Pulsar PSACH01246EKO Скачать руководство пользователя страница 5

www.pulsar.pl 

PSACH01246EKO 

   

 

 

Operating specifications (tab.5). 

Operating temperature 

-

25ºC...+40ºC 

Storage temperature 

-

25ºC...+60ºC 

Relative humidity 

10%...90% without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 
2. Installation. 
 

2.1 Requirements 

The  AC/AC  power  supply  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and required for a given country) for 230  V interference  and low-voltage  installations. The  unit  should 
be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, without condensation) and temperature from -25

°C to +40°C (table 5). The PSU shall work in 

a vertical or horizontal position.  

Before mounting the PSU module, perform a load balance. During normal operation, total current drawn by 

the receivers cannot exceed

 I=6 A.  

As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
2.2 Installation procedure. 

 

 

Before installation, make sure that the voltage in the 230 V power-supply circuit is cut off. To 

switch power off, use an external switch, in which the distance between the contacts of all 

poles in the disconnection state is not less than 3 mm. 

 

 

1.

 

Mount the PSU in a selected location and connect the wires.

 

2. Connect the power cables to the L-N terminals.  

 

 

The  shock  protection  circuit  shall  be  performed  with  a  particular  care,  i.e.  the  yellow  and 

green wire coat of the power cable shall stick to one side of the terminal marked with the '

earth  symbol  in  the  PSU  enclosure.  Operation  of  the  power  supply  without  a  properly  made 
and  fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  result  in  device 
damage or an electric shock. 

 

 

3. Connect the ground wire to the terminal marked by the earth symbol  

”. Use a three-core cable (with a yellow 

and  green  protection  wire 

)  to  make  the  connection.  Lead  the  cables  to  the  appropriate  terminals  of  the 

connection board through the bushing. 
4. Connect the conductors of consumers to the terminals 24 V 

– 0 V and/or  the terminal box on the power-supply 

unit (the balance of the power-supply load shall be performed). 
5. Restore the mains power ~230 V. 
6. Once the tests and control operation have been completed, close the PSU. 
 

3. Operation and use. 

 

3.1 Overload or short circuit at the PSU output 

The 24 V 

– 0 V PSU outputs are protected against a short circuit with glass fuse. If the PSU is loaded with 

current  exceeding  6  A 

(110%for  ÷  150%  of  S  power),  there  occurs  the  F2  and/or  F1  fuse  damage  in  the  230  V 

circuit. In case of a failure, replace the fuse of the same parameters. 

 
 
 

 

Содержание PSACH01246EKO

Страница 1: ...PSACH01246EKO v 1 0 PSACH 24VAC 6A 1x6A AC power supply for 1 rotating camera ABS enclosure EN Edition 1 from 14 04 2020 Supersedes the edition ...

Страница 2: ...e warranty 2 year from the production date Sample power supply unit for rotating camera supplied with AC voltage Schematic diagram of a power supply CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operation and use 3 1 Overload or short circuit at the PSU out...

Страница 3: ...rheat OHP The PSU is housed in a ABS enclosure 1 2 Block diagram Fig 1 Block diagram of the PSU 1 3 Description of PSU components Tab 1 Elements of the power supply unit Element no Fig 2 Description 1 Isolation transformer 2 AUX 24 V 0 V secondary voltage connector devices power supply SEC 3 F2 fuse in the secondary voltage circuit 4 F1 fuse in the power supply circuit 230 V PRI 5 L N connector 23...

Страница 4: ...ations tab 3 External dimensions of the PSU W 160 H 160 D 90 2 mm Mounting dimensions PSU W1 126 H1 145 2 mm Height glands H2 25 mm The number of cable glands Ø cables 2 pcs 4 8mm Net gross weight 2 4 2 5 kg Enclosure ABS IP65 light grey Closing Cheese screw x 4 at the front Connectors Power supply Φ0 63 2 50 AWG 22 10 Outputs Ф0 63 2 50 AWG 22 10 Notes The enclosure has a removable mounting board...

Страница 5: ...stallation make sure that the voltage in the 230 V power supply circuit is cut off To switch power off use an external switch in which the distance between the contacts of all poles in the disconnection state is not less than 3 mm 1 Mount the PSU in a selected location and connect the wires 2 Connect the power cables to the L N terminals The shock protection circuit shall be performed with a parti...

Страница 6: ... a significant dust level clean the interior with compressed air In case of a fuse replacement use one of the same parameters WEEE MARK According to the EU WEE Directive It is required not to dispose of electric or electronic waste as unsorted municipal waste and to collect such WEEE separately Pulsar sp j Siedlec 150 32 744 Łapczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro puls...

Отзывы: