background image

 

Electrical strength of insulation: 
-  between  input  (network)  circuit  and  output  circuits 
of power-supply (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-
FG) 
-  between  output  circuit  and  PE  protection  circuit 
(O/P-FG) 

 
 
3000 V/AC min. 
 
1500 V/AC min. 
 
500  V/AC min. 

Insulation resistance: 
-  between  input  circuit  and  output  or  protection 
circuit 

 
100 M

, 500V/DC  

Storage temperature 

-20ºC...+60ºC 

Vibrations and impulse waves during transport 

according to PN-83/T-42106 

 
1.3. Output current vs temperature. 
 

 

 

 
 
 
 
 

Graph 1.  
Allowable output current from the power 
supply depending on ambient temperature.  

2. Installation. 

 
2.1. Requirements. 
 
The  buffer  power supply  shall  be  mounted  by  the  qualified  installer  having  appropriate  (required  and  necessary 

for  a  given  country)  permissions  and  qualifications  for  connecting  (operating)  230V/AC  installations  and  low  voltage 
installations.  The  device  shall  be  mounted  in  closed  rooms,  according  to  the  environment  class  II,  of  the  normal  air 
humidity (RH=90% max. without condensation) and the temperature within the range from -10°C to +40°C. 

 
The power supply shall be mounted in a close casing (a cubicle, a terminal device) and in order to fulfill LVD and 

EMC requirements the rules for power-supply, encasing and shielding shall be observed according to application. 

Due to the power supply design, the PE wire has to be connected to the corresponding connector of the 

supply unit. Operation without proper grounding of the power supply is not allowed! 

 
Prepare  the power  supply  loading  balance  before  installation.  Under  normal  operation,  the  total  current 

drawn by the device  may not exceed I = 1 A.  Maximum battery charging current: 0,5 A. Total device  c 
battery: 1,5 A max. 

 
 
2.2. Installation procedure. 

1. Before beginning installation, ensure that the power in the 230V AC power supply circuit is disconnected. 
2. Install the unit in the previously selected place. 
3. Connect the 230VAC power leads. Connect the PE cable (yellow-green) to an appropriate terminal on the 
power supply unit (marked with 

). 

 

The circuit of the shock protection shall be performed with a particular care, i.e. the yellow and green 

protection wire of the power cable shall be connected from one side to the terminal marked by the 

symbol of 

  in the casing of the power-supply. Operation of the power-supply without the properly 

made and fully operational circuit of the shock protection is 

UNACCEPTABLE! 

 It can result in failure of devices and electric shock. 

 

 

4. Connect load/loads to proper output connectors of the power supply (positive end is marked as +V, 
negative as -V). 
5. Connect battery to the unit according marks (colors). 
6. After the completion of tests and trial activation, close the housing, cabinet etc. 

 
 
 