output current 

- for grades 1, 2:  

 

 

 

Io = 1,4A + 3A battery charge 

- for grade 3: 

 

 

Io = 0,56A + 3A battery charge - (connection with ARC 

required, compliant with 9.2 – PN-EN 50131-1) 
 

Io = 0,28A + 3A battery charge 

- for general use: 
           Io =5A 

(without bartery) 

 

Io =4,4A + 0,6A battery charge 

 

Io = 3,5A + 1,5A battery charge 

           Io = 2,8A + 2,2A battery charge 
           Io = 2A + 3A battery charge 

Output voltage setting, escalation and keeping 
time 

5ms / 40ms / 18ms 
 

Output voltage adjustment range 

12 V÷ 14,5 V  

Ripple voltage 

30 mV p-p max. 

Current consumption by the PSU systems 
during batter-assisted operation 

I = 26mA  
I = 17 mA – highlighting of the LCD desktop is off 

Battery charging current 

0,6A/ 1,5A/ 2,2A/ 3A –I

BAT 

jumper selectable

 

Low battery voltage indication 

Ubat < 11,5V, during battery-assisted operation 

Over voltage protection OVP 

U>15,5V, disconnection of the output voltage, automatic return 
(AUX+ disconnection)

 

Short circuit protection SCP 

200% ÷ 250% of the PSU power - current limiting and/or fuse 
fault in the battery circuit (fuse-element replacement required)

 

Overload protection OLP 

Program - equipment 

Battery circuit protection SCP and reverse 
polarity connection 

T6,3 A- current limiting, F

BAT

 fuse (failure requires fuse-element 

replacement)

 

Deep discharge battery protection UVP 

U<10,0 V (± 2%) – disconnection (-BAT) of the battery, 
adjustment from the 

LCD desktop’s level 

- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

- time lag, approx. 5s/140s/17m/2h 20m (+/-5%) 
- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

Technical outputs: 
- EPS FLT; output indicating AC power failure 
 
- APS FLT; output indicating battery failure 
 
- PSU FLT; output indicating PSU failure  
 
- TAMPER output indicating enclosure opening 
and 

detachment

 from the mounting surface 

- microswitches x2, NC contacts (enclosure closed and fixed to 
the mounting surface)

, 0,5A@50V DC (max.) 

Содержание PSBEN 5012C/LCD

Страница 1: ...PSBEN 5012C LCD v 1 0 PSBEN 13 8V 5A 17Ah EN LCD Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Страница 2: ...the EPS output lag 16 Setting the communication address 17 3 4 3 Desktop 17 Setting the language of messages 18 Setting the date 18 Setting the time 19 Setting the highlighting 19 Setting the contrast...

Страница 3: ...QUIREMENTS 30 7 2 INSTALLATION PROCEDURE 30 8 OPERATION AND USE 31 8 1 OVER VOLTAGE PROTECTION OVP AT THE PSU OUTPUT 31 8 2 OVERLOAD OF THE PSU 31 8 3 SHORT CIRCUIT AT THE PSU OUTPUT 31 8 4 BATTERY RE...

Страница 4: ...operation history failure history real time clock battery backed optical indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs ou...

Страница 5: ...d to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 3A battery charge General use if the PSU is not mounted within an installation which is PN EN 50131 compli...

Страница 6: ...off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZZER acoustic indicator 8 FBAT fuse in the battery circuit 9 Connectors AC AC power input BAT DC power battery output A...

Страница 7: ...N 230V AC power connector PE connector 6 Battery connectors positive BAT red negative BAT black 7 Grip of tamper resistance Fig 3 The view of the PSU 3 Operating status indication 3 1 Control panel T...

Страница 8: ...lay The main screen of the LCD display shows basic electrical parameters and informs about the current PSU state Fig 5 The main screen Table 4 Description of the symbols on the main screen Screen fiel...

Страница 9: ...tatus during operation Highlighting of an element informs about an active state and reflects the status of LEDs on the pcb of the PSU see table 1 12 Fig 7 Screen parameters of the PSU Table 5 Descript...

Страница 10: ...analysis of the values shown on the chart the time range of the chart screen can be adjusted in the bottom axis Here are the available ranges 8h 24h 2days week weekly In order to change the displayed...

Страница 11: ...erates 3 levels of access to configuration which limit the possibility of changing the PSU s settings from the level of the LCD desktop They are protected with separate passwords Keypad password locks...

Страница 12: ...ear with or choose the right level of the password confirm your choice with the SET button with or enter the first digit confirm your choice with the SET button with or enter the second digit confirm...

Страница 13: ...swords have been lost there is a procedure that will allow reassigning the passwords Please do as follows a unplug the PSU from the AC network and the battery for at least 10 seconds b press the STOP...

Страница 14: ...to the PSU NO battery not connected to the PSU see chapter 4 6 Battery test YES battery test on NO battery test off see chapter 4 3 Battery protection YES battery protection function disconnection on...

Страница 15: ...onfirm your choice with the SET button Setting the battery test with or choose the Battery test menu press the SET button you will see the prompt at the end of the line with or set YES or NO YES batte...

Страница 16: ...nction disconnection on NO battery protection function disconnection off confirm your choice with the SET button Setting the EPS output lag with or choose the EPS output lag menu press the SET button...

Страница 17: ...mputer confirm your choice with the SET button 3 4 3 Desktop The facility is only available after entering the correct user s or installer s password The Desktop menu enables setting the current date...

Страница 18: ...you will see the prompt at the end of the line with or choose the language of messages confirm your choice with the SET button Setting the date with or choose the Date menu press the SET button the pr...

Страница 19: ...ection with or set the minutes press the SET button the prompt will move to the second section with or set the seconds approve the settings with the SET button Setting the highlighting Intensity of th...

Страница 20: ...t to the constant option with or change the setting into 60 s press the SET button the prompt will move to the end of the line with or set the demanded screen brightness approve your choice with the S...

Страница 21: ...y the output is close In case of a power failure the PSU will switch the output into the open state after a period of time determined by the EPS output lag facility see 3 4 2 table 7 APS FLT output in...

Страница 22: ...IN technical input has been implemented with galvanic isolation between the PSU s systems and the devices attached Fig 16 Electrical diagram of the EXT IN input The electrical diagram below shows the...

Страница 23: ...attery test facility can be switched off Deactivating activating the test enter the PSU settings from the level of the LCD desktop by pressing the SET button Then choose PSU Battery protection YES NO...

Страница 24: ...3 7h 2 2 J1 J2 J3 10h12m 1 5 J1 J2 J3 25h30m 0 6 J1 J2 J3 4 6 Operation without a battery In case of an expected PSU operation without an attached battery make a necessary configuration setting from t...

Страница 25: ...ces 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz freque...

Страница 26: ...Ethernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correct...

Страница 27: ...ation with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and mem...

Страница 28: ...4 4A 0 6A battery charge Io 3 5A 1 5A battery charge Io 2 8A 2 2A battery charge Io 2A 3A battery charge Output voltage setting escalation and keeping time 5ms 40ms 18ms Output voltage adjustment rang...

Страница 29: ...x 355 x 100 8 WxHxD mm 2 Fixing 300 x 318 x 6 x4 WxH Fitting battery 17Ah 12V SLA max Net gross weight 6 0 6 4 kg Enclosure Steel plate DC01 1mm colour RAL 9005 black Closing Cheese head screw x2 at...

Страница 30: ...and assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 7 2 Installation procedure CAUTION Before installation cut off the voltage in the 2...

Страница 31: ...peration and use 8 1 Over voltage protection OVP at the PSU output In case of voltage exceeding 15 5V 0 5V at the regulator s output the system cuts off the power at the outputs to protect the battery...

Страница 32: ...igh output voltage Output voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of...

Страница 33: ...ssibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are car...

Отзывы: