   Table 7. List of PSU failure codes. 

Failure 

code 

Information 

Technical 

output 

activation 

Additional information 

Additional 

information 

F01 

AC power fail! 

EPS FLT 

- No AC mains supply 
- F

MAINS 

fuse failure 

 

F02 

AUX fuse fail! 

PSU FLT 

- Blown F

AUX

 fuse 

- AUX output overload 

 

F03 

BAT fuse fail! 

APS FLT  

- Blown F

BAT

 fuse

 

- Short circuit in the battery circuit 
- Short circuit in the AUX output circuit 

 

F04 

Output overload! 

PSU FLT 

- PSU overload 

Section 5.9 

F05 

Battery fail! 

APS FLT 

- Worn out battery 
- Undercharged battery 
- Battery not connected 

Section 5.5 

Section 6 

F06 

High AUX voltage! 

PSU FLT  

- Output voltage over 29.4V 

 

F07 

High battery voltage! 

PSU FLT 

- Battery voltage >28V 

 

F08 

Charge circuit fail! 

PSU FLT 

- The output voltage of the PSU set  too low , 
below 26V 
- Battery charging circuit failure 

 

F09 

Low AUX voltage! 

PSU FLT 

- Output voltage  below 23,6V  
(during buffer operation) 

 

F10 

Low battery voltage! 

APS FLT 

- the battery voltage has dropped below 23V 
(during battery-assisted operation) 

 

F11 

Low battery volt. 

– 

off! 

APS FLT 

- the battery voltage has dropped below 20V 
(during battery-assisted operation) 

 

F12 

External input EXTi! 

 

- Activation of the input of collective failure 
EXT IN 

Section 5.6 

F13 

PSU cover opened! 

PSU FLT 

  

 

F50-F54 

Internal supply fail! 

PSU FLT 

- service codes 

 

F60 

No communication 

PSU FLT 

- no communication with LCD panel 

 

F61-F64 

Control panel fail 

PSU FLT 

- service codes 

 

F65 

Access unlocked 

 

- passwords unlocked 

 

 
  Table 8. List of PSU message codes. 

Message 

code 

Description 

I00 

Power supply start-up 

I01 

AC power back 

I02 

AUX fuse replaced 

I03 

BAT fuse replaced 

I04 

Battery OK 

I05 

Battery test 

– START 

I06 

PSU cover closed 

 

Table 9. Optical indication of failure with the PSU LED on the PCB of the PSU. 

The number of 

flashes of the PSU 

LED on the PCB of 

the power supply 

Failure 

code 

Failure description 

F06 

High AUX voltage! 

F07 

High battery voltage! 

F08 

Charge circuit fail! 

F09 

Low AUX voltage! 

F50-F54 

F60 

Internal supply fail! 
No communication 

F13 

PSU cover opened! 

Содержание PSBEN 2024C

Страница 1: ...PSBEN 2024C v 1 1 PSBEN 27 6V 2A 2x17Ah EN Buffer switch mode power supply unit EN Edition 6 from 02 02 2015 Supercedes edition 5 from 18 06 2014 LED Version...

Страница 2: ...ss Adr applies to cooperation with PowerSecurity 19 5 3 4 Setting the transmission speed trS applies to cooperation with PowerSecurity 20 5 3 5 Setting the parity of the transmission trP applies to co...

Страница 3: ...ww pulsar pl PSBEN2024C BLACK POWER 3 8 TECHNICAL PARAMETERS 31 TABLE 13 ELECTRICAL PARAMETERS 31 TABLE 14 MECHANICAL PARAMETERS 32 TABLE 15 SAFETY OF USE 32 9 TECHNICAL INSPECTIONS AND MAINTENANCE 33...

Страница 4: ...overcharge protection battery output protection against short circuit and reverse polarity connection jumper selectable battery charging current 0 2A 0 6A 1A 1 5A remote battery test additional module...

Страница 5: ...ES YES No battery charge YES YES Low output voltage YES YES High output voltage YES YES PSU failure YES YES Surge protection YES YES Short circuit protection YES YES YES YES Overload protection YES YE...

Страница 6: ...standard Output current 0 28A 1 5A battery charge General use if the PSU is not mounted in an installation complaint with the EN 50131 standard the acceptable current efficiency amounts to 1 Output cu...

Страница 7: ...ACK POWER 7 3 2 Block diagram The PSU is manufactured based on a high duty system of DC DC converter The microprocessor system is responsible for full diagnostics of the PSU and battery parameters Fig...

Страница 8: ...button disconnection of the PSU during battery assisted operation pin activation of the acoustic indication indication on indication off Caption jumper on jumper off VADJ potentiometer DC voltage adju...

Страница 9: ...no Description Insolation transformer PSU board see Tab 1 fig 2 TAMPER micro switch contacts of tamper resistance NC FMAINS fuse in the supply circuit 230V AC L N power supply connector 230V AC PE pro...

Страница 10: ...llation is one of the requirements of the EN 50131 6 standard Fig 4 Fixing a tamper grip 2 Connect the power cables 230VAC to L N terminals of the PSU Connect the ground wire to the terminal marked by...

Страница 11: ...urrent consumption of the receivers taking into account the battery charging current so as not to exceed the total current efficiency of the PSU 12 Once the tests are completed close the PSU cover Tab...

Страница 12: ...5 Control panel Table 5 The description of the buttons and LEDs of the LED panel Description Additional information moves the pointer on the screen next screen selection selection approval red LED in...

Страница 13: ...he voltage indicator displays the measured output voltage at the AUX output If the voltage drops below 26V during operation with activated battery test or exceeds 29 4V the PSU will indicate a failure...

Страница 14: ...tically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failures 5 2 4 Current fai...

Страница 15: ...e code will be automatically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failu...

Страница 16: ...Low battery voltage APS FLT the battery voltage has dropped below 23V during battery assisted operation F11 Low battery volt off APS FLT the battery voltage has dropped below 20V during battery assist...

Страница 17: ...bols Symbol Description Additional information Battery test tSt On battery test on OFF battery test off Sections 5 3 1 LED display dimmer On dimmer ON OFF dimmer OFF Sections 5 3 2 Communication addre...

Страница 18: ...your choice with the OK button in order to return to the main menu simultaneously press the rightmost and leftmost buttons on the LED panel Deactivating activating the test with the STOP button on the...

Страница 19: ...mer on OFF dimmer off confirm by pressing OK in order to return to the main menu simultaneously press the rightmost and leftmost buttons 5 3 3 Setting the communication address Adr applies to cooperat...

Страница 20: ...ss parity and speed should have the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 However if it is connected to the network...

Страница 21: ...e panel use the or buttons in order to set the required communication mode 8N2 8E1 factory setting 8O1 confirm by pressing OK in order to return to the main menu simultaneously press the rightmost and...

Страница 22: ...dicates the PSU failure Under normal status during correct operation the output is close In case of a failure the PSU will switch the output into the open state Any failures can be triggered by the fo...

Страница 23: ...ee a correct cooperation between the module and the EXT IN input the VEXT jumper must be on and the connections are to be made accordingly to the diagram below Fig 11 Example of a connection with the...

Страница 24: ...ed by the OVP yellow LED on the PCB board and the PSU FLT output 5 9 PSU overload The PSU is fitted with the LED OVL overload on the PCB and indicator on the LED panel informing about output overload...

Страница 25: ...s voltage The protection mode is off when the PBAT jumper is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing...

Страница 26: ...charging time The PSU has a battery circuit charged with direct current The current selection is done with use of the IBAT jumpers The table below shows how long does it take to charge a fully dischar...

Страница 27: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 6 4 7 1 Communication via the USB TTL interface The easiest way of...

Страница 28: ...against adverse environmental conditions Fig 14 Ethernet network communication using the RS485 INTRE interface 7 3 The Wi Fi wireless communication The Wi Fi wireless communication can be implemented...

Страница 29: ...nst adverse environmental conditions Fig 16 The Wi Fi communication using the RS485 WIFI INTRW interface 7 4 RS485 network communication Another type of network communication is the RS485 communicatio...

Страница 30: ...the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orient...

Страница 31: ...the output voltage AUX disconnection automatic return Short circuit protection SCP Electronic current limitation and or FBAT fuse failure in the battery circuit requires fuse replacement Automatic ret...

Страница 32: ...et gross weight 5 9 6 4 kg Enclosure Steel plate DC01 1mm color RAL 9005 black Closing Cheese head screw x2 at the front lock assembly possible Terminals Supply 0 63 2 50 AWG 22 10 Outputs 0 51 2 AWG...

Страница 33: ...equire any specific maintenance however its interior should be cleaned with compressed air if it is used in dusty conditions In case of fuse replacement use only compatible replacement parts Technical...

Страница 34: ...epted the manufacturer is obliged to provide warranty repairs at the earliest convenience however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair...

Отзывы: